| Date |
Text |
| 2007-04-04 07:45:09 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | |
| | FBCFLORIDA BUILDING CODE 2004 |
| | FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING |
| | CODE |
| | FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC* |
| | CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 |
| | |
| | ***NOTE - PLAN REVIEW COMMENTS WERE CHANGED 4/12/07 TO |
| | DOCUMENT ITEMS DISCUSSED/NEGOTIATED WITH ARCHITECT AND |
| | CONTRACTOR IN A MEETING 4/11/07** |
| | ***NOTE THAT A LIFE SAFETY PLAN WAS ACCEPTED DURING THE |
| | PLAN REVIEW PROCESS DURING REVIEW #3.THIS IS THE 4TH |
| | COURTESY REVIEW REFERRED TO IN THE PLAN REVIEW |
| | NOTES.*** |
| | |
| | 1-8.) ADDRESSED. |
| | |
| | 9.)A SEPARATE PERMIT WILL BE REQUIRED FOR THE SIGN |
| | SHOWN ON A-0.1.SEPARATE PLANS AND PERMIT APPLICATION |
| | WILL BE REQUIRED.INFORMATIONAL ONLY; THIS IS NOT |
| | REQUIRED TO BE ADDRESSED AT THIS TIME. |
| | |
| | 10-12.)ADDRESSED. |
| | |
| | 13.)EXTRA FP1 SHEETS WERE SUBMITTED.PLEASE PROVIDE |
| | THREE ORIGINALS, ONE PUT INTO EACH ROLLED PERMIT SET. |
| | |
| | THREE SETS SUBMITTED.PLEASE KEEP THE THREE SETS IN |
| | THE PACKAGE.THEY ARE NOT CURRENTLY A PART OF THE |
| | BOUND SET.THIS IS ACCEPTABLE; HOWEVER, PLEASE ENSURE |
| | THAT THEY ARE NOT INADVERTENTLY REMOVED FROM THE |
| | PACKAGE AS THIS IS A STATUTORY REQUIREMENT AND THE |
| | PERMIT CANNOT BE ISSUED WITHOUT SPRINKLER PLANS. |
| | |
| | 14-15.) ADDRESSED. |
| | |
| | 16.)A NEW LIFE SAFETY PLAN WAS ACCEPTED DURING THE |
| | PLAN REVIEW PROCESS.NOTE THAT THE ORIGINAL LS PLAN |
| | SUBMITTED DID NOT PROPERLY ADDRESS THE COMMENTS AND A |
| | NEW LS PLAN WAS SUBMITTED AFTER DISCUSSION WITH THE |
| | ARCHITECT. |
| | |
| | 3RD REVIEW:ONLY ONE ACCESSIBLE EXIT SHOWN FOR EACH |
| | AREA.BASED ON OCCUPANT LOAD, TWO EXITS ARE REQUIRED |
| | FOR THE DISTRIBUTION AREA, TWO EXITS ARE REQUIRED FOR |
| | THE OFFICE AREA.PROVIDE ALL INFORMATION FOR EXITING |
| | ON THE LIFE SAFETY PLAN FOR THE ACCESSIBLE EXITS. |
| | REVIEW WAS STOPPED AND I AGREED TO ACCEPT A NEW LIFE |
| | SAFETY PLAN IN ATTEMPT TO ISSUE THE PERMIT IF ALL OTHER |
| | ITEMS WERE ADDRESSED FROM ALL PLAN REVIEWERS, INCLUDING |
| | MY LIST.HOWEVER, THE LIFE SAFETY PLAN SUBMITTED WAS |
| | NOT COMPLIANT. |
| | |
| | FOURTH (COURTESY) REVIEW.THE NEW LIFE SAFETY PLAN |
| | SHOULD BE REVISED TO SHOW THE FOLLOWING FOR THE SECOND |
| | ACCESSIBLE MEANS OF EGRESS FROM THE DISTRIBUTION AREA: |
| | |
| | EXIT LIGHTS, FBC1006.3 |
| | EXIT CAPACITY, FBC1004.1.3 |
| | DOOR SWING, FBC1008.1.2 |
| | TRAVEL DISTANCE, FBC1015 |
| | EGRESS CAPACITY, FBC1005 |
| | |
| | NOTE THAT TRAVEL DISTANCE IS SHOWN THROUGH THE MIDDLE |
| | OF SOME ROOMS; THIS IS USUALLY DONE AROUND THE |
| | PERIMETER OF THE ROOM, FBC1015.1. |
| | |
| | ALL OF THE ABOVE INFORMATION WAS PROVIDED ON THE LIFE |
| | SAFETY PLAN BUT DID NOT ADDRESS ACCESSIBLE MEANS OF |
| | EGRESS.SEE COMMENT 17, ACCESSIBLE MEANS OF EGRESS |
| | SHALL BE PROVIDED IN THE SAME NUMBER AS REQUIRED FOR |
| | EXITS BY LOCAL BUILDING/LIFE SAFETY REGULATIONS, |
| | FBC11-4.1.3(9).A LIFT WAS ADDED, EXITING THROUGH THE |
| | OFFICE AREA WAS DISCUSSED BUT NOTHING IS SHOWN ON THE |
| | PLAN; OTHER INFORMATION ABOVE NOT PROVIDED. |
| | |
| | 17.)FBC11-4.1.3(9), ACCESSIBLE MEANS OF EGRESS SHALL |
| | BE PROVIDED IN THE SAME NUMBER AS REQUIRED FOR EXITS BY |
| | LOCAL BUILDING/LIFE SAFETY REGULATIONS. A RAMP IS SHOWN |
| | AT THE BUILDING ENTRANCE, NO OTHER ACCESSIBLE EXITS |
| | SHOWN. |
| | |
| | 2ND REVIEW, THE RESPONSE LETTER STATES THAT ALL EXITS |
| | ARE ACCESSIBLE.SEE FBC11-3, DEFINITION OF EGRESS, |
| | MEANS OF; DOES NOT INCLUDE STAIRS, STEPS, OR |
| | ESCALATORS. |
| | |
| | (REVISED 4/12) 3RD COURTESY REVIEW, TWO EXITS ARE |
| | REQUIRED FROM THE DISTRIBUTION AREA AND TWO EXITS |
| | REQUIRED FROM THE OFFICE AREA.ONLY ONE ACCESSIBLE |
| | EXIT FOR EACH AREA IS SHOWN. |
| | |
| | (REVISED 4/12) 4TH REVIEW, REVISED LIFE SAFETY PLAN |
| | SUBMITTED DURING REVIEW; THERE IS STILL ONLY ONE |
| | ACCESSIBLE EXIT FROM THE DISTRIBUTION AREA, TWO |
| | REQUIRED BASED ON OCCUPANT LOAD. |
| | |
| | 18.)1ST/2ND REVIEW: THIS BUILDING REQUIRES MORE THAN |
| | ONE EXIT, SEE FBC1018.2.THIS WAS NOT ADDRESSED FOR |
| | ACCESSIBLE EXITS; ONLY ONE SHOWN. |
| | |
| | (REVISED 4/12) 3RD REVIEW:SEE COMMENT 17. |
| | |
| | (REVISED 4/12) 4TH COURTESY REVIEW:THERE IS NOW ONE |
| | ACCESSIBLE EXIT SHOWN FOR THE DISTRIBUTION AREA |
| | (REQUIRES TWO BASED ON OCCUPANT LOAD) AND ONE FOR THE |
| | OFFICE AREA.OFFICE AREA IS COMPLIANT AS IT REQUIRES |
| | ONE EXIT BASED ON OCCUPANT LOAD, BUT TWO ACCESSIBLE |
| | EXITS ARE REQUIRED FOR THE DISTRIBUTION AREA. |
| | |
| | 19-22.)ADDRESSED. |
| | |
| | 23.)1ST/2ND REVIEWS: EXIT OR EXIT ACCESS DOORWAY |
| | ARRANGEMENT SHALL COMPLY WITH FBC1014.2 OR |
| | FBC1014.2.2., SHOW DISTANCE APART, SEE EXCEPTION 2. |
| | THERE ARE TO BE TWO ACCESSIBLE EXITS WHICH ARE REMOTELY |
| | LOCATED.ONLY ONE SHOWN ON THE PLAN (ALL OTHERS HAVE |
| | STAIRS). |
| | |
| | 3RD REVIEW (REVISED 4/12):THE TWO DOORS SHOWN SERVE |
| | TWO DIFFERENT AREAS.SHOW THE TWO ACCESSIBLE EXITS, |
| | REMOTELY LOCATED, AS REQUESTED. |
| | |
| | 4TH (COURTESY) REVIEW: THE DISTANCE IS SHOWN BETWEEN |
| | THE TWO ACCESSIBLE EXITS BUT THE EXIT WITH THE RAMP |
| | DOES NOT SERVE THE DISTRIBUTION AREA (NO EXIT SIGNS |
| | FROM DISTRIBUTION AREA THROUGH OFFICE, NOTHING ON THE |
| | PLAN TO SHOW THAT THIS IS TO BE AN EXIT TO SERVE THE |
| | DISTRIBUTION AREA).IT IS CLEAR THAT NON ACCESSIBLE |
| | EXITS ARE COMPLIANT.SHOW COMPLIANCE FOR ACCESSIBLE |
| | EXITS AS REQUESTED ON PREVIOUS REVIEWS. |
| | |
| | 24.) ADDRESSED. |
| | |
| | 25.)SIGN THE OWNER/AGENT LINE OF THE ENERGY CALC. |
| | |
| | 26.)THE COMMENT REGARDING REMOVABLE SHUTTERS WAS, I |
| | BELIEVE, ADDRESSED WITH SUBMITTAL OF IMPACT DOOR |
| | PRODUCT APPROVALS.IT APPEARS THAT IMPACT RATED |
| | PRODUCTS WILL BE USED.PLEASE NOTE THAT IF NON IMPACT |
| | PRODUCT APPROVALS ARE SUBMITTED ON THIRD REVIEW, A |
| | SHUTTER INSTALLATION PLAN WILL BE REQUIRED PRIOR TO |
| | PERMIT ISSUANCE.PLEASE CONTACT ME IF YOU WOULD LIKE |
| | TO PROPOSE THE USE OF REMOVABLE SHUTTERS TO DISCUSS |
| | THAT APPROVAL PROCESS.IF ALL PRODUCTS WILL BE IMPACT |
| | RATED, DISREGARD THE COMMENT. |
| | |
| | THIRD REVIEW - PLEASE SUBMIT ALL REQUIRED PRODUCT |
| | APPROVALS AT THIS TIME. |
| | |
| | 27.)PLEASE NOTE THAT PRODUCT APPROVALS FOR IMPACT |
| | DOORS WERE SUBMITTED.PRODUCT APPROVALS ARE TO BE |
| | REVIEWED BY DESIGNER OF RECORD, FBC*106.3.3.NO OTHER |
| | PRODUCT APPROVALS WERE SUBMITTED.FLORIDA STATE OR |
| | LOCAL PRODUCT APPROVAL REQUIRED IN ADDITION TO THE |
| | EVALUATION REPORT (MIAMIDADE NOA IN THIS CASE) |
| | PROVIDED, FAC9B72; WWW.FLORIDABUILDING.ORG.IF FLORIDA |
| | STATE PRODUCT APPROVAL IS NOT AVAILABLE, PLEASE CONTACT |
| | ME TO DISCUSS. |
| | |
| | NO ROOFING PR-DUCT APPROVALS WERE SUBMITTED. CONTRACTOR |
| | OR DOR IS TO SELECT THE APPROVED ASSEMBLY. |
| | |
| | FOR ALL OTHER PRODUCTS, INCLUDING THE STANDING SEAM |
| | ROOF PANELS, IF THERE ARE DIFFERENT OPTIONS FOR |
| | INSTALLATION AND NOT ALL OF THEM ARE COMPLIANT FOR |
| | DESIGN PRESSURES FOR THIS BUILDING, CIRCLE THE |
| | INSTALLATION OR PARTICULAR OPTION YOU ARE USING SO THAT |
| | CODE COMPLIANCE CAN BE DETERMINED. |
| | |
| | THIRD REVIEW ? THE PRODUCT APPROVALS WHICH ARE IN THE |
| | PACKAGE STILL HAVE NO EVIDENCE THAT THEY HAVE BEEN |
| | REVIEWED BY DESIGNER OF RECORD.THIS MAY BE DONE WITH |
| | A SHOP DRAWING REVIEW STAMP, A LETTER, OR INCORPORATED |
| | INTO THE PLAN BY REFERENCE. |
| | |
| | ALL PRODUCT APPROVALS REQUIRED BY FAC9B72 ARE REQUIRED |
| | AT THIS TIME DUE TO A POLICY CHANGE.STATEMENTS IN THE |
| | PREVIOUS COMMENTS THAT THEY COULD BE SUBMITTED IN THE |
| | FUTURE UNDER SEPARATE PERMIT HAVE BEEN REMOVED FROM |
| | THIS REVIEW TO AVOID CONFUSION. |
| | |
| | AS THE DOR DID NOT PROVIDE A SCHEDULE, ALL WALL |
| | PRODUCTS ARE TO COMPLY WITH WORST CASE WALL PRESSURE OF |
| | -48PSF.PRODUCT APPROVALS REQUIRED INCLUDE STOREFRONT, |
| | SKYLIGHT, OVERHEAD DOOR, FULL LOUVER METAL DOOR, |
| | LOUVERS, ROOF HATCH, 24 GA GALVALUME STANDING SEAM |
| | METAL ROOF, 4 PLY BUR OVER INSULATED LW CONCRETE.THIS |
| | MAY NOT BE A COMPLETE LIST; CONTRACTOR OR DOR IS |
| | RESPONSIBLE FOR THE COMPLETENESS OF THE SUBMITTED |
| | PACKAGE. |
| | |
| | **4/12/07** DURING THE MEETING WITH THE ARCHITECT I |
| | BECAME AWARE THAT THE THREE BOUND SETS OF DOCUMENTS |
| | SUBMITTED WERE NOT IDENTICAL SETS.THERE WERE SOME |
| | PRODUCT APPROVALS REVIEWED BY DOR IN THE OTHER PACKAGE. |
| | THE ROOF PRODUCT APPROVAL WAS REVIEWED BY ANOTHER |
| | ARCHITECT FROM A DIFFERENT PRODUCT. |
| | |
| | WHEN RESUBMITTING, PLEASE PROVIDE THREE IDENTICAL BOUND |
| | SETS FOR PERMIT ISSUANCE.FAILURE TO DO SO WILL RESULT |
| | IN PERMIT DELAYS. |
| | |
| | ALL OTHER COMMENTS IN REGARDS TO PRODUCT APPROVALS |
| | STILL APPLY.FLORIDA STATE OR LOCAL PRODUCT APPROVAL |
| | REQUIRED FOR ALL PRODUCTS, FAC9B72, |
| | WWW.FLORIDABUILDING.ORG.FLORIDA STATE PRODUCT |
| | APPROVAL IS TO BE FOR THE 2004 CODE (NOT 2001 AS IS THE |
| | CASE WITH THE OVERHEAD DOOR PRODUCT APPROVAL).ONLY |
| | ONE SHEET OF THE NOA FOR THE INGERSOLL RAND DOOR WAS |
| | SUBMITTED; ALL SHEETS REQUIRED.IF A FLORIDA STATE |
| | PRODUCT APPROVAL IS NOT AVAILABLE FOR ANY OF THE |
| | PRODUCTS YOU HAVE SELECTED, PLEASE CONTACT ME IN |
| | REGARDS TO THE PROCEDURE FOR APPLICATION FOR LOCAL |
| | PRODUCT APPROVAL. |
| | |
| | 28.)SQUARE FOOT AREAS ON THE ENERGY CALCS DO NOT |
| | MATCH THE PLAN. |
| | |
| | THIRD REVIEW - THE ARCHITECT RESPONSE LETTER STATES |
| | THAT INSIDE DIMENSIONS WERE USED FOR THE ENERGY CALCS. |
| | SEE FBC 13, CHAPTER 2, DEFINITION OF FLOOR AREA, GROSS. |
| | AS NEW ENERGY CALCS ARE REQUIRED, ELECTRIC REVIEW WILL |
| | ALSO BE REQUIRED ON RESUBMITTAL.NOTE THAT ENERGY |
| | CALCS ARE A STATUTORY REQUIREMENT AND STATUTORY |
| | REQUIREMENTS CAN NEVER BE WAIVED OR PROVISO?D (PER |
| | BUILDING OFFICIAL). |
| | |
| | 29.)FROM FIRST REVIEW - THE ENGINEER'S TITLE BLOCK IS |
| | TO COMPLY WITH FAC61G15-23.002, VP BUILDINGS. |
| | |
| | 4/12/07MR. JOHN RYAN, ATTORNEY FOR FLORIDA BOARD OF |
| | PROFESSIONAL ENGINEERS, CONFIRMED THE CERTIFICATE OF |
| | AUTHORIZATION REQUIREMENT, FS471.023.THE ENGINEER'S |
| | LETTER STATING THAT ENGINEERING IS NOT THE PRODUCT |
| | OFFERED TO THE PUBLIC IS ACKNOWLEDGED.HOWEVER, WHEN |
| | PRACTICING ENGINEERING THROUGH A COMPANY, A CERTIFICATE |
| | OF AUTHORIZATION IS REQUIRED REGARDLESS OF PRODUCT |
| | OFFERED.PLEASE CONTACT FBPE IF YOU NEED FURTHER |
| | CLARIFICATION, 850-521-0500.AS THIS IS A STATUTORY |
| | REQUIREMENT, THIS CANNOT BE WAIVED OR PROVISO'D; PLANS |
| | MUST BE IN COMPLIANCE FOR PERMITTING. |
| | |
| | 30.)ADDRESSED. |
| | |
| | 31.)THE ENGINEER'S SIGNATURE IS A PHOTOCOPY, ORIGINAL |
| | WET SIGNATURE REQUIRED.SEE PANEL SHEETS AND VP |
| | SHEETS. |
| | |
| | THIRD REVIEW - PANEL ENGINEERING STILL HAS A PHOTOCOPY |
| | SIGNATURE.ALSO ALL INFORMATION REQUIRED BY |
| | FAC61G15-23.002 IS REQUIRED TO BE ON EACH SHEET |
| | (CERTIFICATE OF AUTHORIZATION). |
| | |
| | THE FOOTERS, SITEWORK, AND STRUCTURE (PANELS, STEEL |
| | STRUCTURE) WERE ISSUED UNDER SEPARATE PERMITS.HAVE |
| | THE CHANGES SHOWN ON THE CIVIL DRAWINGS BEEN MADE TO |
| | THE ISSUED SITEWORK PERMIT?PLEASE PROVIDE A PERMIT |
| | NUMBER FOR THE SITEWORK. |
| | |
| | THE PANEL PLANS AND STEEL STRUCTURAL PLANS ARE NOT |
| | REQUIRED FOR THIS PERMIT AS THEY ARE INCLUDED IN THE |
| | SCOPE OF WORK OF ANOTHER PERMIT.IF EITHER PLAN IS |
| | CHANGED AS A RESULT OF THESE COMMENTS, THE CHANGES |
| | SHOULD BE SUBMITTED AS REVISIONS TO THE ISSUED PERMIT. |
| | ALSO HAVING A SET INCLUDED FOR REFERENCE (AS LONG AS IT |
| | MATCHES THE PERMIT SET) WILL ASSIST IN PLAN REVIEW. |
| | |
| | 32-36.) ADDRESSED. |
| | |
| | 37.)SEE ATTACHED FS553.80(2)(B).NOTE THAT THIS IS A |
| | MANDATORY FINE AND CANNOT BE WAIVED.NOTE THAT SOME |
| | COMMENTS HAVE ALREADY BEEN MADE THREE TIMES (ENERGY |
| | CALCS, LIFE SAFETY).A 4X PLAN REVIEW FEE HAS BEEN |
| | CHARGED. |
| | |
| | NEW COMMENTS: |
| | |
| | 38.)SEE CIVIL SHEET 17 OF 29 PREPARED BY BOYER |
| | SINGLETON.THIS SHEET HAS A DATE OF FEBRUARY 12, 2007, |
| | NO CHANGES CLOUDED.THE SECOND BUILDING REVIEW WAS |
| | JANUARY 30, 2007.THIS IS EITHER A NEW SHEET OR |
| | CHANGES WERE MADE TO THE SHEET AND NOT INDICATED.ALL |
| | CHANGES TO THE PLAN ARE TO BE CLEARLY INDICATED WITH |
| | CLOUDS AND REVISION NUMBERS.WHEN CHANGES ARE |
| | SUBMITTED A COMPLETE NEW PLAN REVIEW IS REQUIRED AS I |
| | CANNOT DETERMINE SPECIFICALLY WHAT HAS CHANGED.NOTE |
| | THAT THE ARCHITECT (CORRECTLY) CLOUDED THE PAGE NUMBER |
| | TO SHOW NEW SHEETS. |
| | |
| | THE "TURNSTILE & HANDICAPPED SECURITY GATE" DETAIL ON |
| | SHEET 17 IS ILLEGIBLE.AS THIS DETAIL IS REQUIRED TO |
| | SHOW CODE COMPLIANCE (ACCESSIBILITY, EGRESS) PLEASE |
| | PROVIDE LEGIBLE DETAILS. |
| | |
| | 4/12/07 ** IN THE MEETING WITH ARCHITECT ON 4/11/7, IT |
| | WAS DISCUSSED THAT THIS DETAIL IS ALSO IN THE ELECTRIC |
| | DRAWINGS.TO AVOID FURTHER PERMITTING DELAYS, DO NOT |
| | ADDRESS THIS COMMENT AT THIS TIME.FOR THE FUTURE, |
| | PLEASE NOTE THAT ALL DETAILS ARE REQUIRED TO BE |
| | LEGIBLE!!!WHEN ISSUING THE PERMIT I WILL MAKE A NOTE |
| | ON THE PLAN REFERRING TO THE APPROPRIATE ELECTRIC |
| | SHEET. |
| | |
| | 39.)SHEET 18 OF 24 OF THE CIVIL DRAWINGS CONTAINS |
| | INFORMATION IN REGARDS TO THE FUEL TANK.THIS IS |
| | CURRENTLY IN THE PLAN REVIEW PROCESS UNDER SEPARATE |
| | PERMIT.AS THIS SHEET HAS NOT BEEN REVIEWED BY ALL |
| | TRADES FOR CODE COMPLIANCE, AND TO AVOID HAVING |
| | INFORMATION IN THIS PERMIT WHICH CONFLICTS WITH OTHER |
| | PERMITS, PLEASE REMOVE THIS SHEET. |
| | |
| | 40.)A3.0, THERE IS A NEW NOTE STATING THAT A |
| | SATELLITE DISH IS TO BE INSTALLED AND A SLEEVE PROVIDED |
| | IN THE TILT WALL PANEL.PROVIDE A DETAIL FOR THE |
| | SATELLITE DISH AND A SPECIFICATION FOR THE SLEEVE.THE |
| | WALL PANEL ENGINEER IS TO INCLUDE THIS INFORMATION IN |
| | HIS STRUCTURAL DRAWINGS.SEE SHEET PN10; THERE IS A |
| | NOTE ADDRESSING CORE DRILLING AFTER ERECTION.IT IS |
| | NOT CLEAR IF THIS SLEEVE IS TO BE PROVIDED IN THE PANEL |
| | WHEN IT IS CONSTRUCTED OR IF IT IS DRILLED AFTER |
| | ERECTION.IN EITHER CASE, IT REQUIRES THE APPROVAL OF |
| | THE WALL PANEL ENGINEER AND SHOULD ALSO BE ADDRESSED ON |
| | HIS DRAWINGS SO THAT THE STRUCTURAL DRAWINGS ARE |
| | CONSISTENT WITH THE ARCHITECTURAL DRAWINGS. |
| | |
| | **4/12/07** IN THE MEETING WITH THE ARCHITECT, IT WAS |
| | AGREED THAT THE STRUCTURE/WALL PANEL PERMIT IS TO BE |
| | REVISED AND THAT THIS PLAN WILL BE REVISED TO SHOW |
| | METHOD OF ATTACHMENT AND ALSO WILL STATE THAT SHOP |
| | DRAWINGS WILL BE REQUIRED PRIOR TO ISSUANCE. |
| | |
| | 41.)A4.0, ELEVATION AND ENTRY DETAIL, SEE |
| | FBC11-4.13.7.WHEN SCALED, IT APPEARS TO MEET THE |
| | MINIMUM REQUIREMENT EXACTLY BUT PLEASE NOTE THAT |
| | REQUIREMENT ON THE PLAN. |
| | |
| | 42.)SEE THE STRUCTURAL PAGES PREPARED AND SIGNED BY |
| | BRADLEY B. JOHNSON, PE.FS471, FAC61G15-23, THE SEAL |
| | IS NOT LEGIBLE. |
| | |
| | **4/12/07**IN THE MEETING WITH THE ARCHITECT AND |
| | CONTRACTOR, IT WAS AGREED THAT THE BEST COURSE OF |
| | ACTION WOULD BE TO SUBMIT AS SOON AS POSSIBLE.THE |
| | ENGINEER HAS ORDERED A NEW SEAL.IF NEWLY SEALED |
| | SHEETS ARE NOT AVAILABLE AT THE TIME OF RESUBMITTAL, I |
| | WILL ALLOW THE CONTRACTOR OR ARCHITECT TO BRING IN THE |
| | NEW SHEETS (NEW SEAL ONLY, NO CHANGE TO DRAWING) AFTER |
| | RESUBMITTAL PROVIDED THAT ALL OTHER COMMENTS FROM ALL |
| | PLANS EXAMINERS HAVE BEEN SATISFIED. |
| | |
| | 43.)***NEW COMMENT 4/12/07***THE ARCHITECT'S |
| | OBJECTION TO SHOWING COMPLIANCE WITH ALL EXITING |
| | REQUIREMENTS FOR ACCESSIBLE EXITS IS NOTED.AS |
| | DISCUSSED, THE NEW LIFE SAFETY PLAN WILL SHOW |
| | COMPLIANCE AS REQUESTED ALTHOUGH THE ARCHITECT DOES NOT |
| | AGREE WITH THE REQUIREMENT. |
| | |
| | HOWEVER, WE ARE IN AGREEMENT REGARDING ITEMS #17 AND |
| | 18.MY UNDERSTANDING IS THAT THE ARCHITECT AGREES THAT |
| | TWO ARE REQUIRED AND ONLY ACCESSIBLE EXIT SERVING THE |
| | DISTRIBUTION AREAIS SHOWN ON THE PLAN, FOUR REVIEWS. |
| | |
| | |
| | TO EXPEDITE PLAN REVIEW, INCLUDE A RESPONSE LETTER |
| | INDICATING HOW EACH ITEM WAS ADDRESSED WHEN |
| | RESUBMITTING. |