| 2007-01-09 13:22:47 | ** UNSAT ** |
| | |
| | 2ND REVIEW |
| | FED EX FREIGHT |
| | |
| | ** PLEASE SEE SOME COMMENTS FROM PREVIOUS REVIEW STILL |
| | ARE IN NEED OF PROVIDING MORE INFORMATION AND/OR |
| | ADDRESSING. |
| | |
| | ** PLEASE SEE SOME NEW COMMENTS BASED ON SUBMITTALS AND |
| | PLANS SUBMITTED. |
| | |
| | 1) NOTE: ** THIS IS NOT A COMMENT FOR KAMM CONSULTING, |
| | HOWEVER IS BEING NOTED BY THIS REVIEWER. |
| | PLEASE SEE THE VP SHEETS AND THE PN SHEETS CONTAIN |
| | RAISED SEALS OVER PHOTO-COPIED SIGNATURES FOR THE |
| | ENGINEERS ON EACH OF THESE WHICH IS NOT PERMITTED UNDER |
| | FLORIDA STATUTES 471.025 AND FLORIDA ADMINISTRATIVE |
| | CODE 61G15-23.002 |
| | PLEASE SEE BUILDING REVIEW COMMENTS FOR THIS ALSO. |
| | **THIS WAS COMMENT #2 FROM THE PREVIOUS REVIEW. |
| | PLEASE KNOW ONE SET OF PLANS MAY BE RETAINED BY THIS |
| | OFFICE. |
| | |
| | 2) NOTE: PLEASE SEE 13-415.1.ABC.1.1, .1.2 AND .1.3 |
| | WHICH SPEAKS OF MAXIMUM TIMES PERMITTED ON THE TYPE OF |
| | DEVICES INSTALLED. |
| | PLEASE SEE NOTES ON E0.1 AND 2.1 IN SEVERAL PLACES |
| | INDICATE OCCUPANCY TYPE DEVICES WITH 3HRS AND 4HRS FOR |
| | MAXIMUM TIMES. PLEASE SEE THE SECTIONS AS NOTED ABOVE |
| | AS THE MAXIMUM PERMITTED TIMES ON THESE TYPES OF |
| | DEVICES IS 30MINS FROM THE LAST SENSING OF THE |
| | OCCUPANT. |
| | PLEASE ADJUST NOTES AND ALSO PLEASE BE SURE TO ADJUST |
| | ALL DEVICES TO CONTAIN NOTES FOR THIS. |
| | **PREVIOUS REVIEW NOTE #3 |
| | |
| | 3) NOTE: PLEASE SEE THE PERFORMANCE/ENERGY CALCULATIONS |
| | SUBMITTED WHICH DO NOT PROVIDE THE INFORMATION NEEDED |
| | FOR REVIEW. |
| | PLEASE SEE RESPONSE LETTER SPEAKS OF EXTERIOR LIGHTING |
| | CONTACTOR AND PHOTO-METRICS PLANS BY OTHERS? |
| | PLEASE SEE ENERGY CALCULATIONS SUBMITTED INDICATE ALL |
| | CONTROLS AS MANUAL ON/OFF WHEN PLANS INDICATE |
| | OTHERWISE? |
| | PLEASE PROVIDE INFORMATION FOR THE PERFORMANCE OF |
| | LIGHTING DENSITIES. |
| | **PREVIOUS REVIEW NOTE #4 |
| | |
| | 4) NOTE: PLEASE PROVIDE WORST CASE VOLTAGE DROP FOR |
| | FEEDER(S) AND BRANCH CIRCUIT(S) PER 13-413.1.ABC.1.1. |
| | RESPONSE LETTER MENTIONS TO SEE 4.1 AND 5.1, HOWEVER |
| | 4.1 IS AIC CALCULATIONS, AND 5.1 WAS THE RISER DIAGRAM |
| | SHEETS WHICH THIS REVIEWER COULD NOT LOCATED ANY |
| | VOLTAGE DROP CALCULATIONS/ OR WORST CASE INFORMATION. |
| | **PREVIOUS REVIEW #6 |
| | |
| | 5) NOTE: PLEASE SEE INFORMATION ON ACCESS CONTROL |
| | SYSTEM DOES NOT YET PROVIDE ENOUGH INFORMATION. PLEASE |
| | SEE NFPA-101 2003 |
| | 7.2.1.5 LOCKS, LATCHES, AND ALARM DEVICES. |
| | 7.2.1.5.1 DOORS SHALL BE ARRANGED TO BE OPENED READILY |
| | FROM THE EGRESS SIDE WHENEVER THE BUILDING IS OCCUPIED. |
| | |
| | 7.2.1.5.2 LOCKS, IF PROVIDED, SHALL NOT REQUIRE THE USE |
| | OF A KEY, A TOOL, OR SPECIAL KNOWLEDGE OR EFFORT FOR |
| | OPERATION FROM THE EGRESS SIDE. |
| | 7.2.1.6 SPECIAL LOCKING ARRANGEMENTS. |
| | PLEASE SEE FIRE REVIEW COMMENTS AS WELL AS THE RESPONSE |
| | AND NOTE ON PLANS MENTIONS IN THE EVENT OF POWER |
| | FAILURE UNDER EMERGENCY OR NORMAL POWER THE FIRE ALARM |
| | AND SECURITY WILL NOT BE AFFECTED. |
| | PLEASE SEE THIS IS BEING CONSIDERED AN EGRESS CONCERN |
| | AND NOT THAT OF THE NOTE AS STATED. |
| | ** PREVIOUS NOTE #9 |
| | |
| | 6) NOTE: PLEASE SUBMIT ALL MANUFACTURES SPEC/CUT SHEETS |
| | FOR THE GENERATOR, ATS, WP ENCLOSURE AND FUEL TANKS. |
| | PLEASE CORRELATE THESE WITH THE SUBMITTED PLANS. |
| | SOME OF THESE WERE SUBMITTED, HOWEVER NOT FOR BOTH |
| | TANKS AND PLEASE SEE SOME OF THESE DO NOT MATCH WITH |
| | THE SUBMITTED PLANS. |
| | PLEASE SEE THE RESPONSE LETTER DOES NOT CONTAIN A |
| | RESPONSE FOR NOTE #11 FROM PREVIOUS REVIEW. |
| | 90.7, 110.3 NEC |
| | FBC 106.1.2 ADMIN SECTION FOR ADDITIONAL INFORMATION. |
| | ** PREVIOUS NOTE #11 |
| | |
| | 7) NOTE: PLEASE SEE 225.31-225.39, 702, 110.27 FOR |
| | DISCONNECTING MEANS REQUIRED FOR FEEDERS FROM THE |
| | GENERATOR. THE RESPONSE LETTER MENTIONS TO BE BY |
| | OTHERS; HOWEVER THIS INFORMATION IS REQUIRED AT THIS |
| | TIME. PLEASE KNOW THIS IS A DISCONNECTING MEANS AND IS |
| | NOT REQUIRED TO CONTAIN OVER CURRENT PROTECTION. THERE |
| | ARE SEVERAL WAYS OF DOING THIS, HOWEVER THE USE OF THE |
| | BREAKER INSIDE THE GEN UNIT WHICH MAY NOT MEET 110.27 |
| | OR 702. |
| | PLEASE PROVIDE MORE INFORMATION ON DISCONNECT, THIS MAY |
| | BE LOCATED OUTSIDE MAIN ELECTRICAL ROOM ON BUILDING OR |
| | IN MAIN ELECTRICAL ROOM. SIGNAGE WILL BE REQUIRED. |
| | 702.8, 230.2E |
| | ** PREVIOUS REVIEW NOTE #19 |
| | |
| | 8) NOTE: PLEASE SEE NOTE #20 FROM THE PREVIOUS REVIEW |
| | WITH RESPECT TO SLAB DETAIL, HEIGHT MOUNTING ETC FOR |
| | THE GENERATOR PER NFPA-110 CHAPTER 7. |
| | PLEASE SEE THE RESPONSE LETTER DOES NOT CONTAIN A |
| | RESPONSE FOR NOTE #20. |
| | |
| | 9) NOTE: PLEASE SHOW MORE INFORMATION FOR NEC 514. |
| | PLEASE SEE 514.11(A) AND (C). PLEASE SEE COMMENTARY |
| | WHICH SPEAKS OF THE LOCATION AND SIGNAGE REQUIREMENTS. |
| | PLANS DO CONTAIN SOME NOTES FOR THESE HOWEVER PLEASE |
| | PROVIDE MORE DETAILS. PLEASE SEE THAT THE PUSHBUTTON EM |
| | CUT-OFF DEVICE SHOULD BE LOCATED AWAY FROM ANY HAZARD |
| | BUT NOT MORE THAN 100FT.PLEASE SEE THE DISTANCE AND |
| | THE LOCATION AS THIS IS BEING SHOWN BEHIND THE ADJACENT |
| | BUILDING WHICH IS PER SCALE PERHAPS LESS THAN 20FT FROM |
| | THE TANK GIVES CONCERN. PLEASE SEE FIRE MARSHAL'S |
| | COMMENTS ALSO. |
| | ** PREVIOUS REVIEW NOTE #22 |
| | |
| | 10) NOTE: PLEASE SEE PROVIDE MORE INFORMATION ON THE |
| | CLASS AND DIVISION LOCATIONS SURROUNDING THE FUEL |
| | DISPENSING. PLEASE SEE THE RESPONSE MENTIONED TO SEE |
| | THE TWO SHEETS, HOWEVER THOSE SHEET 1.1 AND 1.4 ONLY |
| | INDICATE THE DOTTED LINES FOR THE AREA. |
| | PLEASE SEE NEC 500, 514 |
| | FBC ADMIN SECTION 106.1.2 |
| | ** PREVIOUS REVIEW NOTE #23. |
| | |
| | 11) NOTE: PLEASE CLARIFY THE LIGHTING FOR LIGHTS TO THE |
| | PUBLIC RIGHT OF WAY. PLEASE SEE THE STAIRS LOCATED |
| | OUTSIDE OF THE EGRESS DOORS WHICH WILL REQUIRE |
| | EMERGENCY LIGHTING OF SOME SORT. |
| | PLEASE ALSO SEE RESPONSE MENTIONS FOR SITE |
| | PHOTO-METRICS TO BE PROVIDED BY OTHERS, HOWEVER PLEASE |
| | SEE THE SITE LIGHTING IS BEING PERMITTED UNDER THIS |
| | BASE BUILDING. |
| | LS 101 7.8, 7.9 |
| | ** PREVIOUS REVIEW NOTE #26. |
| | |
| | 12) NOTE: PLEASE SEE THE MISSING STRUCTURAL BUILDING |
| | STEEL AND FIRE SPRINKLER LINE ATTACHMENT AS PART OF THE |
| | GROUNDING ELECTRODE SYSTEM. |
| | 250.50, 250.104. |
| | |
| | ** ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | |
| | |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |