| 2006-10-24 10:36:28 | *** PLEASE SEE NOW THAT AN ADDRESS HAS BEEN CREATED, |
| | PLEASE PLACE ON TITLE BLOCKS FOR PLANS. |
| 2006-10-24 10:31:25 | ********* UNSAT ********** |
| | |
| | |
| | 1) NOTE: PLEASE LIST ALL OF THE FOLLOWING CODES |
| | RELEVANT TO PLANS AND DESIGNS ON THEOR RESPECTIVE |
| | SHEETS. |
| | PLEASE SEE THE FOLLOWING ARE REQUIRED AT A MINIMUM: |
| | 2002NFPA-70, 2002 NFPA-72, 2003 NFPA-101, 2003 NFPA-20, |
| | 2002 NFPA-110, 2000 NPPA-30A,2004 FBC . |
| | PLEASE BE AWARE OF ANY OTHER APPLICABLE CODES FROM |
| | OTHER REVIEWERS WHICH MAY BE REQUIRED. |
| | |
| | 2) NOTE: PLEASE SEE "VP" BUILDING SHEETS AND SETS WHICH |
| | CONTAINEDRAISED SEALS OVER "PHOTO-COPIED" SIGNATURES. |
| | PLEASE SEE THIS COMMENT IS MADE WETHER OR NOT COMMENT |
| | IS MADE BY ANY OTHER REVIEWER. |
| | PLEASE SEE FLORIDA ADMINISTRATIVE CODE 61G15-23.002, |
| | FLORIDA STATUTES 471.025, PLEASE ALSO SEE MISSING |
| | REQUIRED TITLE BLOCK INFORMATION. |
| | |
| | 3) NOTE: PLEASE SEE FBC 2004 CHAPTER 13. |
| | 13-415.1.ABC.1.1, .1.2 AND .1.3. PLEASE SEE NO MORE |
| | THAN 4HRS IS PERMITTED ON OVER-RIDE DEVICES. (SOME |
| | SHOWN AS 12HRS). PLEASE SEE OTHER AREAS WHERE A TIMED |
| | OR OCCUPANT TYPE DEVICE IS NOT INDICATED. PLEASE |
| | CLARIFY THE USE OF THE MOMNETARY CONTACTS, FOR AREAS OF |
| | INGRESS/EGRESS.THE OCCUPANT MUST BE ABLE TO OVER RIDE |
| | ANY TIME OF DAY SCHEDULEING DEVICE AND SEE THE LIGHTING |
| | BEING CONTROLLED. (TIMES OR SENSOR TYPE). PLEASE SEE |
| | SYSMBOL LEGEND NEEDS TO INDICATE THE MAX AMOUNT OF |
| | TIMES ON DEVICE WHICH ARE SHOWN ON THIS LEGEND, HOWEVER |
| | NOT ON PLANS. |
| | (30MINS MAX OS, 4HRS MAX TIMER TYPE) |
| | |
| | 4) NOTE: PLEASE PROVIDE ALL LIGHTING PERFORMANCE |
| | CALCULATIONS PER 13-415.2, 13-415.2.ABC.1, TBALES |
| | 415.2.C.1, 415.2.B1, AS SPACE BY SPACE WILL BE REQUIRED |
| | FOR SOME AREAS. |
| | PLEASE SEE METHOD "A" AS SUBMITTED DOES NOT SHOW |
| | THESE. |
| | |
| | 5) NOTE: PLEASE SEE NO PLANS, DOCUMENTS ETC MAY CONTAIN |
| | "WHITE-OUT" OF ANY KIND ON SAID DOCUMENTS WITH |
| | HANDWRITTEN ITEMS OVER SUCH SHEETS. PLEASE SEE ENERGY |
| | CALCULATIONS. |
| | FS471 |
| | |
| | 6) NOTE: PLEASE PROVIDE VOLTAGE DROP CALCULATIONS FOR |
| | WORST CASE FOR EACH FOR FEEDERS AND BRANCH CIRCUITS. |
| | PLEASE SEE FBC 13-413.1.ABC.1.1 &.1.2. |
| | |
| | 7) NOTE: PLEASE SEE SYMBOLSHOWN IN STORAGE/SPRINKLER |
| | ROOM ON 3.1, AND 2.1 APPEARS TO BE THAT OF A |
| | TRANSFORMER, YET THIS IS UNCLEAR AT THIS TIME.?? |
| | FBC ADMIN SECT 106.1.2 |
| | |
| | 8) NOTE: PLEASE SEE IT WILL NOT BE PERMITTED THAT THE |
| | ONLY ACCESS TO THE MAIN ELECTRICAL ROOM IS THROUGH A |
| | STORAGE ROOM AND AREA. THESE TYPES OF ROOMS DO NOT |
| | TYPICALLY PROVIDE THE READY ACCESS TO THE ELECTRICAL |
| | EQUIPMENT IN THE QUICK TIME WHICH MAY BE NEED IN THE |
| | CASE OF AN EMERGENCY FOR FIRE DEPARTMENT OR ANY OTHER |
| | PERSONNEL TRYING TO SHUT OFF THE POWER. PLEASE SEE THAT |
| | RELOCATION OR ACCESS SEPARATELY FOR ROOM WILL BE |
| | REQUIRED AT THIS TIME. |
| | 230.70,110.26, 408.7,90.4 |
| | |
| | 9) NOTE: PLEASE SEE POSSIBLE FIRE REVIEW COMMENTS WIHT |
| | RESPECT TO ACCESS CONTROL SYSTEM WHICH WILL REQUIRE |
| | ADDITIONAL INFORMATION. PLEASE INDICATE THAT IN THE |
| | EVENT OF AN EMERGENCY OR FAILURE OF NORMAL POWER EGRESS |
| | FROM THE BUILDING WILL NOT BE AFFECTED. PLEASE SEE LS |
| | 101. SEE FIRE REVIEW COMMENTS. |
| | |
| | 10) NOTE: PLEASE SEE FBC 11-4.28, 11-4.28.3. PLEASE |
| | INDICATE THE MIN LEVELS FOR DB RATINGS OF HORNS/ OR |
| | COMBO DEVICES.PLEASE SEE SCHEDULE INDICATES A |
| | POSSIBLE OF 15CD MIN, HOWEVER AS INDICATE ON PLANS AND |
| | ADA REQUIREMENTS, A MIN OF 75 CD IS REQUIRED. PLEASE |
| | PROVIDE AND COMPLETE THE LAYOUT OF THE FA DEVICES ON |
| | PLANS. THE 2ND AND THIRD SECTIONS DO NOT APPEAR ON FA |
| | SHEETS. |
| | 11-4.28.3(4). |
| | |
| | 11) NOTE: PLEASE SUBMIT COMPLETE MANUFACTURE SPECS/CUT |
| | SHEETS FOR ALL OF THE FOLLOWING. GENERATOR, FUEL |
| | TANK(REVIEW BY OTHERS), ATS, FIRE PUMP AND FIRE PUMP |
| | CONTROLLER. PLEASE SEE AS NONE OF THESE ARE SUBMITTED |
| | AT THIS TIME NOT REVIEW FOR SOME CODE REQUIRED ITMES |
| | CAN EB DONE. |
| | 110.3, 90.7. |
| | |
| | 12) NOTE: PLEASE INDICATE ALL OCP DEVICE SIZES AT THE |
| | GEN. PLEASE SEE SHEET7.3 INDICATES A BREAKER FOR FIRE |
| | PUMP AT GEN AS G-1 , YET THE RISER DOES NOT INDICATE |
| | THIS BREAKER AT ALL ON GEN. |
| | PLEASE SEE 445.13 AS THE SIZING OF THE FEEDERS CAN NOT |
| | BE VERIFIED AT THIS TIME. |
| | |
| | 13) NOTE: PLEASE SEE THE GEN SEEMS IT WILL FEED A FIRE |
| | PUMP, THE STAND-BY FOR THIS BUILDING AND THE POSSIBLE |
| | STAND-BY FOR AN ADDITIONAL LOCATION, HOWEVER A COMPLETE |
| | LOAD SUMMARY AND LOAD SHEDDDING DETAILS HAVE NOT BEEN |
| | PROVIDED AT THIS TIME. PLEASE SEE THE LOAD ON THE MD IS |
| | THE ONLY LOAD SHOWN AT THIS TIME. PLEASE PROVIDE A LOAD |
| | SUMMARY FOR THE GEN AS THIS IS A LEGALLY REQUIRED |
| | STAND-BY UNIT. |
| | 701.6,6.3 OF NFPA-110, NFPA-20 9.6.1.1 ETC.,THESE |
| | ITEMS CAN NOT BE REVIEWED AT THIS TIME. |
| | |
| | 14) NOTE: PLEASE PROVIDE ALL MINIMUM FUEL CONSUMPTION |
| | FOR THEGENERATOR AS THIS FEED THE FIRE PUMP AND |
| | SYSTEM AS SHOWN NEEDS TO MEET THE MINIMUM OF HRS FOR |
| | 100% LOAD INCLUDING ALL OTHER LOADS 9.6.2.2. |
| | CAN NOT REVIEW AT THIS TIME. |
| | |
| | 15) NOTE: PLEASE SUBMIT ALL THE INFORMATION FOR FIRE |
| | PUMP SERVICE, LOCATION, LOCKED ROTOR OCP SIZE ETC. |
| | PLEASE SEE PLANS AND RISER DO NOT SEEM TO INDICATE ANY |
| | INFORMATION FOR THE FIRE PUMP. PLEASE SEE FP SHEETS |
| | ALSO DO NOT INDICATE ANY FP?PLEASE SEE 2003 NFPA-20 |
| | CHAPTER 9 FOR DISCONNECTING MEANS, ISOLATION SWITCH |
| | REQUIREDETC ETC. |
| | |
| | 16) NOTE: PLEASE PROVIDE ALL AIC RATINGS FOR ALL |
| | SERVICE EQUIPMENT. PLEASE PROVIDE A DETAIL FOR |
| | SELECTIVE COORDINATION. 110.9/240.12. |
| | PLEASE SEE NEC 701.6, 700.5 AND NFPA-110, 6.5.2 ETC FOR |
| | ATS AND ALL OTHER EQUIPMENT ASSOCIATED WITH ELECTRICAL |
| | SYSTEM. |
| | |
| | 17) NOTE: PLEASE VERFIY WITH MANUFACTURE THE GENERATOR |
| | GROUNDING SCENARIO, AS IT IS KNOWN TO THIS OFFICE SOME |
| | OF THESE DEPENDING ON THE MANUFACTURE ARE SHIPPED AND |
| | WIRED FOR SEPARATELY DERIVED SYSTEM, PLEASE MAKE ANY |
| | ADJUSTMENTS AS NEED. |
| | 90.7., 250.20, 250.50, ETC |
| | |
| | 18) NOTE: PLEASE CORRELATE CIRCUITING FOR PANEL FD, |
| | PANEL "LB" DOES NOT SHOW FEEDING OF THIS PANEL . |
| | PLEASE SEE CIRCUITS FOR OTHER ITEMS SHOWN ON SCHEDULE. |
| | 240.4,310.16,408.4, |
| | FBC 106.3.5.1.2. ADMIN SECT. |
| | |
| | 19) NOTE: PLEASE SEE MISSIGN A DISONNECTING MEANS FOR |
| | FEEDERS FROM GENERATOR INTO BLDG LOCATED IN CLOSE |
| | PROXIMITY OF OTHER MAINS OR MEETINGEXCEPTIONS UNDER |
| | CODE, HOWEVER SYSTEM IS NOT KNOWN AT THIS TIME |
| | CLASSIFICATION OF BACK UP POWER IS NOT CLEAR. PLEASE |
| | ALSO KNOW AS INFORMATION FOR THE GEN AND W/P ENCLOSURE |
| | AND ACCESS IS ALSO NOT KNOW AT THIS TIME. |
| | 225.31-225.39 |
| | 700, 701, 702 ? |
| | |
| | 20) NOTE: PLEASE SEE NOT INFORMATION FOR LOCATION, |
| | ELEVATION, MOUNTING , SLAB DETAIL ETC COULD BE LOCATED |
| | ON PLANS. PLEASE SEE NFPA-110 2002 CHAPTER 7, AS MANY |
| | OF THESE SCETIONS APPLY, HOWEVER AS NOTHING COULD BE |
| | LOCATED FOR THIS, A REVIEW FOR COMPLIANCE COULD NOT BE |
| | DONE AT THIS TIME. |
| | |
| | 21) NOTE: PLEASE SEE MD AS THIS SHOWS A NEUTRAL |
| | CONDUCTOR BEING SHOWN FEEDING THE TRANSFORMER WHICH IS |
| | A SD SYSTEM. PLEASE SEE 250.30, 250.20 ETC |
| | |
| | 22) NOTE: PLEASE SEE ANY COMMENTS WITH RESPECT THE EM |
| | SHUT OFF OF POWER FOR THEFD PANEL. PLEASE SEE 514 |
| | |
| | 23) NOTE: PLEASE PROVIDE A LAYOUT AND SHOW ALL |
| | HAZARDOUS LOCATIONSON PLANS. |
| | 500. CLASS AND DIVISIONS. |
| | |
| | 24) NOTE: PLEASE SEE MECH REVIEW NOTES FOR SEPARATE |
| | FUEL PERMIT REQUIRED. |
| | |
| | 25: ) NOTE: PLEASE SEE THE GEN SPECIFICATIONS ON 7.3 DO |
| | NOT LIST THE OTHER OCP/ BREAKERS ON GEN AS SHOWN ON |
| | RISER. |
| | |
| | 26) ) NOTE: PLEASE PROVIDE EM BATTERY BACK UP |
| | FIXTURE(S) OF SOME TYPE LEADING TO THE PUBLIC RIGHT OF |
| | WAY. PLEASE PROVIDE PHOTO-METRICS FOR EGRESS PATHS |
| | UNDER NORMAL AND UNDER EMERGENCY POWER. PLEASSE SEE |
| | NFPA-101 7.8.1.3, 7.9.2.2, PLEASE SEE STAIR AREAS |
| | LEADING TO THE OUTSIDE. |
| | |
| | 27) NOTE: PLEASE SEE SOME SHEETS IN SETS ARE PLACED IN |
| | SETS BACKWARDS. PLEASE SEE THE FOLLOWING NOTE. |
| | ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | ** PLEASE KNOW AS THERE IS INFORMATION NOT YET |
| | SUBMITTED FOR REVIEW , PLEASE KNOW THERE MAY BE FURTHER |
| | COMMENTS UPON NEXT REVIEW. |
| | |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| | |
| | |
| | |
| 2006-10-22 19:47:55 | ONE SET IN ELEC FOR REVIEW |