| 2006-10-23 10:52:13 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | |
| | FBCFLORIDA BUILDING CODE 2004 |
| | FBC EBFLORIDA BUILDING CODE 2004 |
| | EXISTING BUILDING CODE |
| | FBC*CITY OF WEST PALM BEACH |
| | AMENDMENTS TO THE FBC2004 |
| | |
| | 1.)A NOTICE OF COMMENCEMENT WILL BE REQUIRED PRIOR TO |
| | PERMIT PICKUP, FS713.13. |
| | |
| | 2.)IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY |
| | PRIOR TO PERMIT ISSUANCE, 2300 N JOG RD.PLEASE CALL |
| | 561-233-5025 FOR MORE INFORMATION. |
| | |
| | 3.)THE COPY OF THE PLAT PROVIDED IS NOT RECORDED. |
| | PLEASE ADVISE AS TO STATUS.IF THIS IS RECORDED, |
| | PROVIDE PLAT FILING INFORMATION (BOOK/PAGE). |
| | |
| | 4.)THE PLAT PROVIDED AND THE PROPOSED PLAT LINES ON |
| | THE OVERALL SITE PLAN PREPARED BY BOWYER SINGLETON DO |
| | NOT MATCH.FOR INSTANCE, THE CIRCULAR SECTION AT THE |
| | END OF THE ROAD (PARCEL G) DOES NOT APPEAR ON THE |
| | OVERALL SITE PLAN.THE PLAT LINES ARE INCOMPLETE ON |
| | THE OVERALL SITE PLAN. |
| | |
| | 5.)THE APPLICATION REFERS TO TWO DIFFERENT PARCEL ID |
| | NUMBERS.YOU CANNOT CROSS PROPERTY LINES.PROVIDE |
| | INFORMATION IN REGARDS TO THE LOCATION OF THE TWO |
| | PARCELS, ENDING IN 3010 AND 3040.OUR GIS RECORDS |
| | SHOWS 3010 AS A VERY SMALL PARCEL (POSSIBLY A ROAD) |
| | GOING THROUGH THE MIDDLE OF THE LARGER PARCEL, 3040. |
| | PLEASE CONTACT ME TO DISCUSS IF YOU ARE UNSURE AS TO |
| | HOW TO GET THIS MATTERS RESOLVED. |
| | |
| | 6.) FBC* 109.3.7RESIDENT INSPECTOR. SUBMIT INSPECTOR |
| | RESUME' AND LICENSE DOCUMENTS TO HAROLD PISKURA, |
| | DIRECTOR OF THE RESIDENT INSPECTOR PROGRAM.A RESIDENT |
| | INSPECTOR PROGRAM IS REQUIRED, ON THIS PROJECT, DUE TO |
| | ONE OR MORE OF THE FOLLOWING: |
| | - BUILDINGS/ADDITIONS OF TYPE I OR II |
| | CONSTRUCTION |
| | - ANY MAJOR STRUCTURAL ALTERATIONS |
| | - STRUCTURES IN WHICH THE CONCRETE |
| | DESIGN IS BASED ON COMPRESSIVE |
| | STRENGTH (F'C) IN EXCESS OF 3000 PSI |
| | - PILE DRIVING |
| | - BUILDINGS OVER 20,000 SQFT IN AREA |
| | - BUILDINGS OVER 2 STORIES IN HEIGHT |
| | - BUILDING/STRUCTURES OF UNUSUAL DESIGN OR METHODS |
| | OF CONSTRUCTION |
| | |
| | ALSO, PLEASE ARRANGE WITH HAROLD PISKURA (INSPECTION |
| | SERVICES MANAGER - TEL: |
| | 561 805 6711), A MEETING INVOLVING THE OWNER, RESIDENT |
| | INSPECTOR, JOB INSPECTOR, CONTRACTOR AND ENGINEER. THIS |
| | MUST BE DONE PRIOR TO PERMIT ISSUANCE.THREE ORIGINAL |
| | SETS OF ALL DOCUMENTS ARE REQUIRED FOR PERMITTING. |
| | |
| | 7.)THERE ARE TWO FULL SETS OF CIVILS WITH DIFFERENT |
| | DATES.MANY SHEETS APPEAR UNNECESSARY AS THEY ARE FOR |
| | OTHER BUILDINGS.THERE IS ALREADY A SITEWORK PERMIT |
| | PENDING.PLEASE COORDINATE WITH ENGINEERING; ANY CIVIL |
| | SHEETS REQUIRED IN THIS PACKAGE TO SHOW CODE COMPLIANCE |
| | IS TO MATCH OTHER APPROVED DRAWINGS.ALSO NOTE THAT |
| | THERE ARE DETAILS FROM THE CITY OF RIVIERA BEACH. |
| | |
| | 8.)RADON FEES DUE, FS553.721.SEE ATTACHED. |
| | |
| | 9.)A SEPARATE PERMIT WILL BE REQUIRED FOR THE SIGN |
| | SHOWN ON A-0.1.SEPARATE PLANS AND PERMIT APPLICATION |
| | WILL BE REQUIRED.NOTE THAT WIND DESIGN CRITERIA |
| | FBC1603.1.4 WILL BE REQUIRED.DESIGN CRITERIA SHOWN |
| | DOES NOT PROVIDE ALL REQUIRED INFORMATION. |
| | |
| | 10.)THE ACCESSIBLE ROUTE FROM THE PUBLIC WAY IS SHOWN |
| | ON A-0.1, SHOW SLOPE AND WIDTH FBC11-4.1.2(1). |
| | |
| | 11.)S2 DECLARED, SEE FBC302; IT APPEARS THAT THIS IS |
| | A MIXED USE DUE TO THE 5000 SF OF BUSINESS AREA, |
| | FBC302.3. |
| | |
| | 12.)S2 DECLARED, SEE FBC311.3, DEFINITION IS FOR |
| | NON-COMBUSTIBLE STORAGE.PROVIDE INFORMATION IN |
| | REGARDS TO WHAT WILL BE STORED AND WHAT ACTIVITY WILL |
| | TAKE PLACE IN THIS BUILDING.NOTE THAT PACKAGING MUST |
| | BE ADDRESSED AS WELL AS THE ITEMS STORED. |
| | |
| | 13.)THE FEDEX FREIGHT SITE PLAN (CIVIL) SHOWS A 10FT |
| | CANOPY.SEE FBC502, DEFINITION OF AREA, BUILDING. |
| | PLEASE CLARIFY WHAT THIS IS, AND SHOULD THIS BE |
| | INCLUDED IN BUILDING AREA? |
| | |
| | 14.)EXTRA FP1 SHEETS WERE SUBMITTED; NOT CLEAR AS TO |
| | WHY.PLEASE PROVIDE ONLY THREE COMPLETE ORIGINAL SETS |
| | FOR PERMITTING, COLLATED. |
| | |
| | 15.)ELECTRIC SHEETS SHOW EXIT LIGHTS LEADING TO THE |
| | WAREHOUSE AREA, NONE AT DOORS TO THE OUTSIDE.SEE |
| | FBC1006.3. |
| | |
| | 16.)PROVIDE A LIFE SAFETY PLAN, FBC*106.3.5.1.1(6) |
| | AND (7).INCLUDE THE FOLLOWING: |
| | OCCUPANT LOAD FOR EACH AREA, FBC302. |
| | EGRESS CAPACITIES, FBC1005. |
| | EXIT LIGHTS, FBC1006.3. |
| | EXITING INFORMATION, FBC10. |
| | ANY OTHER INFORMATION REQUIRED TO DETERMINE CODE |
| | COMPLIANCE |
| | |
| | 17.)FBC11-4.1.3(9), ACCESSIBLE MEANS OF EGRESS SHALL |
| | BE PROVIDED IN THE SAME NUMBER AS REQUIRED FOR EXITS BY |
| | LOCAL BUILDING/LIFE SAFETY REGULATIONS. A RAMP IS SHOWN |
| | AT THE BUILDING ENTRANCE, NO OTHER ACCESSIBLE EXITS |
| | SHOWN. |
| | |
| | 18.)THIS BUILDING REQUIRES MORE THAN ONE EXIT, SEE |
| | FBC1018.2. |
| | |
| | 19.)A1.0 SHOWS A CHECK WRITING STAND, REFERS TO DTL |
| | 4/A2.01.I COULD NOT LOCATE THAT SHEET.PROVIDE A |
| | DETAIL, OR CHANGE REFERENCE, AND SHOW ACCESSIBILITY |
| | FBC11-7.2. |
| | |
| | 20.)BREAK ROOM IS SHOWN AS POD AREA, WHAT DOES THIS |
| | MEAN? |
| | |
| | 21.)A1.0 SHOWS AN AREA OF RESCUE.DO YOU MEAN AREA |
| | OF RESCUE ASSISTANCE?IT IS ACCEPTABLE TO EXCEED CODE, |
| | BUT NOTE THAT THIS IS NOT REQUIRED FBC11-4.1.3(9) |
| | EXCEPTION.ALSO THIS IS FOR EXITS FROM OCCUPIABLE |
| | LEVELS ABOVE OR BELOW THE LEVEL OF THE MEANS OF |
| | ACCESSIBLE EXIT DISCHARGE.THIS IS THE LEVEL OF |
| | ACCESSIBLE EXIT DISCHARGE, SO AN ACCESSIBLE EXIT IS |
| | REQUIRED. |
| | |
| | 22.)FBC11-4.1.3(8)(A)(II), ACCESSIBLE ENTRANCES |
| | REQUIRED AT LEAST EQUIVALENT TO THE NUMBER OF |
| | ACCESSIBLE EXITS. |
| | |
| | 23.)EXIT OR EXIT ACCESS DOORWAY ARRANGEMENT SHALL |
| | COMPLY WITH FBC1014.2 OR FBC1014.2.2., SHOW DISTANCE |
| | APART, SEE EXCEPTION 2. |
| | |
| | 24.)S2.1, CONCRETE NOTE 1, REFERS TO ACI318-95, |
| | PLEASE USE CURRENT STANDARD.CHECK ALL REFERENCES. |
| | |
| | 25.)SIGN THE OWNER/AGENT LINE OF THE ENERGY CALC. |
| | |
| | 26.)IMPACT PROTECTION REQUIRED.NONIMPACT STOREFRONT |
| | PRODUCT APPROVALS WERE SUBMITTED.SEE ATTACHED POLICY, |
| | ITEM 13, IN REGARDS TO IMPACT PROTECTION ON COMMERCIAL |
| | BUILDINGS.USE IF REMOVABLE SHUTTERS ON COMMERCIAL |
| | BUILDINGS MUST BE APPROVED BY THE BUILDING OFFICIAL. |
| | |
| | |
| | 27.)IF YOU ARE USING HURRICANE SHUTTERS, SEE ATTACHED |
| | SCHEDULE FOR INSTALLATION.PROVIDE PRODUCT APPROVALS |
| | AND ALL REQUIRED INFORMATION TO DETERMINE CODE |
| | COMPLIANCE. |
| | |
| | 28.)SQUARE FOOT AREAS ON THE ENERGY CALCS DO NOT |
| | MATCH THE PLAN. |
| | |
| | 29.)THE ENGINEER'S TITLE BLOCK IS TO COMPLY WITH |
| | FAC61G15-23.002, VP BUILDINGS. |
| | |
| | 30.)INCLUDE THE CORRECT JURISDICTION ON THE ENERGY |
| | CALCS, 604700 FBC13. |
| | |
| | 31.)THE ENGINEER'S SIGNATURE IS A TITLE BLOCK, |
| | ORIGINAL WET SIGNATURE REQUIRED. |
| | |
| | 32.)PROVIDE ROOF DRAINAGE CALCULATIONS FBC1503.4. |
| | PROVIDE DETAILS, SHOW OVERFLOW. |
| | |
| | |
| | TO EXPEDITE PLAN REVIEW, INCLUDE A RESPONSE LETTER |
| | INDICATING HOW EACH ITEM WAS ADDRESSED WHEN |
| | RESUBMITTING. |