| Plan Review Notes For Permit 06090691 |
| Permit Number |
06090691 |
|
| Review Stop |
FIRE |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2007-04-03 13:46:54 | ****PROVISO***** | | | | | | | | | | | | | | | | | | | | | | | | | | | 20.FIRE ALARM SYSTEM IS TO BE CLASS A OR FULLY | | | ADDRESSABLE.PLEASE CORRECT TYPOGRAPHICAL ERROR IN | | | FIRE ALARM PLAN NOTE #3 (SEE SHEET E6.1 & E6.2); | | | WORDING SHOULD BE ADDRESSABLE NOT ACCESSIBLE..... | | | | | | | | | | | | | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|