| Date |
Text |
| 2007-01-12 17:10:50 | *****UNSAT 2ND REVIEW ****** |
| | |
| | FED-EX GROUND. |
| | |
| | ** PLEASE ADDRESSING ON PLANS SHALL BE REQUIRED TO |
| | CORRELATE. PLEASE SEE PERMIT APPLICATION, THE ASSIGNED |
| | ADDRESS AND PLANS DO NOT MATCH. PLEASE SEE THE ADDRESS |
| | SHALL APPEAR ON ALL SHEETS TITLE BLOCKS. FAC 61G1, |
| | 61G15 |
| | |
| | ** PLEASE SEE SOME COMMENTS FROM THE PREVIOUS REVIEWS |
| | WHICH ARE STILL IN NEED OF ADDRESSING. |
| | COMMENTS WILL BE IDENTIFIED AS FOLLOWS IN THE SAME |
| | NUMERICAL ORDER FROM THE PREVIOUS REVIEW. ANY NEW NOTES |
| | WILL BE ADDED TO THE END OF THE REVIEW. |
| | |
| | A) NO, MEANS THE COMMENT IS STILL IN NEED OF FURTHER OR |
| | CORRECTED INFORMATION. IT WILL BE FOLLOWED BY FURTHER |
| | EXPLANATION FOR MORE INFORMATION OR TO TRY AND BETTER |
| | EXPLAIN THE COMMENT. |
| | B) OK, IS COMMENT IS ADDRESSED AND THE PREVIOUS NOTE |
| | WILL BE REMOVED. |
| | C) NO/OK IS THAT PART OF THE COMMENT MAY HAVE BEEN |
| | ADDRESSED BUT NOT ALL. A FURTHER EXPLANATION WILL BE |
| | TYPED TO PROVIDE MORE INFORMATION FOR WHAT IS NEED. |
| | |
| | |
| | 1) NOTE:NO, PLEASE SEE THERE ARE NUMEROUS SHEETS IN |
| | ONE SET WHICH ARE NOT SIGNED, DATED OR SEALED AT ALL. |
| | PLEASE SEE YET ANOTHER SET ONLY CONTAINS ONE ELECTRICAL |
| | SHEET WHICH IS SIGNED, DATED AND SEALED.PLEASE SEE |
| | THE THIRD SETS ALSO. |
| | PLEASE SEE THE SAME SETS CONTAINS MANY MECHANICAL AND |
| | PLUMBING SHEETS WHICH ARE NOT SIGNED, DATED OR SEALED |
| | EITHER? |
| | PLEASE SEE OTHER SETS WHICH SOME SHEETS ARE SIGNED, |
| | DATED AND SEALED AND MANY OTHER SHEETS ARE NOT? |
| | PLEASE SEE OTHER DOCUMENTS WHICH ARE IN FACT |
| | PHOTO-COPIES OF SIGNED AND SEALED DOCUMENTS. |
| | AS PREVIOUSLY MENTIONED, ALL THREE SETS, ALL DOCUMENTS |
| | PREPARED BY THE DESIGNERS OF RECORD ARE REQUIRED TO |
| | CONTAIN AN ORIGINAL SIGNATURE, DATED AND A RAISED |
| | EMBOSSED SEALED AS REQUIRED IN THE SECTIONS OF THE |
| | FLORIDA ADMINISTRATIVE CODE AND FLORIDA STATUTES GIVEN |
| | ON PREVIOUS REVIEW. |
| | ** PLEASE KNOW, SETS OF PLANS MAY BE RETAINED BY THIS |
| | OFFICE. |
| | ** PLEASE ALSO KNOW THAT THIS COMMENT IS REQUIRED FOR |
| | ALL TRADES AND FOR ALL SHEETS WHETHER OR NOT COMMENT IS |
| | MADE BY ANY OTHER REVIEWER(S). |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE SEE ALL MEP SHEETS SHALL CONTAIN THE RAISED |
| | EMBOSSED SEAL FOR THE ENGINEER OF RECORD. PLEASE SEE |
| | FAC 61G15-23.001,FS 471.025 |
| | PLEASE ALSO SEE THE SEAL WHICH IS BEING INDICATED ON |
| | SAID MEP'S IS NO LONGER VALID WITH THE STATE OF |
| | FLORIDA. PLEASE SEE FAC 61G15-23.001, WHICH PASSED A |
| | RULING IN FEB 04" WHICH REQUIRED THE SEAL WORDING TO |
| | CHANGE FROM "CERTIFICATE" TO "LICENSE". PLEASE KNOW AN |
| | EXTENSION WAS GIVEN TO 12/31/05. |
| | |
| | 2) NOTE: OK. |
| | |
| | 3) NOTE: NO, THIS IS STILL REQUIRED AND IT HAS COME TO |
| | OUR ATTENTION THAT THE FIRM DOES NOT CONTAIN THE |
| | LICENSE NUMBER AS NEEDED AND AS REQUIRED PER SECTIONS |
| | GIVEN BELOW IN THE PREVIOUS REVIEW. PLEASE SEE RESPONSE |
| | MENTIONS THE ENGINEER WAS ADDED TO THE TITLE BLOCKS, |
| | HOWEVER THIS IS NOT THE ONLY REQUIRED INFORMATION. |
| | PLEASE ALSO KNOW THAT EVEN THOUGH THE ENGINEERING FIRM |
| | AS SHOWN IS LOCATED OUT OF STATE, THIS HAS NO BEARING |
| | ON THE REQUIREMENT. |
| | ** THE TITLE BLOCKS WERE REVISED FOR THE FOUNDATION |
| | PERMIT. IF THIS IS DONE, ADDRESS AND COMPLETED |
| | INFORMATION FOR THE INDIVIDUAL ENGINEER OF EACH TRADE |
| | IS REQUIRED TO BE COMPLETED. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE SEE MISSING REQUIRED INFORMATION ON TITLE |
| | BLOCKS. PLEASE SEE MISSING THE PRINTED LICENSE # OF |
| | ARCHITECT ON A SHEETS. PLEASE SEE THE MISSING |
| | INFORMATION AS REQUIRED ON ENGINEERING FIRM. PLEASE SEE |
| | MISSING CERTIFICATE OF AUTHORIZATION NUMBER. PLEASE SEE |
| | ALL TITLE BLOCKS FOR ALL SHEETS ARE REQUIRED TO MEET |
| | FAC 61G1-16.004, 61G15-23.002 AND FS 481.219, 471.023. |
| | ** REQUIRED FOR ALL WHETHER OR NOT COMMENT IS MADE BY |
| | OTHER REVIEWER(S). |
| | |
| | 4) NOTE: OK. |
| | |
| | 5) NOTE: NO, PLEASE SEE THE ENERGY CALCULATIONS |
| | SUBMITTED DO NOT COMPLY OR SUPPLY THE INFORMATION AS |
| | NEEDED UNDER 13-415.1AB.1 OR 13-415.2. PLEASE SEE THE |
| | SHEETS SUBMITTED, SOME ARE SIGNED AND SEALED AND SOME |
| | ARE NOT. |
| | PLEASE SEE LIGHTING PERFORMANCE ON PLANS INDICATES THE |
| | 2003 ICC WHICH IS NOT ADOPTED INTO THE STATE OF |
| | FLORIDA. |
| | PLEASE ALSO SEE THE ENTIRE BUILDING IS BEING DESIGNATED |
| | AS ONE USE? |
| | PLEASE SEE THE PREVIOUS NOTE AS THE COMPLIANCE |
| | BREAKDOWN REQUIRED FOR METHOD A SHOULD BE SUBMITTED |
| | SHOWING ALL INFORMATION AS NEEDED. |
| | THIS MAY NOT BE CONSIDERED INDUSTRIAL WORK. A CALL TO |
| | GO OVER USAGE MAY HELP. |
| | |
| | **PREVIOUS REVIEW NOTE** |
| | PLEASE SEE FBC 2004 FOR REQUIRED ENERGY CALCULATIONS. |
| | PLEASE SEE 1993 ASHAE/ ETC IS BEING REFLECTED ON SAID |
| | DOCUMENTS. PLEASE SEE FBC 2004 CHAPTER 13. |
| | 13-415.1.AB.1 |
| | PLEASE KNOW THESE WILL ALSO BE REQUIRED TO BE SIGNED, |
| | DATED AND SEALED AS REQUIRED ON NOTES ABOVE. PLEASE SEE |
| | THESE ARE ALSO STAMPED WITH A "RUBBER STAMP" FOR SAID |
| | SEAL AND CONTAINS "CERTIFICATE" IN SEAL. |
| | |
| | 6) NOTE:OK/NO. PLEASE SEE RESPONSE LETTER MENTIONS |
| | THAT THE ENTIRE BUILDING WILL BE OPERATING 24/7. THIS |
| | EXCEPTION SHALL BE NOTED AND STATED ON THE PLANS. |
| | PLEASE SEE NO INFORMATION FOR THE WORST CASE VOLTAGE |
| | DROP CALCULATIONS OR SCENARIOS COULD BE LOCATED ON |
| | PLANS. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE SEE CHAPTER 13 13-415.1.ABC.1.1, .1.2 AND .1.3 |
| | FOR MINIMUM LIGHTING CONTROLS REQUIRED. PLEASE PROVIDE |
| | PERFORMANCE CALCULATIONS PER 13-415.2, 13-415.2.ABC.1. |
| | PLEASE SEE TABLES AND SPACE BY SPACE METHODS. |
| | PLEASE PROVIDE SCHEDULING. |
| | PLEASE SEE ALL OF CHAPTER 13, BASED ON THE 2004 FBC. |
| | PLEASE PROVIDE ALL WORST CASE SCENARIO'S FOR VOLTAGE |
| | DROP CALCULATIONS PER13-413.1ABC.1 FOR BOTH BRANCH |
| | CIRCUIT AND FEEDERS. |
| | |
| | 7) NOTE:NO, THE ATTACHED DOCUMENTS DO NOT PROVIDE THE |
| | WIND LOAD INFORMATION, DO NOT SUPPLE THE MAXIMUM EPA, |
| | AND IF SUBMITTING SHOP/PRODUCTS, FOR COMPLIANCE AND |
| | SHOWING AND STATING THE INFORMATION ON PLANS, THEN ALL |
| | OF THESE DOCUMENTS FOR POLES, WIND LOAD INFORMATION AND |
| | EPA'S SHALL BE REVIEWED AND STAMPED/SIGNED BY THE |
| | ENGINEER OF RECORD. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE PROVIDE WIND LOAD CALCULATIONS FOR SITE LIGHTING |
| | POLES. PLEASE KNOW, THE BUILDING/STRUCTURAL REVIEWER |
| | WILL REVIEW SAID DOCUMENTS FOR ACTUAL WIND LOADS WHICH |
| | WILL BE REQUIRED TO SHOW EPA FOR PROPOSED FIXTURES. |
| | FBC 2004 140MPH. ETC. |
| | |
| | 8) NOTE:NO, PLEASE SEE RESPONSE MENTIONS DESIGN WILL |
| | MEET THIS; HOWEVER NO REVIEW FOR COMPLIANCE CAN BE DONE |
| | UNTIL PHOTO-METRICS ARE SHOWN FOR COMPLIANCE. THE |
| | LEVELS ARE BEING SUBMITTED FOR WAREHOUSE UNDER NORMAL, |
| | HOWEVER NO INFORMATION FOR CONDITIONS UNDER EMERGENCY |
| | OR OFFICE EGRESS AREAS IS SHOWN. |
| | |
| | ** PREVIOUS REVIEW NOTE** |
| | PLEASE PROVIDE MINIMUM PHOTO-METRICS FOR EGRESS |
| | LIGHTING PER NFPA-101 7.8, 7.9 |
| | PLEASE SEE NORMAL IS SHOWN, HOWEVER NEED TO SEE MIN |
| | UNDER EMERGENCY CONDITIONS. |
| | |
| | 9) NOTE: OK, AS NOTED HOWEVER SEE OTHER NEW COMMENTS AS |
| | THE PLANS WERE REVIEWED AS THIS MAIN DIST PANEL |
| | CONTAINING A SINGLE MCB RATED AT THE 1600AMPS. |
| | SEE NEW NOTES. |
| | |
| | 10) NOTE: OK. |
| | |
| | 11) NOTE: PLEASE SEE 110.9, 240.13 AND PROVIDE ALL |
| | MINIMUM REQUIRED AIC RATINGS AND SELECTIVE COORDINATION |
| | FOR EQUIPMENT AS SHOWN. PLEASE SHOW DETAIL FOR |
| | EQUIPMENT. |
| | |
| | 12) NOTE: NO, PLEASE SEE RESPONSE SAYS THE EGC IS |
| | AFTER; HOWEVER PLEASE SEE RISER NOTE WHICH SHOWS ALL |
| | PHASE CONDUCTORS AND AN EGC FROM THE FPL(LOCAL POWER |
| | COMPANY ) TRANSFORMER. |
| | PLEASE SEE RISER. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE SEE 250.6, 250.24B AS AN "EQUIPMENT GROUNDING |
| | CONDUCTOR" IS BEING SHOWN BEFORE THE FIRST MEANS OF |
| | DISCONNECT ON THE LINE SIDE OF THE MAIN. PLEASE KNOW |
| | THE EGC IS ONLY INSTALLED AFTER THE FIRST MEANS OF |
| | DISCONNECT. |
| | |
| | 13) NOTE: OK. |
| | |
| | 14) NOTE: NO, RESPONSE MENTIONS WHAT TO DO, HOWEVER |
| | WHERE IS THIS DETAIL ON PLANS AS PREVIOUSLY REQUESTED? |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE PROVIDE A STRUCTURAL SUPPORT DETAIL FOR BOTH |
| | TRANSFORMERS. |
| | PLEASE KNOW THIS STRUCTURAL DETAIL WILL BE REVIEWED BY |
| | BUILDING REVIEWER. |
| | FBC 106.1.2 |
| | |
| | 15) NOTE: OK. |
| | |
| | 16) NOTE:NO. PLEASE SEE RESPONSE MENTIONS THE MINIMUM |
| | LEVELS WHICH ARE REQUIRED PER ADA UNDER THE FBC AS |
| | EXCESSIVE. THESE ARE MINIMUM LEVELS. PLEASE SEE THE FBC |
| | DICTATES THE LEVELS WHICH ARE MORE RESTRICTIVE THAN |
| | THAT OF THE LEVELS IN NFPA-72. PLEASE SEE THAT THERE |
| | ARE MAXIMUM LEVELS WHICH ARE 1000 CD. |
| | THE LEVELS FOR THESE AREAS WHICH ARE TAKEN DIRECTLY |
| | FROM THE SECTIONS GIVEN MUST MEET THESE LEVELS AT A |
| | MINIMUM. |
| | AS REVIEWING THE RESPONSE IT HAS BEEN NOTED, HOWEVER |
| | THESE ARE STATED IN THE CODE THERE IS NO MENTION FOR |
| | EXCEPTIONS DUE TO MEDICAL CONDITIONS AS MENTIONED. |
| | PLEASE PROVIDE MORE INFORMATION FOR THESE LEVELS FROM |
| | THE FBC IF SECTIONS WRE INF THE CODE WHICH WILL SUPPORT |
| | THESE LESSER LEVELS. |
| | |
| | ** PREVIOUS REVIEW NOTES** |
| | PLEASE SEE FBC 11-4.28, 11-4.28.2 AND .3(4) WHICH |
| | REQUIRE A MIN OF 75 CANDELAS AT ALL AREAS AS STATED FOR |
| | ADA. PLEASE SEE MIN LEVELS STATED FOR ADA ON PLANS |
| | MENTIONS 15CD? |
| | PLEASE KNOW ALL OF THESE AREAS WILL BE TESTED FOR |
| | MINIMUM LEVELS, PLEASE BE SURE THE DEVICES AS SHOWN AND |
| | INSTALLED WILL MEET TESTED LEVELS. PLEASE ADJUST NOTES |
| | ON PLANS AT THIS TIME. |
| | |
| | 17) NOTE: OK. |
| | |
| | 18) NOTE: OK/NO, PLEASE SEE RESPONSE MENTIONS THAT ALL |
| | CONVEYOR SYSTEMS AND ELECTRICAL WORK WILL BE UNDER A |
| | SEPARATE PERMIT PLANS AND FEES. PLEASE SEE THE MDP |
| | SHOWS CONDUCTORS AND CONDUITS BEING INSTALLED AT THIS |
| | TIME YET THE RISER DOES NOT SHOW THESE CONDUITS BEING |
| | DONE AT THIS TIME. PLEASE ALSO SEE NEW NOTE WITH |
| | RESPECT TO THE AMOUNT OF MAINS. |
| | PLEASE ADJUST MDP IF THIS WORK IS NOT BEING DONE AT |
| | THIS TIME AS SHOWN ON RISER AS FUTURE. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE PROVIDE INFORMATION FOR CONVEYOR SYSTEM, PLEASE |
| | PROVIDE INFORMATION ON ALL LISTINGS FOR EQUIPMENT BRING |
| | INSTALLED. |
| | PLEASE PROVIDE SPECS ON THE MCC. |
| | 110.3, 90.7. |
| | FBC 106.1.2 |
| | |
| | 19) NOTE: OK. |
| | |
| | 20) NOTE:OK, THIS WAS ONLY NOTED A |
| | |
| | 21) NOTE: NO, PLEASE SEE RESPONSE MENTIONS THAT THE |
| | LOCK ON/OFF DEVICE WILL PART OF THE BREAKER, HOWEVER |
| | THIS IS ONLY BEING NOTED IN RESPONSE LETTER, PLEASE |
| | PLACE THIS NOTE ON PLANS RELEVANT TO THE PANEL |
| | SCHEDULES AND BREAKERS BEING INSTALLED. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE SEE PANEL NOTES MENTIONS "LOCK-OFF" BREAKERS, |
| | PLEASE KNOW THESE TYPE OF LOCK OFF DEVICES SHALL BE AN |
| | INTEGRAL PART OF THE BREAKER AND SHALL NOT BE REMOVABLE |
| | WITHOUT THE REMOVAL OF SAID BREAKER. 90.7, 110.3, 90.4 |
| | |
| | 22) NOTE: OK, FUELING STATION WILL NOT BE PART OF THIS |
| | PERMIT. |
| | |
| | ** NEW NOTES THIS REVIEW ** |
| | |
| | 23) NOTE: PLEASE SEE AS THE MDP CONTAINS MORE THAN SIX |
| | SPACES AND THEY ARE NOT BEING COMPLETED AND SPACES ARE |
| | NOT FILLED AT THIS TIME, A MCB WILL BE REQUIRED. OTHER |
| | OPTIONS WOULD BE TO INSTALL THE 3-POLE BREAKERS AS |
| | SPARES AT THIS TIME AND WILL BE REQUIRED TO BE SHOWN, |
| | OR THE PLANS SHALL BE NOTED THAT THE DEAD-FRONT FROM |
| | THE MANUFACTURE SHALL CONTAIN A PERMANENT FACTORY |
| | INSTALLED FILLER FOR THIS SECTION FOR 2D. |
| | 230.70, 230.71 90.4. |
| | PLEASE KNOW, THE OTHER OPTION WOULD BE TO INSTALL A |
| | 1600AMP MCB WITH GF PROTECTION. |
| | |
| | 24) NOTE: PLEASE SEE MDP WHICH SHOWS 1/0'S FOR THE |
| | FEEDERS TO THE TRANSFORMER FOR PP1, HOWEVER RISER SHOWS |
| | #1'S. PLEASE CORRELATE. |
| | PLEASE KEEP IN MIND THE VOLTAGE DROP AS PREVIOUSLY |
| | NOTED. |
| | |
| | 25) NOTE: PLEASE SEE FLORIDA STATUTES 553.80(2)(B) IS |
| | BEING GIVEN AS A NOTICE AT THIS TIME WITH RESPECT TO |
| | REPEAT COMMENTS FOR CODE COMPLIANCE. THIS IS ONLY A |
| | NOTICE; HOWEVER ONE SET OF PLANS MAY BE RETAINED. |
| | |
| | ** PLEASE KNOW AS THERE IS INFORMATION WHICH HAS NOT |
| | YET BEEN SUBMITTED FOR REVIEW, THERE MAY BE COMMENTS ON |
| | NEXT REVIEW WHICH ARE NOT STATED IN THESE REVIEW |
| | NOTES. |
| | |
| | |
| | *** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] ND IF IT IS AN ISSUE THEN RELOCATION |
| | WILL BE REQUIRED. |