| Date |
Text |
| 2006-10-20 15:28:51 | DENIED: |
| | 1.PLAN SHEET M1.1 INDICATES THE DESIGN IS TO THE |
| | INTERNATIONAL MECHANICAL CODE.THIS SHOULD READ 2004 |
| | FLORIDA BUILDING CODE/MECHANICAL. |
| | |
| | 2.PLAN SHEET M3.1 "KEYED NOTES" NUMBER 6 INDICATES |
| | THE INTAKE LOUVER FOR MAKE-UP AIR IS LOCATED 36" A.F.F. |
| | THIS APPEARS TO BE LOCATED IN A LOADING OR PARKING |
| | AREA.PER 2004 401.5.1 INTAKE OPENINGS SHALL BE |
| | LOCATED A MINIMUM OF 10 FT FROM ANY NOXIOUS CONTAMINANT |
| | SUCH AS PARKING LOTS, STREETS, ALLEYS, AND LOADING |
| | DOCKS.PLEASE CLARIFY. |
| | |
| | 3.PLAN SHEET M3.1 NOTE 3 INDICATES FUME SENSOR |
| | MOUNTED 5 FT A.F.F., MATCH TO EXISTING & CONNECT TO |
| | EXISTING SYSTEM.THE PERMIT APPLICATION INDICATES THIS |
| | IS A NEW BUILDING, WHAT WILL BE "EXISTING"? PROVIDE |
| | MANUFACTURE SUBMITTAL DATA FOR THE SENSOR.AT WHAT |
| | PARTS PER MILLION WILL THE SENSOR BE SET AT (25 PPM - |
| | PER 2004 FMC 404.1). |
| | |
| | 4.PLEASE INDICATE HOW THE REQUIREMENT FOR |
| | VENTILATION RATE OF .05 CFM PER SQUARE FT WHEN THE FANS |
| | WILL NOT RUN CONTINUOUSLY. |
| | |
| | 5.PLAN SHEET A2.1 DETAIL 1 (WEST ELEVATION), WHAT |
| | WILL BE USING THE DRIVE-IN DOOR, VEHICLES, FORK-LIFTS, |
| | ETC. |
| | |
| | 6.PLAN SHEET M3.1, PLEASE CLARIFY WHAT THE "SPECIAL |
| | HANDLING CAGE" WILL BE UTILIZED FOR.EF-10IS NOT |
| | INDICATED ON THE FAN SCHEDULE ON PLAN SHEET.PLAN |
| | SHEET M5.2 INDICATES AN EXHAUST FAN TO THE HOOD, IS |
| | THIS EF-10? |
| | |
| | 7.PLEASE INDICATE WHAT THE FUME HOOD WILL BE USED |
| | FOR. |
| | |
| | 8.PLAN SHEET M3.2 INDICATES DUCT SMOKE DETECTORS IN |
| | THE RETURN AIR DUCT.PER 2004 FMC 606.2.1, SMOKE |
| | DETECTORS ARE REQUIRED IN THE SUPPLY AIR DUCT. |
| | |
| | 9.PLEASE PROVIDE A DETAIL OF THE RTU ATTACHMENT TO |
| | THE ROOF.NO SUPPORT IS INDICATED ON THE STRUCTURAL, |
| | ARCHITECTURAL OR MECHANICAL PLANS.SHOW COMPLIANCE |
| | WITH 2004 FBC 1509.7. |
| | |
| | 10.PROVIDE LOCATION OF THE CONDENSING UNIT (GROUND OR |
| | ROOF). |
| | |
| | 11.PLEASE INDICATE ACCESS TO THE EQUIPMENT LOCATED ON |
| | THE ROOF.PER 2001 FMC 306.5, EQUIPMENT ON LOCATED ON |
| | ROOF OR ELEVATED STRUCTURE AT A HEIGHT GREATER THAN 16 |
| | FT SHALL HAVE A PERMANENT MEANS OF ACCESS.PLEASE |
| | NOTE,ACCESS SHALL NOT REQUIRE CLIMBING OVER |
| | OBSTRUCTIONS GREATER THAN 30 INCHES OR WALKING ON ROOFS |
| | HAVING A SLOPE GREATER THAN 4/12 PITCH. |
| | |
| | 12.PER 2004 FMC 306.6 ROOFS HAVING GREATER THAN 25% |
| | SLOPE AND HAVING AN EDGE MORETHAN 30 INCHES ABOVE GRADE |
| | AT SUCH EDGE, A LEVEL PLATFORM SHALL BE PROVIDED ON |
| | EACH SIDE OF THE APPLIANCETO WHICH ACDESS IS REQUIRED |
| | BY THE MANUFACTURER'S INSTALLATION INSTRUCTIONS FOR |
| | SERVICE, REPAIR OR MAINTENANCE.THE PLATFORM SHALL NOT |
| | BE LESS THAN 30 INCHES IN ANY DIMENSION AND BE PROVIDED |
| | WITH GUARDS IN ACCORDANCE WTIH SECTION 304.10. |
| | |
| | 13.PLEASE PROVIDE MOUNTING DETAIL FOR SF1 THROUGH |
| | 7.13. |
| | |
| | 14.PLANS DO NOT INDICATE OVERFLOW PROTECTION AS |
| | REQUIRED IN 2004 FMC 307.2.3. |
| | |
| | 15.PLAN SHEET A0,2 INDICATES "FUTURE FUEL ISLAND & |
| | MAITENANCE GARAGE"WILL THIS BE UNDER A SEPARATE |
| | PERMIT? |
| | |
| | 16.PLEASE PROVIDE OUTSIDE AIR CALCULATIONS IN |
| | ACCORDANCE WITH 2004 FMC TABLE 403.3. |
| | |
| | 17.PLEASE PROVIDE ENERGY CALCULATIONS IN ACCORDANCE |
| | WITH 2004 FBC CHAPTER 13 SUB-CHAPTER 4. |
| | |
| | 18.PER FAC 61G15-23.001(1), SEALS ARE TO BE EMBOSSED |
| | (RAISED) TYPE,STAMPS ARE NOT ACCEPTABLE.ENGINEERS |
| | SHALL LEGIBLY INDICATE NAME, ADDRESS, AND NUMBER ON |
| | EACH SHEET. |
| | |
| | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT PATTY KRAUSS |
| | AT (561)805-6719 OR E-MAIL [email protected]. |
| | |
| | |
| | |