| 2006-11-06 14:36:09 | *****DENIED***** |
| | |
| | |
| | |
| | 01.NFPA 101 - 2003 EDITION AND FLORIDA FIRE |
| | PREVENTION CODE - 2004 EDITION SHALL BE REFERENCED. |
| | |
| | 02.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR |
| | DEMOLITION SHALL COMPLY WITH NFPA241. |
| | |
| | 03.CONSTRUCTION AND/OR DEMOLITION OPERATIONS SHALL |
| | NOT INTERFERE OR HINDER EMERGENCY ACCESS TO THE SAID |
| | PROPERTY OR VICINITY THEREOF. |
| | |
| | 04.ALL PAVEMENT ROAD SYSTEMS SHALL BE CAPABLE OF |
| | SUPPORTING 32 TONS FOR FIRE EQUIPMENT. |
| | |
| | 05.LANDSCAPING SHALL NOT OBSTRUCT OR INTERFERE WITH |
| | FIRE PROTECTION EQUIPMENT.PROPER CLEARANCES SHALL BE |
| | MAINTAINED AT ALL TIMES. |
| | |
| | 06.SHOW/DISPLAY THE NUMERICAL ADDRESS OF THE BUILDING |
| | ON THE PROPER ELEVATION.AS PER WEST PALM BEACH CODE, |
| | THOSE NUMBERS SHALL BE NO LESS THAN 6" IN HEIGHT AND 1" |
| | IN WIDTH.IF A MONUMENT SIGN OR MARKEE IS REQUIRED, A |
| | NUMERICAL ADDRESS WILL ALSO BE POSTED.IF THERE ARE |
| | GOING TO BE SEVERAL ADDRESSED BUILDINGS WITHIN THE FED |
| | EX COMPLEX, A RANGE OF ADDRESSES FROM THE LOWEST TO THE |
| | HIGHEST WILL BE REQUIRED ON THE MONUMENT SIGN OR |
| | MARKEE. |
| | |
| | 07.FIRE DEPARTMENT CONNECTIONS (FDC'S) SHALL BE |
| | POSITIONED SO THAT THEY CANNOT BE BLOCKED BY STORAGE, |
| | VESSELS, EQUIPMENT, ETC. |
| | |
| | 08.KNOX LOCKING CAPS ARE REQUIRED FOR NEW FIRE |
| | DEPARTMENT CONNECTIONS. |
| | |
| | 09.ELECTRONIC SWITCHES IN ADDITION TO CHAIN AND LOCK |
| | IS REQUIRED FOR DOUBLECHECK DETECTOR ASSEMBLY. |
| | |
| | 10.KNOX BOX FOR THE BUILDING WILL BE REQUIRED. PLEASE |
| | CONTACT THE FIRE PREVENTION BUREAU AT (561) 804-4724 |
| | FOR APPLICATIONS. |
| | |
| | 11.WILL THERE BE SECURITY GATES TO THE PREMISES AND |
| | IF SO, HOW WILL THE MEANS OF EGRESS BE IMPACTED? |
| | |
| | 12.PLEASE PROVIDE PRESCIPTIVE STRENGHT FOR ALL |
| | HANDRAILS / GUARDRAILS. |
| | |
| | 13.ALL FIRE DOORS AND WINDOWS SHALL COMPLY WITH NFPA |
| | 80. |
| | |
| | 14.INTERIOR FINISH FOR WALLS AND CEILING IN EXITS AND |
| | EXIT ACCESS CORRIDORS SHALL BE CLASS "A" OR CLASS "B". |
| | |
| | 15.LIFE SAFETY PLAN SHALL INCLUDE ALL COMMON PATHS OF |
| | TRAVEL TO EXITS. |
| | |
| | 16.FIRE EXTINGUISHERS ARE TO BE RATED 2A-10BC. |
| | |
| | 17.SEPARATE SHOP DRAWINGS AND PERMITS ARE REQUIRED |
| | FOR FIRE SPRINKLER AND FIRE ALARM SYSTEMS. |
| | |
| | 18.FIRE SPRINKLER SYSTEM IS TO BE MONITORED. |
| | |
| | 19.THE FIRE ALARM SHALL BE UL CERTIFIED FOR CENTRAL |
| | STATION SERVICE. |
| | |
| | 20.FIRE ALARM SYSTEM IS TO BE CLASS A OR FULLY |
| | ADDRESSABLE. |
| | |
| | 21.DELAYED-EGRESS LOCKS AND/ORACCESS-CONTROLLED |
| | EGRESS DOORS SHALL COMPLY WITH NFPA 101, CH. 7.2.1.6, |
| | SPECIAL LOCKING ARRANGEMENTS. |
| | |
| | |
| | |
| | |
| | |
| | CAPT. MICHAEL A. WILLIAMS |
| | FIRE PLAN REVIEW |
| | 561-805-6722 |