| 2006-10-19 15:23:29 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | |
| | FBCFLORIDA BUILDING CODE 2004 |
| | FBC EBFLORIDA BUILDING CODE 2004 |
| | EXISTING BUILDING CODE |
| | FBC*CITY OF WEST PALM BEACH |
| | AMENDMENTS TO THE FBC2004 |
| | |
| | 1.)A NOTICE OF COMMENCEMENT WILL BE REQUIRED PRIOR TO |
| | PERMIT PICKUP, FS713.13. |
| | 2.)IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY |
| | PRIOR TO PERMIT ISSUANCE, 2300 N JOG RD.PLEASE CALL |
| | 561-233-5025 FOR MORE INFORMATION. |
| | |
| | 3.)THE COPY OF THE PLAT PROVIDED IS NOT RECORDED. |
| | PLEASE ADVISE AS TO STATUS.IF THIS IS RECORDED, |
| | PROVIDE PLAT FILING INFORMATION (BOOK/PAGE). |
| | |
| | 4.)THE PLAT PROVIDED AND THE PROPOSED PLAT LINES ON |
| | THE OVERALL SITE PLAN PREPARED BY BOWYER SINGLETON DO |
| | NOT MATCH.FOR INSTANCE, THE CIRCULAR SECTION AT THE |
| | END OF THE ROAD (PARCEL G) DOES NOT APPEAR ON THE |
| | OVERALL SITE PLAN.THE PLAT LINES ARE INCOMPLETE ON |
| | THE OVERALL SITE PLAN. |
| | |
| | 5.)THE APPLICATION REFERS TO TWO DIFFERENT PARCEL ID |
| | NUMBERS.YOU CANNOT CROSS PROPERTY LINES.PROVIDE |
| | INFORMATION IN REGARDS TO THE LOCATION OF THE TWO |
| | PARCELS, ENDING IN 3010 AND 3040.OUR GIS RECORDS |
| | SHOWS 3010 AS A VERY SMALL PARCEL (POSSIBLY A ROAD) |
| | GOING THROUGH THE MIDDLE OF THE LARGER PARCEL, 3040. |
| | PLEASE CONTACT ME TO DISCUSS IF YOU ARE UNSURE AS TO |
| | HOW TO GET THIS MATTERS RESOLVED. |
| | |
| | 6.) FBC* 109.3.7RESIDENT INSPECTOR. SUBMIT INSPECTOR |
| | RESUME' AND LICENSE DOCUMENTS TO HAROLD PISKURA, |
| | DIRECTOR OF THE RESIDENT INSPECTOR PROGRAM.A RESIDENT |
| | INSPECTOR PROGRAM IS REQUIRED, ON THIS PROJECT, DUE TO |
| | ONE OR MORE OF THE FOLLOWING: |
| | - BUILDINGS/ADDITIONS OF TYPE I OR II |
| | CONSTRUCTION |
| | - ANY MAJOR STRUCTURAL ALTERATIONS |
| | - STRUCTURES IN WHICH THE CONCRETE |
| | DESIGN IS BASED ON COMPRESSIVE |
| | STRENGTH (F'C) IN EXCESS OF 3000 PSI |
| | - PILE DRIVING |
| | - BUILDINGS OVER 20,000 SQFT IN AREA |
| | - BUILDINGS OVER 2 STORIES IN HEIGHT |
| | - BUILDING/STRUCTURES OF UNUSUAL DESIGN OR METHODS |
| | OF CONSTRUCTION |
| | |
| | ALSO, PLEASE ARRANGE WITH HAROLD PISKURA (INSPECTION |
| | SERVICES MANAGER - TEL: |
| | 561 805 6711), A MEETING INVOLVING THE OWNER, RESIDENT |
| | INSPECTOR, JOB INSPECTOR, CONTRACTOR AND ENGINEER. THIS |
| | MUST BE DONE PRIOR TO PERMIT ISSUANCE.THREE ORIGINAL |
| | SETS OF ALL DOCUMENTS ARE REQUIRED FOR PERMITTING. |
| | |
| | 7.)VALUATION ADJUSTMENT DONE USING BUILDING VALUATION |
| | DATA FROM THE ICC WEBSITE, SEE ATTACHED BILL. |
| | |
| | 8.)RADON FEES DUE, FS553.721.SEE ATTACHED BILL. |
| | |
| | 9.)PROVIDE COMPONENTS & CLADDING PRESSURES, |
| | FBC1603.1.4. |
| | |
| | 10.)THE ACCESSIBLE ROUTE FROM THE PUBLIC WAY IS SHOWN |
| | ON THE OVERALL SITE PLAN, SHOW SLOPE AND WIDTH |
| | FBC11-4.1.2(1). |
| | |
| | 11.)S2 DECLARED, SEE FBC311.3, DEFINITION IS FOR |
| | NON-COMBUSTIBLE STORAGE.PROVIDE INFORMATION IN |
| | REGARDS TO WHAT WILL BE STORED AND WHAT ACTIVITY WILL |
| | TAKE PLACE IN THIS BUILDING.HOW WILL YOU CONTROL THE |
| | SHIPPING OF COMBUSTIBLES SUCH AS PAPER AND BOOKS?NOTE |
| | THAT PACKAGING MUST BE ADDRESSED AS WELL AS THE ITEMS |
| | STORED. |
| | |
| | 12.)IF NECESSARY, REVISE TRAVEL DISTANCE, OCCUPANT |
| | LOAD, ANY OTHER ITEMS AFFECTED BY ITEM 11. |
| | |
| | 13.)PROVIDE A LIFE SAFETY PLAN, FBC*106.3.5.1.1(6) |
| | AND (7).INCLUDE THE FOLLOWING: |
| | EGRESS CAPACITIES, FBC1005. |
| | INDICATE ACCESSIBLE EXITS FBC11-4.1.3(9) |
| | ANY OTHER INFORMATION REQUIRED TO DETERMINE CODE |
| | COMPLIANCE |
| | |
| | 14.)3-A9.2, PROVIDE A GUARD DETAIL IN COMPLIANCE WITH |
| | FBC1012 AND FBC1607.7. |
| | 15.)2-A9.2, THE HANDRAIL EXTENSIONS ARE TO COMPLY |
| | WITH FBC1009.11.5.ANY ACCESSIBLE STAIRS ARE TO ALSO |
| | COMPLY WITH FBC11-4.9.4. |
| | |
| | 16.)SEE FBC11-4.1.3(8)(III), WHERE FEASIBLE, |
| | ACCESSIBLE ENTRANCES SHALL BE THE ENTRANCES USED BY THE |
| | MAJORITY OF PEOPLE VISITING OR WORKING IN THE BUILDING. |
| | IT IS NOT CLEAR IF THE WAREHOUSE ENTRY IS ACCESSIBLE. |
| | |
| | 17.)FBC11-4.1.3(9), ACCESSIBLE MEANS OF EGRESS SHALL |
| | BE PROVIDED IN THE SAME NUMBER AS REQUIRED FOR EXITS BY |
| | LOCAL BUILDING/LIFE SAFETY REGULATIONS; MORE THAN ONE |
| | EXIT REQUIRED FROM THE STORAGE AREA DUE TO OCCUPANT |
| | LOAD, FBC10181.2. A RAMP IS SHOWN AT THE BUILDING |
| | ENTRANCE, NO OTHER ACCESSIBLE EXITS SHOWN.IT IS NOT |
| | CLEAR IF THE STOOPS SHOWN AT THE DOORS AT GRADE LEVEL |
| | ARE AT THE SAME ELEVATION AS THE ASPHALT OR IF THEY ARE |
| | HIGHER.PLEASE CLARIFY ON THE PLAN. |
| | |
| | 18.)FBC11-4.1.3(8)(A)(II), ACCESSIBLE ENTRANCES |
| | REQUIRED AT LEAST EQUIVALENT TO THE NUMBER OF |
| | ACCESSIBLE EXITS. |
| | |
| | 19.)72 INCHES OF STRAIGHT AND LEVEL CLEARANCE |
| | REQUIRED AT THE BOTTOM OF THE RAMP, FBC11-4.8.4(2). |
| | |
| | 20.)A3.1 DOES NOT SHOW AN ELEVATION CHANGE INSIDE OF |
| | THE BUILDING, BUT THE ELEVATIONS ON A2.1 SHOW A RAMP TO |
| | THE EAST DOOR, SOUTH ELEVATION, BUT THE OTHER DOOR IS |
| | SET AT GRADE.PLEASE CLARIFY. |
| | |
| | 21.)SPECIFY INTERIOR FINISH CLASSIFICATION, FBC TABLE |
| | 803.5. |
| | |
| | 22.)ENERGY CALCS REQUIRED.WHEN SUBMITTING, SIGN THE |
| | OWNER/AGENT LINE OF THE ENERGY CALC, VERIFY THAT SF |
| | AREA ON THE ENERGY CALC MATCHES THE SF ON THE PLAN, AND |
| | INCLUDE CORRECT JURISDICTION CITY OF WEST PALM BEACH, |
| | 604700. |
| | |
| | 23.)IMPACT PROTECTION REQUIRED.NONIMPACT STOREFRONT |
| | PRODUCT APPROVALS WERE SUBMITTED.SEE ATTACHED POLICY, |
| | ITEM 13, IN REGARDS TO IMPACT PROTECTION ON COMMERCIAL |
| | BUILDINGS.USE IF REMOVABLE SHUTTERS ON COMMERCIAL |
| | BUILDINGS MUST BE APPROVED BY THE BUILDING OFFICIAL. |
| | |
| | |
| | 24.)IF YOU ARE USING HURRICANE SHUTTERS, SEE ATTACHED |
| | SCHEDULE FOR INSTALLATION.PROVIDE PRODUCT APPROVALS |
| | AND ALL REQUIRED INFORMATION TO DETERMINE CODE |
| | COMPLIANCE. |
| | |
| | 25.)FLORIDA STATE OR LOCAL PRODUCT APPROVALS REQUIRED |
| | IN ADDITION TO THE NOA SUBMITTED, FAC9B72. |
| | WWW.FLORIDABUILDING.ORG FOR MORE INFORMATION. |
| | |
| | 26.)ENGINEERING FOR VP BUILDINGS, DECLARE GOVERNING |
| | CODE. |
| | |
| | 27.)MECHANICAL EQUIPMENT LOADS NOT ADDRESSED ON THE |
| | VP BUILDING STRUCTURALS. |
| | |
| | 28.)THE ENGINEER'S SIGNATURE IS A PHOTOCOPY (VP). SEE |
| | FAC61G15-23.002. |
| | |
| | 29.)ENGINEER'S TITLE BLOCK IS TO COMPLY WITH |
| | FAC61G15-23.002. |
| | |
| | 30.)THE ARCHITECT SPECIFIES IMPACT GLASS, NONIMPACT |
| | PRODUCT APPROVALS SUBMITTED. |
| | |
| | 31.)ROOF DRAINAGE IS TO COMPLY WITH FBC1503.4. |
| | PROVIDE CALCULATIONS AND DETAILS FOR SCUPPERS AND |
| | OVERFLOW SCUPPERS. |