2006-09-26 00:00:00*****APPROVED***** W/REMINDERS
  
  
  
  
 1.) AS PER WPB FIRE PREVENTION (AHJ),
 DUCT SMOKE DETECTORS SHALL ACTIVATE A
 GENERAL FIRE ALARM; NOT AS A SUPERVISORY
 AS RECORDED IN THE FIRE ALARM SEQUENCE
 OF OPERATION NOTES (SHEET FA-14).
  
 2.) FIRE SPRINKLER WATERFLOW TO ACTIVATE
 A GENERAL FIRE ALARM WITHIN 45 TO 60
 SECONDS.
  
 3.) INSTALL/POST UL CERTIFICATE AT THE
 FIRE ALARM CONTROL PANEL AND PROVIDE A
 COPY TO WPB FIRE PREVENTION BY THE FINAL
 FIRE ALARM INSPECTION.
  
  
  
  
  
  
  
  