| Plan Review Notes For Permit 06090675 |
| Permit Number |
06090675 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2006-09-26 00:00:00 | *****APPROVED***** W/REMINDERS | | | | | | | | | | | | | | | 1.) AS PER WPB FIRE PREVENTION (AHJ), | | | DUCT SMOKE DETECTORS SHALL ACTIVATE A | | | GENERAL FIRE ALARM; NOT AS A SUPERVISORY | | | AS RECORDED IN THE FIRE ALARM SEQUENCE | | | OF OPERATION NOTES (SHEET FA-14). | | | | | | 2.) FIRE SPRINKLER WATERFLOW TO ACTIVATE | | | A GENERAL FIRE ALARM WITHIN 45 TO 60 | | | SECONDS. | | | | | | 3.) INSTALL/POST UL CERTIFICATE AT THE | | | FIRE ALARM CONTROL PANEL AND PROVIDE A | | | COPY TO WPB FIRE PREVENTION BY THE FINAL | | | FIRE ALARM INSPECTION. | | | | | | | | | | | | | | | | | | | | | | | | | | | LT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|