| Date |
Text |
| 2006-11-28 09:58:50 | ***********UNSAT ************* |
| | |
| | PUBLIX GENERATOR |
| | 831 VILLAGE, #319 |
| | |
| | ** PLEASE SEE THE SAME PLANS AS PREVIOUSLY SUBMITTED |
| | ARE SUBMITTED BACK WITH OUT ANY CHANGES. |
| | |
| | 1) NOTE:PLEASE SEE THE VALUE HAS BEEN ADJUSTED. |
| | PLEASE SEE AN AMOUNT OF FEES DUE ARE $1975.80. |
| | THIS IS DUE BEFORE PLANS CAN BE PICKED UP. |
| | |
| | 2) NOTE:PLEASE SEE NOTE FROM PERVIOUS REVIEW WITH |
| | RESPECT TO THE EQUIPMENT SPECS. PLEASE SEE NONE WERE |
| | SUBMITTED IN PERMIT APPLICATION PACKAGE. PLEASE SEE |
| | NOTE BELOW WAS FROM PREVIOUS REVIEW. |
| | THE EQUIPMENT ON THE PREVIOUS PROJECT HAS NOT BEEN |
| | FINALIZED AND THERE IS STILL QUESTION ON THE |
| | EQUIPMENT. |
| | |
| | ** PREVIOUS NOTE ** |
| | PLEASE SUBMIT SPECS/MANUFACTURE CUT SHEETS.APS/ ATS |
| | DO NOT INDICATE THE REQUIRED MEANS OF DISCONNECT AS |
| | REQUIRED BY 230.76, 230.79, 225.31-39. |
| | PLEASE SEE A MANUAL MEANS OF DISCONNECT COULD NOT BE |
| | LOCATED RATED FOR THE LOAD SERVED ON THE OUTSIDE OF |
| | EQUIPMENT SUBMITTED. |
| | THIS WAS NEVER VERIFIED FROM PREVIOUS PERMIT PULLED FOR |
| | PREVIOUS PROJECT. |
| | NO PERMITS WILL BE RELEASED UNLESS THIS IS VERIFIED ON |
| | ALL SUBMITTED SPECS AND PLANS SUBMITTED BEFORE PERMIT |
| | IS ISSUED. |
| | PLEASE SEE ALL EQUIPMENT SHALL BE LISTED FOR USE.90.7, |
| | 110.3 |
| | |
| | 3) NOTE: PLEASE SEE THE RELAY DEVICE AS BEING NOTED IN |
| | THE RESPONSE LETTER IS NOT AN ACCEPTABLE MEANS OF OCP |
| | AS NOTED IN THE RESPONSE LETTER. |
| | |
| | ** PREVIOUS REVIEW NOTE** |
| | PLEASE INDICATE THE OCP AT THE |
| | GEN. PLEASE SEE 445.13 AS IT HAS COME TO OUR ATTENTION |
| | ON A PREVIOUS PROJECT THAT THE GEN MAY NOT CONTAIN OCP |
| | AND CAN NOT BE VERIFIED AT THIS TIME. |
| | |
| | 4) NOTE:PLEASE SUBMIT AND INDICATE ALL LOAD |
| | CALCULATIONS OR HIGHEST DEMAND LOADS ON PLANS. MAY NOT |
| | BE IN RESPONSE LETTER AS THE ENGINEER OF RECORD SHALL |
| | SIGN, DATE AND SEAL INFORMATION PROVIDED. PLEASE ADJUST |
| | PLANS AND INCLUDE. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE SEE NO LOAD CALCULATIONS WERE SUBMITTED FOR |
| | REVIEW. PLEASE SUBMIT. |
| | PLEASE SUBMIT AND INDICATE ANY LOAD SHEDDING DETAILS IF |
| | APPLICABLE. |
| | 702.5, 220 |
| | |
| | 5) NOTE: PLEASE SEE FBC CHAPTER 27, AS THIS HAS NOT |
| | BEEN REVISED TO INCLUDE AN EXCEPTION FOR EXCLUSION OF |
| | OPTIONAL STAND-BY SYSTEMS. PLEASE SEE2002 NFPA-70, 2002 |
| | NFPA-110. |
| | PLEASE SEE PLANS SHALL INDICATE ALL RELEVANT CODES. ** |
| | PREVIOUS REVIEW NOTE ** |
| | PLEASE SEE PLANS SHALL INDICATE THE CURRENT CODES IN |
| | EFFECT FOR INSTALLATION AS FOLLOWS. |
| | PLEASE SEE FBC 2004 CHAPTER 27 FOR ADOPTED CODES |
| | RELEVANT TO POWER GENERATORS. |
| | |
| | |
| | 6) NOTE: PLEASE CLARIFY THE COMPLETE GROUNDING |
| | ELECTRODE SYSTEM, PLEASE CLARIFY AND SHOW THE COLD |
| | WATER PIPE, SPRINKLER ETC. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE SEE THE APS/ATS IS BECOMING THE NEW FIRST MEANS |
| | OF DISCONNECT HOWEVER THE NEW GROUNDING ELECTRODE |
| | SYSTEMS DOES NOT SEEM TO BE COMPLETE AS PER 250.50. |
| | PLEASE SEE GROUNDING DETAIL MENTIONS NEW SLAB STEEL |
| | WHICH IS OK, HOWEVER PLEASE INDICATE ATTACHMENT. THESE |
| | NEW SLAB/STEEL ATTACHMENTS DO NOT MEET THE MIN |
| | REQUIREMENTS. |
| | PER 250.50,250.52, 250.104 |
| | IF SLAB STEEL IS ONLY BEING BONDED THEN PLEASE |
| | INDICATE. |
| | PLEASE COMPLETE GROUNDING ELECTRODE SYSTEM(S) AND |
| | BONDING FOR ALL AS ABOVE. |
| | |
| | 7) NOTE: PLEASE SEE RESPONSE NOW MENTIONS THIS UNIT |
| | BEING A BI-FUEL UNIT, HOWEVER THE MANUFACTURE SPECS/CUT |
| | SHEETS SUBMITTED WERE NOT CHANGED, INFORMATION FOR THIS |
| | SYSTEM WAS NOT SUBMITTED AND GAS RISER INFORMATION WAS |
| | NOT SUBMITTED. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE KNOW, BASED ON A PREVIOUS PROJECT, IS THIS |
| | UNIT GOING TO BE "BI-FUEL"?? |
| | IF SO, SUBMIT ALL INFORMATION AND SPECS ON UNIT(S). |
| | 90.7, 110.3 |
| | |
| | |
| | |
| | ** ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | |
| | |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |