| Plan Review Notes For Permit 06090668 |
| Permit Number |
06090668 |
|
| Review Stop |
M |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2008-04-04 14:34:58 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE & | | | REFERENCED CODES WITH 05, 06 REVISIONS, CITY OF WEST | | | PALM BEACH AMENDMENTS TO CHAPTER 1 (WPB), FLORIDA | | | ADMINISTRATIVE CODE (FAC), AND FLORIDA STATUTES (FS). | | | | | | *** DENIED *** | | | 1) AS NOTED IN LAST REVIEW 9/6/08 NOTE #1. THE | | | GENERATOR HAS A 1,000 GALLON DIESEL FUEL STORAGE TANK | | | BELOW IT AND NEEDS TO COMPLY WITH NFPA 30 TABLE | | | 4.3.2.1.1(B) WHICH REQUIRES THE TANK TO BE 15 FEET FROM | | | A PROPERTY LINE THAT IS OR CAN BE BUILT UPON. PLAN SHOW | | | THE TANK IS 10'-11" FROM THE WEST PROPERTY LINE, PLEASE | | | CORRECT. | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729 | | | E-MAIL; [email protected] |
|