| Plan Review Notes For Permit 06090668 |
| Permit Number |
06090668 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2006-12-05 12:36:42 | *****DENIED***** | | | | | | | | | | | | 1.PLEASE SHOW/DISPLAY THE LOCATION OF THE PROPOSED | | | GENERATOR IN RELATIONSHIP TO THE BUILDING(S), | | | STREETS/ROADWAYS, ETC IN THE IMMEDIATE VICINITY. | | | | | | 2.CONSTRUCTION OPERATIONS SHALL NOT INTERFERE OR | | | HINDER EMERGENCY RESPONDERS ACCESS TO THE SAID PROPERTY | | | OR VICINITY THEROF. | | | | | | 3.WILL THE PROPOSED GENERATOR BE TIED INTO THE FIRE | | | ALARM SYSTEM CURRENTLY BEING USED AT PUBLIX? | | | | | | 4.HOW WILL THE PROPOSED STRUCTURE BE PROTECTED FROM | | | VEHICULAR DAMAGE? | | | | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE | | | LETTER INDICATING HOW/WHERE EACH ITEM WAS ADDRESSED. | | | | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|