| Date |
Text |
| 2006-10-06 00:00:00 | ***********UNSAT ************* |
| | |
| | PUBLIX GENERATOR |
| | HAVERHILL, #821 |
| | |
| | 1) NOTE:PLEASE ADJUST VALUE FOR |
| | COMPLETE SCOPE OF WORK BEING APPLIED |
| | FOR. THE VALUE OF $10K ON PERMIT |
| | APPLICATION AUBMITTED IS EXTREMELY LOW |
| | PLEASE KNOW, THAT VALUE SHALL BE |
| | ALL LABOR AND MATERIALS EVEN IF |
| | MATERIALS ARE OWNER SUPPLIED. PLEASE SEE |
| | VALUE FOR LABOR AND INSTALLATION IS WAY |
| | LOW FOR SCOPE PF WORK. PLEASE SEE FBC |
| | 2004, ADMINISTRATIVE CODE SECTION 108.3 |
| | AS ADOPTED BY THE CITY OF WEST PALM |
| | BEACH. |
| | PLEASE KNOW, A VALUE WILL BE ASSESSED |
| | USING THE MARSHALL'S& SWIFT GUIDE. |
| | PLEASE KNOW, UNDER CONTRACTING LAWS AND |
| | RULES SET UP AND ADOPTED INTO FLORIDA |
| | STATUES, 489, FBC ADMINISTRATIVE SECTION |
| | 105.5.1 ANY INFORMATION PROVIDED ON |
| | OFFICAL PERMIT APPLICATION IF KNOWINGLY |
| | BEING FALSIFIED CAN VOID/REVOKE SUCH |
| | PERMIT/ APPLICATION. |
| | |
| | 2) NOTE: PLEASE KNOW, ANY SYSTEMS |
| | LOCATED IN A FLOOD ZONE "A" WILL BE |
| | REQUIRED TO BE MOUNTED AT A MIN OF 6" |
| | ABOVE BFE. PLEASE SEE BUILDING REVIEW |
| | COMMENTS. |
| | |
| | 3) NOTE: PLEASE SUBMIT SPECS/MANUFACTURE |
| | CUT SHEETS.APS/ ATS DO NOT INDICATE |
| | THE REQUIRED MEANS OF DISCONNECT AS |
| | REQUIRED BY 230.76,230.79,225.31-39. |
| | PLEASE SEE A MANUAL MEANS OF DISCONNECT |
| | COULD NOT BE LOCATED RATED FOR THE LOAD |
| | SERVED ON THE OUTSIDE OF EQUIPMENT |
| | SUBMITTED. |
| | THIS WAS NEVER VERIFIED FROM PREVIOUS |
| | PERMIT PULLED FOR PREVIOUS PROJECT. |
| | NO PERMITS WILL BE RELEASED UNLESS THIS |
| | IS VERIFIED ON ALL SUBMITTED SPECS AND |
| | PLANS SUBMITTED BEFORE PERMIT IS ISSUED. |
| | PLEASE SEE ALL EQUIPMENT SHALL BE LISTED |
| | FOR USE.90.7, 110.3 |
| | |
| | 4) NOTE: PLEASE INDICATE THE OCP AT THE |
| | GEN. PLEASE SEE 445.13 AS IT HAS COME TO |
| | OUR ATTENTION ON A PREVIOUS PROJECT THAT |
| | THE GEN MAY NOT CONTAIN OCP AND CAN NOT |
| | BE VERIFIED AT THIS TIME. |
| | |
| | 5) NOTE: PLEASE SEE NO LOAD CALCULATIONS |
| | WERE SUBMITTED FOR REVIEW. PLEASE |
| | SUBMIT. |
| | PLEASE SUBMIT AND INDICATE ANY LOAD |
| | SHEDDING DETAILS IF APPLICABLE. |
| | 702.5, 220 |
| | |
| | 6) NOTE: PLEASE PROVIDE INFORMATION IF |
| | THE GEN WILL BE FEEDING ANY "LEGALLY |
| | REQUIRED STAND-BY SYSTEMS. |
| | |
| | |
| | 7) NOTE:PLEASE SEE PLANS SHALL |
| | INDICATE THE CURRENT CODES IN EFFECT FOR |
| | INSTALLATION AS FOLLOWS. |
| | PLEASE SEE FBC 2004 CHAPTER 27FOR |
| | ADOPTED CODES RELEVANT TO POWER |
| | GENERATORS. |
| | 2002 NFPA-70, 2002 NFPA-110. |
| | |
| | 8) NOTE: PLEASE EXPLAIN, NOTE WHICH |
| | MENTIONS TO SET THE OCP ABOVE THE |
| | EXISTING MAIN ON E-1.??? |
| | |
| | 9) NOTE: PLEASE SEE THE APS/ATS IS |
| | BECOMING THE NEW FIRST MEANS OF |
| | DISCONNECT HOWEVER THE NEW GROUNDING |
| | ELECTRODE SYSTEMS DOES NOT SEEM TO BE |
| | COMPLETE AS PER 250.50. |
| | PLEASE SEE GROUNDING DETAIL MENTIONS NEW |
| | SLAB STEEL WHICH IS OK, HOWEVER PLEASE |
| | INDICATE ATTACHMENT. |
| | THESE NEW SLAB/STEEL ATTACHMENTS DO NOT |
| | MEET THE MIN REQUIREMENTS. PER |
| | 250.50,250.52, 250.104 |
| | IF SLAB STEEL IS ONLY BEING BONDED , |
| | THEN PLEASE INDICATE. |
| | PLEASE COMPLETE GROUNDING ELECTRODE |
| | SYSTEM(S) AND BONDING FOR ALL AS ABOVE. |
| | |
| | 10) NOTE: PLEASE INDICATE THE ACTUAL |
| | SEPARATION OF ALL NEUTRAL AND |
| | "GROUNDING" CONDUCTORS FROM THE FIRST |
| | MEANS OF DISCONNECT. 250.6, 250.24B |
| | DETAIL SHOWS THESE TO REMAIN TOGETHER |
| | WHICH WOULD PARALLEL THE NEUTRAL WHICH |
| | IS NOT PERMITTED. |
| | |
| | 11) NOTE: PLEASE SEE SETS OF CONDUITS |
| | AND FEEDERS DO NOT SEEM TO INDICATE |
| | THEW NEW REQUIRED "EQUIPMENT GROUNDING |
| | CONDUCTOR" TO THE EXISITING MAINS. THESE |
| | ARE NO LONGER THE FIRST MEANS OF |
| | DISCONNECT. |
| | PER 250.110,250.122,250.24B |
| | 215.5 |
| | |
| | 12) NOTE: |
| | |
| | 13) NOTE:PLEASE KNOW, BASED ON A |
| | PREVIOUS PROJECT, IS THIS UNIT GOING TO |
| | BE BE "BI-FUEL"?? |
| | IF SO, SUBMIT ALL INFORMATION AND SPECS |
| | ON UNIT(S). |
| | 90.7, 110.3 |
| | |
| | |
| | ** PLEASE KNOW, AS MUCH INFORMATION WAS |
| | NOT SUBMITTED, A COMPLETE REVIEW COULD |
| | NOT BE DONE. |
| | |
| | ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |