Plan Review Notes
Plan Review Notes For Permit 06090625
Permit Number 06090625
Review Stop E
Sequence Number 4
Notes
Date Text
2007-08-20 17:44:04 
 *** DENIED 4TH REVIEW ***
  
  
 1) NOTE: PLEASE SEE THE ENERGY CALCULATIONS NOW
 SUBMITTED IS UNDER THE CORRECT VERSION.
 PLEASE SEE SOME INPUT INFORMATION ON THE INPUT DATA
 REPORT STILL DOES NOT CORRELATE WITH PLANS.
 PLEASE SEE THE METHOD OF CONTROL NOW HAS BEEN REVISED
 TO INDICATE *MANUAL ON/OFF* INSTEAD OF THE AUTOMATE
 TYPE CONTROLS WHICH WERE OK AND CORRECT ON PREVIOUS
 SUBMITTED ENERGY CALCULATIONS.
 PLEASE SEE THE INPUT OF TYPES OF FIXTURES INCLUDING
 TRACK LIGHTING IS NOT CORRECT AND DOES NOT MATCH WITH
 THE PLANS, FIXTURE LEGEND AND WITH THE MINIMUM REQUIRED
 UNDER THE FBC. PLEASE SEE THE NOTES BELOW THE FIXTURE
 LEGEND FOR TYPE OF LUMINARIES.
 PLEASE SEE THE METHOD HAS NOW BEEN CHANGED TO METHOD
 A, AND TYPE IS LISTED AS CONVENTION CENTER. METHOD A IS
 OK, HOWEVER CLARIFY THE TYPE OF BUILDING AS ENTERED.
 13-415.1.A, 13-415.2.ABC.1.2.
 THE NOTE AT THE BOTTOM OF THE FIXTURE LEGEND STATES
 TRACK LIGHTING IS IN COMPLIANCE WITH 13-415.2.B.2, HOW
 IS THIS POSSIBLE WHEN THE METHOD HAS NOW CHANGED TO
 METHOD A?
  
 PLEASE REVISE, COORDINATE PLANS WITH THE ENERGY
 CALCULATIONS.
  
 2) NOTE: PLEASE SEE THE 2ND SET OF PLANS IS NOT
 COMPLETE. SET IS MISSING THE FOLLOWING SHEETS
 E,2,3,4,5,7,8,9 AND 10.
 THE PREVIOUS PLANS WHICH WERE SUBMITTED AND REVIEW DID
 HAVE ONE SET OF ELECTRICAL SHEETS REMOVED FROM SETS BY
 THIS REVIEWER HAVE BEEN RETAINED BY THIS AUTHORITY
 HAVING JURISDICTION. PLANS SUBMITTED FOR PUBLIC RECORD
 MAY BE RETAINED BY THIS OFFICE. PLANS ARE RETAINED
 SOLELY FOR THE USE OF THIS OFFICE WHEN SUBMITTED TO THE
 STATE OF FLORIDA BOARD OF ENGINEERS. THE STATE BOARD OF
 ENGINEERS REQUIRES PLANS TO BE SUBMITTED WHEN FILING TO
 THE BOARD. PLEASE CONTACT THE FLORIDA BOARD OF
 ENGINEERS OR THE FLORIDA BOARD OF ARCHITECTS AS THESE
 RULES ARE SET-FORTH BY THE STATE.
 THE PLANS PREVIOUSLY RETAINED ALONG WITH ENERGY
 CALCULATIONS MAY BE FORWARDED TO THE STATE BOARD OF
 ENGINEERS FOR REVIEW.
 THIS IS THE FORTH REVIEW OF SAID PROJECT AND CODE
 COMPLIANCE HAS NOT BEEN MET.
 THIS REVIEWER HAS PREVIOUSLY SPOKEN TO THE ENGINEER OF
 RECORD ON TWO OCCASIONS AND INFORMED THE DESIGNER OF
 THIS. THIS REVIEWER HAS ALSO INFORMED THE ENGINEER OF
 RETAINED PLANS FOR THIS REVIEW ALSO.
 PLEASE SEE FS 471.025
 THIS REVIEWER HAS CONTACTED THE ENGINEER OF RECORD BY
 PHONE AT 4:30PM AT THE DATE OF THIS REVIEW AND GONE
 OVER THE ITEMS AND INCONSISTENCIES OF PLANS AND ENERGY
 CALCULATIONS.
 THE ENGINEER OF RECORD HAS REQUESTED A MEETING FOR
 8/22/07 AT 9:30AM. THIS IS A TENTATIVE TIME WHICH MAY
 BE MOVED.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]