Plan Review Notes
Plan Review Notes For Permit 06090625
Permit Number 06090625
Review Stop E
Sequence Number 3
Notes
Date Text
2007-06-23 17:34:51*** UNSAT 3RD REVIEW ***
  
  
 1) NOTE:PLEASE SEE THE PHOTO-METRICS PREVIOUSLY
 REQUESTED FOR STAIRS UNDER NORMAL AND EMERGENCY LEVELS
 COULD NOT BE LOCATED ON PLANS. PLEASE SUPPLY. **PLEASE
 SEE CONDITIONS WHICH MAY BE GIVEN FOR THIS AT THE END
 OF REVIEW NOTES.
 LS 101 7.8.1.3, 7.9.2.2
  
 2) NOTE: PLEASE SEE THE PERMIT WAS APPLIED UNDER THE
 2004 FBC W/ 2006 REVISIONS. PLEASE SEE THE ENERGY
 CALCULATIONS SUBMITTED HAVE AN EFFECTIVE DATE OF
 DECEMBER 8TH, 2006 WHICH IS WHEN THE CODE CHANGED.
 PLEASE SEE THE VERSION IS NOT 3.0.
 PLEASE SEE THE ENERGY CALCULATIONS ARE NOT SIGNED,
 DATED AND SEALED BY THE ENGINEER OF RECORD AS REQUIRED
 PER 13-103.1.1.1.
 PLEASE SEE THE OWNER AGENT IS NOT SIGNED ON SHEET 2 AS
 NEEDED.
 PLEASE SEE THE ENERGY CALCULATIONS INPUT DATA REPORT,
 THE LIGHTING ENTERED FOR THE TOTAL NUMBER OF FIXTURES
 AND WATTAGE ON FIXTURES DOES NOT CORRELATE WITH PLANS.
 PLEASE SEE THERE ARE WATTAGES ON PLANS WHICH ARE NOT
 SHOWN ON ENERGY CALCULATIONS. PLEASE COORDINATE THE
 PLANS AND CALCULATIONS AS THERE ARE SEVERAL WHICH DOE
 NOT MATCH.( PLEASE SEE POSSIBLE MISPRINT FOR FIXTURES
 LISTED AT 252WATTS)?
 PLEASE SEE THE EXTERIOR LIGHTING ON PLANS DOES NOT
 CORRELATE WITH THE INPUT DATE REPORT OR SUMMARY
 SHEETS.
 PLEASE PROVIDE WHERE THE TRACK LIGHTING PER
 13-415.2.ABC.2 IS SHOWN ON ENERGY CALCULATIONS. THE
 AMOUNT FOR TRACK LIGHTING SHALL BE BASED ON THE TOTAL
 OF THE TRACK FIXTURES AT THE WATTAGE PER HEAD OR THE
 30VA PER FT AS LISTED IN THE ENERGY CODE WHICH EVER IS
 GREATER.
 13-415.1.AB.1.1, 13-415.2
  
 3) NOTE: PLEASE SEE THE MINIMUM CD LEVELS FOR STROBES
 FOR ADA COULD NOT BE FOUND ON THE LEGEND OR PLANS. THIS
 CAN BE REDLINED ON PLANS FOR THE MINIMUM LEVEL OF 75CD
 AS THIS SHEET E-1 DOES NOT NEED TO BE REPLACED. THIS
 WAS DONE ON ONE SET.
 FBC 11-4.28.3(4)
  
 ** NOTICE**
 **PLEASE ADDRESS NOTES ONE AND TWO:NOTE #3 CAN BE
 REDLINED ON PLANS.
 ** PLEASE KNOW THAT THE LEVELS FOR THE STAIRS MAY NOT
 BE READILY AVAILABLE AS THE SPIRAL STAIRS MAY TAKE SOME
 TIME/EFFORT TO DETERMINE AND THE PERMIT CAN BE ISSUED
 WITH A *PROVISO* TO PROVIDE THE INFORMATION FOR STAIRS
 WITHIN A GIVEN TIME FRAME.
 PLEASE KNOW THE INFORMATION ON NOTE #2 DOES NEED TO BE
 CORRECTED AT THIS TIME.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  