2007-03-20 12:50:29PLANNING AND ZONING DEPARTMENT
  
 ***FAILED***
  
 1. PROVIDE RESPONSE TO COMMENTS IN WRITING.
  
 2. ALL ARCHITECTURAL DRAWINGS SHALL REFLECT THE EXACT
 LOCATION OF THE WEST PROPERTY LINE.ACCORDING TO THE
 SURVEY AND SITE PLAN, THE WEST PROPERTY LINE RUNS EAST
 OF THE SIDEWALK ALONG SPRUCE AVENUE; HOWEVER, THE
 ARCHITECTURAL DRAWINGS SHOW THE PROPERTY LINE WEST OF
 THE SIDEWALK ALONG SPRUCE AVENUE.
  
 3. ACCORDING TO THE SITE PLAN AND ARCHITECTURAL
 DRAWINGS, ONLY THE PROPOSED COFFEE SHOP IS NOT PART OF
 THIS PERMIT APPLICATION.HOWEVER, ALL ENGINEERING
 PLANS (PLUMBING, MECHANICAL, AND ELECTRICAL), SHOW THAT
 THE ENTIRE WEST PORTION OF THE SITE IS NOT PART OF THIS
 PERMIT APPLICATION.FURTHERMORE, THE SITE PLAN,
 ARCHITECTURAL DRAWINGS AND SOME OF THE ENGINEERING
 PLANS SHOW THE JANITOR CLOSET/VENDING MACHINE AREA AS
 PART OF THIS PERMIT APPLICATION, BUT OTHER ENGINEERING
 PLANS STATE THAT IT IS NOT PART OF THIS CONTRACT.ALL
 PLANS AND DRAWINGS SHALL REFLECT THE SAME CONDITIONS.
 PLEASE CLARIFY WHAT IS AND WHAT IS NOT INCLUDED IN THIS
 PERMIT APPLICATION.
 A. PLEASE NOTE THAT IF ONLY THE PROPOSED COFFEE SHOP IS
 TO BE EXCLUDED, A SITE PLAN AND LANDSCAPE PLAN SHALL BE
 PROVIDED FOR THE WEST PORTION OF THE SITE.
 B. PLEASE NOTE THAT PER SECTION 94-210(D)(11),
 AUTOMATIC FOOD AND DRINK MACHINES MUST BE LOCATED
 INSIDE BUILDINGS.IF THE VENDING MACHINE AREA WILL BE
 ENCLOSED, THE AREA SHALL BE TWO STORIES PER NMUD
 REGULATIONS.
 C. PROPOSED JANITOR CLOSET SHALL BE TWO STORIES.
  
 4. LANDSCAPE PLANS, PREPARED BY A LANDSCAPE
 ARCHITECT AND AUTHORIZED BY F.S. CH. 481, PT. II, SHALL
 BE PROVIDED.
  
 5. FDOT APPROVAL FOR THE PROPOSED METAL AWNINGS ON THE
 WINDOWS SHALL BE PROVIDED.
  
 6. ACCESSIBLE ROUTES FOR HANDICAP PARKING SPACES SHALL
 BE NO LESS THAN 44 INCHES WIDE.
  
 7. PROVIDE HANDICAP PARKING STALL DETAIL.
 A. PARKING ACCESS AISLES FOR HANDICAP PARKING SPACES
 MUST BE NO LESS THAN 5 FEET WIDE.
 B. HANDICAP PARKING SPACES MUST BE PROMINENTLY OUTLINED
 IN BLUE PAINT.
 C. HANDICAP SYMBOL MUST BE FACING RIGHT (OPPOSITE
 DIRECTION)
 D. HANDICAP SYMBOL SHALL BE 3 FEET OR 5 FEET HIGH AND
 WHITE IN COLOR.
 E. HANDICAP SYMBOL SHALL BE 2 FEET FROM THE OPEN END OF
 THE PARKING SPACE.
  
 8. PER THE FINAL ORDER DATED FEBRUARY 1, 2007, THE TWO
 NEW WINDOWS SHALL 2 FEET ABOVE THE GROUND.ACCORDING
 TO THE ELEVATIONS SUBMITTED, THE WINDOWS ARE 2 FEET 6
 INCHES ABOVE THE GROUND.THESE WINDOWS SHALL BE
 RECONFIGURED TO MEET THIS CONDITION OF THE FINAL
 ORDER.
  
 9. EXTERIOR FINISH MATERIAL OF THE PROPOSED TICKET
 BOOTH SHALL BE PROVIDED.PLEASE NOTE THAT PER SECTION
 94-213(D)(1), WALLS SHALL BE NO MORE THAN TWO MATERIALS
 AND SHALL CHANGE MATERIAL ALONG A HORIZONTAL LINE, WITH
 THE HEAVIER MATERIAL BELOW THE LIGHTER MATERIAL.
  
 10. TOTAL CLEAR GLAZED AND OPENINGS PERCENTAGE SHALL BE
 PROVIDED FOR THE SECOND STORY.PLEASE NOTE THAT PER
 SECTION 94-213(D)(6), STORIES ABOVE THE FIRST FLOOR
 SHALL HAVE CLEAR GLAZED ARE AND OPENINGS BETWEEN 25
 PERCENT AND 45 PERCENT OF THE FACADE AREA.
  
 11. PER SECTION 94-213(D)(7), WINDOWS SHALL BE RECESSED
 A MINIMUM OF TWO INCHES FROM THE EXTERIOR FACE OF THE
 FACADE.
  
 12. PER SECTION 94-213(D)(13), ALL WINDOWS, EXCEPT
 STOREFRONT WINDOWS, SHALL BE OPERABLE.
  
 13. PLEASE NOTE THAT A SIGN PERMIT SHALL BE SUBMITTED
 FOR ALL NEW SIGNS.
  
 COMMENTS/QUESTIONS, CONTACT ANDREINA DAVILA Q. OR ERIC
 SCHNEIDER, PRINCIPAL PLANNER, AT 822-1435.