| Plan Review Notes For Permit 06090625 |
| Permit Number |
06090625 |
|
| Review Stop |
FIRE |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2007-04-17 18:10:28 | *****UNSAT***** | | | | | | THE FOLLOWING COMMENTS TAKEN FROM THE PREVIOUS FIRE | | | PLAN REVIEW STILL NEED TO BE ADDRESSED: | | | | | | | | | 07.ON PAGE E3, NOTE INDICATES THAT NOT ALL FIRE ALARM | | | EQUIPMENT IS SHOWN.PLEASE VERIFY THAT THE ADDED FIRE | | | ALARM DEVICES (AS PER REVISED SHEET E-3) COMPLY WITH | | | NFPA 72 (2002 EDITION) | | | | | | 13.ENSURE THAT THE BUILDING ADDRESS IS PROVIDED ON | | | THE BUILDING.ON SHEET A-3, DISPLAY/SHOW THE ACTUAL | | | ADDRESS NUMBERS ON THE APPROPIATE EXTERIOR ELEVATION | | | WHICH FRONTS 24TH STREET | | | | | | 19.THE EXISTING ELECTRICAL ROOM DOOR MUST BE RATED | | | SINCE IT WILL BE LOCATED WITHIN A TWO HOUR RATED WALL. | | | BETTER CLARIFY HOW/WHERE THIS HAS BEEN ADDRESSED | | | | | | 20.COULD NOT LOCATE ANY PORTABLE FIRE EXTINGUISHERS | | | ON THE LIFE SAFETY PLAN.SHOW/INDICATE THE LOCATION OF | | | THE 2A10BC RATED FIRE EXTINGUISHERS SATISFYING THE 75' | | | TRAVEL DISTANCE | | | | | | | | | PLEASE BE ADVISED THAT POSITIVE RESPONSES TO ALL OTHER | | | PLAN REVIEW COMMENTS WILL FURTHER ASSIST THE FIRE | | | PORTION OF THE PLAN REVIEW PROCESS | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|