| 2007-03-24 10:33:23 | |
| | ****** UNSAT 2ND REVIEW****** |
| | |
| | ** PLEASE KNOW THAT AS SOME INFORMATION HAS NOT YET |
| | BEEN SUBMITTED FOR REVIEW YET THERE MAY VERY WELL BE |
| | NEW COMMENTS ON THE NEXT REVIEW. |
| | ** PLEASE SEE THAT THERE ARE COMMENTS WHICH STILL NEED |
| | TO BE ADDRESSED FROM PREVIOUS REVIEW AND THERE ARE |
| | *NEW* COMMENTS BASED ON *CHANGES* MADE TO PLANS WHICH |
| | WERE *NOT* ON PREVIOUS ELECTRICAL PLANS. |
| | |
| | ** PLEASE KNOW THAT ANY REFERENCE TO THE FBC CHAPTER 1 |
| | IN THE PLAN REVIEW COMMENTS CAN BE FOUND IN THE |
| | ADMINISTRATIVE SECTION OF THE 2004 FBC AS ADOPTED BY |
| | THE CITY OF WEST PALM BEACH. |
| | |
| | |
| | |
| | 1) NOTE:PLEASE CORRELATE ALL CODES AS STATED AND |
| | SHOWN ON PLANS INCLUDING ARCHITECTURAL SHEETS AND |
| | ELECTRICAL SHEETS. |
| | PLEASE SEE THE CORRECT NEC/ NFPA-70 IS SHOWN ON THE |
| | ARCHITECTURAL SHEETS, HOWEVER THE ELECTRICAL SHEETS |
| | SHOWS THE 2005 NEC. |
| | PLEASE ALSO SEE THE ARCHITECTURAL SHEETS MENTIONS THE |
| | 2006 REVISIONS TO THE 2004 FBC WHICH SHOULD NOT. |
| | PLEASE KNOW THAT THIS PROJECT WAS SUBMITTED BEFORE THE |
| | CODE CHANGES OF DECEMBER 8TH, 2006.THIS PLACES THE |
| | PERMIT UNDER THE PREVIOUS CODES. |
| | PLEASE SEE THAT THE FOLLOWING CODES ARE TO BE SHOWN AND |
| | COORDINATED ON BOTH THE ARCHITECTURAL AND ELECTRICAL |
| | SHEETS. |
| | 2004 FBC ( NOT W/ THE 2006 REVISIONS) |
| | 2002 NFPA-70 |
| | 2003 NFPA-101(ALREADY ON ELECTRICAL) |
| | 2002 NFPA-72 (ALREADY ON ELECTRICAL). |
| | |
| | 2) NOTE: PLEASE SEE THAT SOME HORN AND STROBE DEVICES |
| | WERE ADDED TO PLANS; HOWEVER THEY DO NOT MEET THE CODE |
| | SECTIONS AS PREVIOUSLY MENTIONED FOR ADA COMPLIANCE. |
| | THESE SHALL BE SHOWN AT THIS TIME MEETING ALL LOCATIONS |
| | PER 11-4.28.1. |
| | PLEASE SEE THAT ALL MINIMUM LEVELS ARE TO BE STATED AND |
| | SHOWN AT THIS TIME. |
| | ONLY SOME DEVICES WERE ADDED IN SOME LOCATIONS. |
| | PLEASE SEE FBC 2004 11-4.28,.1, .2, AND .3(4). |
| | |
| | 3) NOTE: PLEASE SEE THAT COMPLIANCE WITH FBC CHAPTER 13 |
| | HAS NOT BEEN MET.THIS WAS FEDERALLY MANDATED AND WAS |
| | ADOPTED INTO THE FBC ON OCT. 1ST , 2005 AND IS |
| | REQUIRED. |
| | THE SINGLE DETAIL ON E-10 DOES NOT SHOW CODE COMPLIANCE |
| | FOR REQUIRED SECTIONS. PLEASE SEE THAT NO ENERGY |
| | CALCULATIONS WERE SUBMITTED IN PACKAGE WHICH CORRELATES |
| | WITH THE SUBMITTED PLANS, NO PERFORMANCE CALCULATIONS |
| | ETC. |
| | NO FIXTURE SCHEDULE, NO LIGHTING CALCULATIONS, NO |
| | LIGHTING CONTROLS IN ALL LOCATIONS AS REQUIRED ETC. |
| | PLEASE KNOW AS MANY ITEMS WERE NOT SUBMITTED, REVIEW |
| | FOR CODE COMPLIANCE CAN NOT BE DONE AT THIS TIME. |
| | PLEASE SEE 13-415.1.ABC.1.1, .1.2 AND .1.3 FOR |
| | AUTOMATED SYSTEM AND /OR DEVICES FOR CONTROL FOR ALL |
| | LIGHTING. PLEASE PROVIDE SCHEDULING (IF CHOOSING A |
| | SYSTEM OF SOME TYPE, TIMES ON OVER RIDE DEVICES ETC |
| | (MAX ALLOWED) WHICH DEPENDS ON WHAT TYPES OF OVER-RIDE |
| | AND OCCUPANCY SENSOR TYPE DEVICES ARE CHOSEN. PLEASE |
| | SEE THAT THE TYPE OF DEVICE CHOSEN WILL BE REQUIRED TO |
| | BE REVIEWED AS COVERAGE FOR AREAS FOR LIFE SAFETY OF |
| | EGRESS ETC WILL NEED TO BE DETERMINED. PLEASE INDICATE |
| | TYPES OF DEVICES. |
| | PLEASE PROVIDE CALCULATIONS PER 13-415.2. PLEASE SEE |
| | TABLES? 13-415.2.C.1, 415.2.B.1 |
| | PLEASE SEE 13-415.1.AB.1.1 AND THE REST OF CHAPTER 13 |
| | |
| | ** PLEASE KNOW THAT LIGHTING FOR FUTURE STAGE LIGHTING |
| | IS NOT BEING CONSIDERED IN THIS REVIEW. THE LIGHTING |
| | WHICH IS MENTIONED ON PANEL *F* IS NOT INCLUDED. |
| | |
| | 4) NOTE: PLEASE SEE THAT THE PREVIOUS NOTES REQUESTED |
| | PHOTO-METRICS FOR EGRESS PATHS BE SUBMITTED TO THE |
| | PUBLIC RIGHT OF WAY. THESE WERE NOT SUBMITTED TO BE |
| | REVIEWED FOR CODE COMPLIANCE. |
| | PLEASE SUBMIT LEVELS UNDER NORMAL AND EMERGENCY FOR ALL |
| | PATHS. PLEASE SEE ANY STAIRS AS THE LEVELS FOR STAIR |
| | AREAS ARE HIGHER THAN FLAT/HALL EGRESS PATHS. PLEASE |
| | SEE THIS INCLUDE STAIRS USED FOR EGRESS/INGRESS TO THE |
| | PUBLIC RIGHT OF WAY. ( 10FT CANDLES UNDER NORMAL AND |
| | PERMITTED DOWN TO 1FT CANDLE UNDER EMERGENCY). |
| | PLEASE SEE NEW STAIRS NOW ADDED WHICH WERE NOT ON |
| | PREVIOUS PLANS. SEE THE FOLLOWING NOTE. PLEASE PROVIDE |
| | MINIMUM PHOTO-METRICS FOR ALL EGRESS PATHS. |
| | PLEASE SEE THE REHEARSAL ROOM WHICH DOES NOT SHOW AN EM |
| | BATTERY BACK UP FIXTURE. PLEASE SEE NEXT COMMENT WITH |
| | RESPECT TO 2ND FLOOR AREA. PLEASE SEE NFPA-101 2003, |
| | 7.8, 7.9. |
| | ** REVIEW CAN NOT BE DONE AT THIS TIME. |
| | |
| | 5) NOTE: PLEASE SEE THE ELECTRICAL PLANS DO NOT INCLUDE |
| | ANY 2ND FLOOR AREAS. PLEASE SEE THE ELECTRICAL PLANS |
| | NOW INCLUDE NEW SPIRAL STAIRS TO THE SECOND FLOOR WHICH |
| | WAS NOT ON PREVIOUS PLANS FOR REVIEW. |
| | PLEASE PROVIDE MINIMUM LIGHTING FOR THIS LEVEL AND FOR |
| | STAIRS, CONTROLS TO MEET THE LIFE SAFETY CODE AND FBC |
| | CHAPTER 13. EM LTS, ETC. |
| | PLEASE SHOW. |
| | FBC 106.1.2 |
| | |
| | 6) NOTE: THE RESPONSE LETTER MENTIONS TRACK LIGHTING |
| | WAS FIGURED FOR THE REQUIREMENT OF 220.12 HOWEVER COULD |
| | NOT LOCATE THIS ON THE PLANS(RECORD SETS OF PLANS) OR |
| | IN THE LOAD CALCULATIONS. |
| | PLEASE INCLUDE. |
| | PLEASE SEE 220.12B FOR TRACK LIGHTING. |
| | FBC 106.3.5.1.2 ADMIN SECT. |
| | |
| | 7) NOTE: THIS COMMENT WILL REMAIN AS THERE ARE STILL |
| | SOME LIGHTING WHICH HAS NOT YET BEEN ADDED TO PLANS. |
| | PLEASE SEE THAT FROM THE PREVIOUS REVIEW IT SEEMS THIS |
| | WAS OK WITH THE NEW CIRCUITS/NL AS SHOWN. |
| | PLEASE SEE 700.12E FOR CIRCUITING OF ALL EM/EXT LTS. |
| | THE BRANCH CIRCUIT FEEDING THE UNIT EQUIPMENT SHALL BE |
| | THE SAME BRANCH CIRCUIT AS THAT SERVING THE NORMAL |
| | LIGHTING IN THE AREA AND CONNECTED AHEAD OF ANY LOCAL |
| | SWITCHES. |
| | |
| | 8) NOTE: PLEASE SEE AS SOME COMMENTS ARE THE SAME CODE |
| | COMPLIANCE COMMENTS FROM THE PREVIOUS REVIEWED PLANS |
| | PLEASE SEE FS 553.80(2)(B). |
| | ONE SET OF EACH OF THE PLANS ARE BEING RETAINED BY THIS |
| | OFFICE AT THIS TIME. |
| | |
| | ** SITE LIGHTING AND WORK FOR THE DETACHED BUILDING |
| | WHICH CONTAINS THE COFFEE SHOP HAS BEEN REMOVED FROM |
| | PLANS. THE SITE LIGHTING WILL BE UNDER SEPARATE PERMITS |
| | ETC. |
| | |
| | ** PLEASE SEE COMMENTS FROM OTHER TRADES WHICH MAY VERY |
| | WELL AFFECT THE ELECTRICAL PLANS. |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |