Plan Review Notes
Plan Review Notes For Permit 06090625
Permit Number 06090625
Review Stop E
Sequence Number 2
Notes
Date Text
2007-03-24 10:33:23 
 ****** UNSAT 2ND REVIEW******
  
 ** PLEASE KNOW THAT AS SOME INFORMATION HAS NOT YET
 BEEN SUBMITTED FOR REVIEW YET THERE MAY VERY WELL BE
 NEW COMMENTS ON THE NEXT REVIEW.
 ** PLEASE SEE THAT THERE ARE COMMENTS WHICH STILL NEED
 TO BE ADDRESSED FROM PREVIOUS REVIEW AND THERE ARE
 *NEW* COMMENTS BASED ON *CHANGES* MADE TO PLANS WHICH
 WERE *NOT* ON PREVIOUS ELECTRICAL PLANS.
  
 ** PLEASE KNOW THAT ANY REFERENCE TO THE FBC CHAPTER 1
 IN THE PLAN REVIEW COMMENTS CAN BE FOUND IN THE
 ADMINISTRATIVE SECTION OF THE 2004 FBC AS ADOPTED BY
 THE CITY OF WEST PALM BEACH.
  
  
  
 1) NOTE:PLEASE CORRELATE ALL CODES AS STATED AND
 SHOWN ON PLANS INCLUDING ARCHITECTURAL SHEETS AND
 ELECTRICAL SHEETS.
 PLEASE SEE THE CORRECT NEC/ NFPA-70 IS SHOWN ON THE
 ARCHITECTURAL SHEETS, HOWEVER THE ELECTRICAL SHEETS
 SHOWS THE 2005 NEC.
 PLEASE ALSO SEE THE ARCHITECTURAL SHEETS MENTIONS THE
 2006 REVISIONS TO THE 2004 FBC WHICH SHOULD NOT.
 PLEASE KNOW THAT THIS PROJECT WAS SUBMITTED BEFORE THE
 CODE CHANGES OF DECEMBER 8TH, 2006.THIS PLACES THE
 PERMIT UNDER THE PREVIOUS CODES.
 PLEASE SEE THAT THE FOLLOWING CODES ARE TO BE SHOWN AND
 COORDINATED ON BOTH THE ARCHITECTURAL AND ELECTRICAL
 SHEETS.
 2004 FBC ( NOT W/ THE 2006 REVISIONS)
 2002 NFPA-70
 2003 NFPA-101(ALREADY ON ELECTRICAL)
 2002 NFPA-72 (ALREADY ON ELECTRICAL).
  
 2) NOTE: PLEASE SEE THAT SOME HORN AND STROBE DEVICES
 WERE ADDED TO PLANS; HOWEVER THEY DO NOT MEET THE CODE
 SECTIONS AS PREVIOUSLY MENTIONED FOR ADA COMPLIANCE.
 THESE SHALL BE SHOWN AT THIS TIME MEETING ALL LOCATIONS
 PER 11-4.28.1.
 PLEASE SEE THAT ALL MINIMUM LEVELS ARE TO BE STATED AND
 SHOWN AT THIS TIME.
 ONLY SOME DEVICES WERE ADDED IN SOME LOCATIONS.
 PLEASE SEE FBC 2004 11-4.28,.1, .2, AND .3(4).
  
 3) NOTE: PLEASE SEE THAT COMPLIANCE WITH FBC CHAPTER 13
 HAS NOT BEEN MET.THIS WAS FEDERALLY MANDATED AND WAS
 ADOPTED INTO THE FBC ON OCT. 1ST , 2005 AND IS
 REQUIRED.
 THE SINGLE DETAIL ON E-10 DOES NOT SHOW CODE COMPLIANCE
 FOR REQUIRED SECTIONS. PLEASE SEE THAT NO ENERGY
 CALCULATIONS WERE SUBMITTED IN PACKAGE WHICH CORRELATES
 WITH THE SUBMITTED PLANS, NO PERFORMANCE CALCULATIONS
 ETC.
 NO FIXTURE SCHEDULE, NO LIGHTING CALCULATIONS, NO
 LIGHTING CONTROLS IN ALL LOCATIONS AS REQUIRED ETC.
 PLEASE KNOW AS MANY ITEMS WERE NOT SUBMITTED, REVIEW
 FOR CODE COMPLIANCE CAN NOT BE DONE AT THIS TIME.
 PLEASE SEE 13-415.1.ABC.1.1, .1.2 AND .1.3 FOR
 AUTOMATED SYSTEM AND /OR DEVICES FOR CONTROL FOR ALL
 LIGHTING. PLEASE PROVIDE SCHEDULING (IF CHOOSING A
 SYSTEM OF SOME TYPE, TIMES ON OVER RIDE DEVICES ETC
 (MAX ALLOWED) WHICH DEPENDS ON WHAT TYPES OF OVER-RIDE
 AND OCCUPANCY SENSOR TYPE DEVICES ARE CHOSEN. PLEASE
 SEE THAT THE TYPE OF DEVICE CHOSEN WILL BE REQUIRED TO
 BE REVIEWED AS COVERAGE FOR AREAS FOR LIFE SAFETY OF
 EGRESS ETC WILL NEED TO BE DETERMINED. PLEASE INDICATE
 TYPES OF DEVICES.
 PLEASE PROVIDE CALCULATIONS PER 13-415.2. PLEASE SEE
 TABLES? 13-415.2.C.1, 415.2.B.1
 PLEASE SEE 13-415.1.AB.1.1 AND THE REST OF CHAPTER 13
  
 ** PLEASE KNOW THAT LIGHTING FOR FUTURE STAGE LIGHTING
 IS NOT BEING CONSIDERED IN THIS REVIEW. THE LIGHTING
 WHICH IS MENTIONED ON PANEL *F* IS NOT INCLUDED.
  
 4) NOTE: PLEASE SEE THAT THE PREVIOUS NOTES REQUESTED
 PHOTO-METRICS FOR EGRESS PATHS BE SUBMITTED TO THE
 PUBLIC RIGHT OF WAY. THESE WERE NOT SUBMITTED TO BE
 REVIEWED FOR CODE COMPLIANCE.
 PLEASE SUBMIT LEVELS UNDER NORMAL AND EMERGENCY FOR ALL
 PATHS. PLEASE SEE ANY STAIRS AS THE LEVELS FOR STAIR
 AREAS ARE HIGHER THAN FLAT/HALL EGRESS PATHS. PLEASE
 SEE THIS INCLUDE STAIRS USED FOR EGRESS/INGRESS TO THE
 PUBLIC RIGHT OF WAY. ( 10FT CANDLES UNDER NORMAL AND
 PERMITTED DOWN TO 1FT CANDLE UNDER EMERGENCY).
 PLEASE SEE NEW STAIRS NOW ADDED WHICH WERE NOT ON
 PREVIOUS PLANS. SEE THE FOLLOWING NOTE. PLEASE PROVIDE
 MINIMUM PHOTO-METRICS FOR ALL EGRESS PATHS.
 PLEASE SEE THE REHEARSAL ROOM WHICH DOES NOT SHOW AN EM
 BATTERY BACK UP FIXTURE. PLEASE SEE NEXT COMMENT WITH
 RESPECT TO 2ND FLOOR AREA. PLEASE SEE NFPA-101 2003,
 7.8, 7.9.
 ** REVIEW CAN NOT BE DONE AT THIS TIME.
  
 5) NOTE: PLEASE SEE THE ELECTRICAL PLANS DO NOT INCLUDE
 ANY 2ND FLOOR AREAS. PLEASE SEE THE ELECTRICAL PLANS
 NOW INCLUDE NEW SPIRAL STAIRS TO THE SECOND FLOOR WHICH
 WAS NOT ON PREVIOUS PLANS FOR REVIEW.
 PLEASE PROVIDE MINIMUM LIGHTING FOR THIS LEVEL AND FOR
 STAIRS, CONTROLS TO MEET THE LIFE SAFETY CODE AND FBC
 CHAPTER 13. EM LTS, ETC.
 PLEASE SHOW.
 FBC 106.1.2
  
 6) NOTE: THE RESPONSE LETTER MENTIONS TRACK LIGHTING
 WAS FIGURED FOR THE REQUIREMENT OF 220.12 HOWEVER COULD
 NOT LOCATE THIS ON THE PLANS(RECORD SETS OF PLANS) OR
 IN THE LOAD CALCULATIONS.
 PLEASE INCLUDE.
 PLEASE SEE 220.12B FOR TRACK LIGHTING.
 FBC 106.3.5.1.2 ADMIN SECT.
  
 7) NOTE: THIS COMMENT WILL REMAIN AS THERE ARE STILL
 SOME LIGHTING WHICH HAS NOT YET BEEN ADDED TO PLANS.
 PLEASE SEE THAT FROM THE PREVIOUS REVIEW IT SEEMS THIS
 WAS OK WITH THE NEW CIRCUITS/NL AS SHOWN.
 PLEASE SEE 700.12E FOR CIRCUITING OF ALL EM/EXT LTS.
 THE BRANCH CIRCUIT FEEDING THE UNIT EQUIPMENT SHALL BE
 THE SAME BRANCH CIRCUIT AS THAT SERVING THE NORMAL
 LIGHTING IN THE AREA AND CONNECTED AHEAD OF ANY LOCAL
 SWITCHES.
  
 8) NOTE: PLEASE SEE AS SOME COMMENTS ARE THE SAME CODE
 COMPLIANCE COMMENTS FROM THE PREVIOUS REVIEWED PLANS
 PLEASE SEE FS 553.80(2)(B).
 ONE SET OF EACH OF THE PLANS ARE BEING RETAINED BY THIS
 OFFICE AT THIS TIME.
  
 ** SITE LIGHTING AND WORK FOR THE DETACHED BUILDING
 WHICH CONTAINS THE COFFEE SHOP HAS BEEN REMOVED FROM
 PLANS. THE SITE LIGHTING WILL BE UNDER SEPARATE PERMITS
 ETC.
  
 ** PLEASE SEE COMMENTS FROM OTHER TRADES WHICH MAY VERY
 WELL AFFECT THE ELECTRICAL PLANS.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]