2006-10-19 18:53:54DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FBC-2004 BUILDING
  
 1. SUBMIT CALCULATIONS FOR MINIMUM FACILITIES PER
 TABLES 1004.1.2 & 403.1.SHOW COMPLIANCE WITH POTTY
 PARITY PER SECTION 403.1.1. SHOW THE SQUARE FOOTAGE OF
 ALL OCCUPANCIES. (BUSINESS, ASSEMBLY, STORAGE ETC.).
  
 2. INDICATE OCCUPANCIES AND INDICATE CODE REFERENCES.
  
 3. FUTURE COFFEE SHOP & SERVICE FOOD PREP AREA. A
 GREASE INTERCEPTOR MAY BE REQUIRED. PLEASE CONTACT LYNN
 MASSON, ENVIRONMENTAL COMPLIANCE MANAGER FOR A
 DETERMINATION. CALL HER AT (561) 822-2271, OR FAX (561)
 822-2279, OR E-MAIL [email protected]. WASTE ORD. 3434.
  
 4. SHT A-1 WOMEN'S H/C BATHROOM. DOOR SHALL NOT SWING
 INTO THE REQUIRED CLEAR FLOOR SPACE FOR ANY FIXTURE.
 SECTION 11-4.22.2. (SEE LAV).
  
 5. SHT A-1 WOMEN'S H/C BATHROOM. SUBMIT A DETAIL FOR
 THE SHOWER SHOWING COMPLIANCE WITH SECTION 11-4.21 AND
 ALL SUBSECTIONS.
  
 6. SHT A-1 SHT A-1 SUBMIT DETAILS FOR MEN'S & WOMEN'S
 TOILET/BATHROOM SHOWING COMPLIANCE WITH SECTIONS
 11-4.16, & 11-4.19 WITH ALL SUBSECTIONS. (COMMENTS 4,
 5, 6 TOILET ROOMS ACROSS FROM ROOMS 128 & 137).
  
 7. SHT A-1 SUBMIT A DETAIL FOR THE LOUNGE ROOM, (132),
 SINK. SHOW COMPLIANCE WITH SECTION 11-4.24 AND ALL
 SUBSECTIONS.
  
 8. SHT A-1 MEN'S AND WOMEN'S TOILET ROOMS 3 & 4. MORE
 INFORMATION IS REQUIRED. ARE THESE SEPARATE TOILET
 ROOMS, OR TOILET STALLS WITHIN TOILET ROOMS 1 & 2? IF
 SEPARATE TOILET ROOMS, AT LEAST ONE STALL IN TOILET
 ROOMS 1 & 2 SHALL BE ACCESSIBLE AND COMPLY WITH FIG.
 30E.
  
 9. SHT A-10 DETAIL D4 BATHROOM FLOOR PLAN. SHOW THE
 TURNING AREA IN THE TOILET ROOMS. SECTION 11-4.22.3.
  
 10. SHT A-10 DETAIL E THE FLUSH CONTROL SHALL BE ON THE
 WIDE SIDE. SECTION 11-4.16.5.
  
 11. SHT A-10 DETAIL A SHOW THE FLUSH CONTROL HEIGHT.
 SECTION 11-4.18.4.
  
 12. SHT A-10 DETAILS C, D, & E. SHOW CLEARANCES PER
 SECTION 11-4.19.2, EXPOSED PIPES & SURFACES SECTION
 11-4.19.4, FAUCETS SECTION 11-4.19.5.
  
 13. SHT A-10 DETAIL C SHOWS MIRROR BOTTOM AT 42".PER
 SECTION 11-4.19.6 THE MIRRORS SHALL BE MAXIMUM 40" TO
 THE BOTTOM.EXPOSED PIPES AND SURFACES PER SECTION
 11-4.19.5, NOT 11-4.23.4 AS SHOWN. CORRECT CODE
 REFERENCE.
  
 14. SHT A-11 DETAIL I SHOW EXPOSED PIPES & SURFACES PER
 11-4.19.5, NOT 11-4.23.5 AS SHOWN. INDICATE COMPLIANCE
 WITH CLEARANCES PER 11-4.19.2, FAUCETS PER 11-4.19.5,
 AND MIRROR PER 11-4.19.6 TO BE 40" TO THE BOTTOM, NOT
 42" AS SHOWN.
  
 15. SHT A-11 DETAILS R, S, A'& B' SHOW COMPLIANCE
 WITH THE FOLLOWING FOR THE W/C'S, 11-4.16.2 CLEAR FLOOR
 SPACE, 11-4.16.5 FLUSH CONTROLS, (S & A'), 11-4.16.6
 DISPENSERS. INDICATE THE W/C'S TO BE 18" OFF THE WALL
 TO THE CENTER OF THE FIXTURE, (FIG 28). FOR THE LAVS
 SHOW CLEARANCES 11-4.19.2, CLEAR FLOOR SPACE 11-4.19.3,
 EXPOSED PIPES & SURFACES 11-4.19.4, FAUCETS 11-4.19.5,
 AND MIRRORS 11-4.19.6. SHOW THE LAVS AS 15" MINIMUM OFF
 THE WALL TO THE CENTER OF THE FIXTURE TO BE CENTERED ON
 THE 30" CLEAR FLOOR SPACE.
  
 16. SUBMIT A DETAIL FOR THE DRINKING FOUNTAIN SHOWING
 COMPLIANCE WITH SECTION 11-4.15 AND ALL SUBSECTIONS.
  
 17. SHTS A-1 & P-1. SHT A-1 INDICATES THE WOMEN'S
 BATHROOM, THE MEN'S TOILET ROOM, AND THE LOUNGE AS
 EXISTING. SHT P-1 INDICATES NEW SANITARY PIPING FOR
 THESE FIXTURES. PLEASE CLARIFY. SECTION 106.1.1.
  
 18. SHTS P-1 & P-2 KEY NOTES 3 & 4 INDICATE THE P/T
 DISCHARGE LINE TO BE RUN UNDER THE SLAB. PER SECTION
 504.6.1 THERE ARE TO BE NO TRAPPED SECTIONS IN THE P/T
 DISCHARGE LINE. ALSO AN AIR GAP OR AIR GAP FITTING IS
 REQUIRED IN THE ROOM OF THE HEATER.
  
 19. SHT P-1 CONDENSATE SHALL DISCHARGE A MINIMUM OF 1'
 AWAY FROM THE STRUCTURE SIDEWALL OF THE BUILDING.
 SECTION 1503.6
  
 20. SHT P-3 SANITARY RISER DIAGRAM FOR NEW TOILET
 CONNECTING TO EXISTING BUILDING DRAIN. THE W/C IN THE
 WOMEN'S BATHROOM SHALL BE WET VENTED WITH THE SHOWER
 LAV, AND NOT VENTED BY THE W/M. SECTION 909.1 (SEE RED
 LINE CORRECTIONS ON ONE SET OF PLANS FOR EXAMPLE).
  
 21. SHT P-3 NOTE #2 PER TABLE 704.1, 2-1/2" AND SMALLER
 PIPE SHALL BE SLOPED AT 1/4"/FT. UPDATE REFERENCE.
  
 22. SHT P-4 DOMESTIC WATER RISER DIAGRAM. WATER HEATERS
 SHALL INDICATE THERMAL EXPANSION CONTROL PER SECTION
 607.3.2. NO TRAPPED SECTIONS IN P/T LINE. (SEE COMMENT
 #18). FULL OPEN VALVES REQUIRED ON ALL DOWN-FEED WATER
 LINES.SECTION 606.1(4). (TWO SETS MISSING VALVES).
  
 23. AN RPZV BACKFLOW IS REQUIRED ON THE WATER SERVICE
 OF THE BUILDING. IF THERE IS ONE EXISTING, PLEASE
 INDICATE ON WATER RISER DIAGRAM. SECTIONS 106.1.1.&
 608.13.2.
  
 24. INFORMATIONAL: FUTURE SERVICE FOOD PREP SHALL BE
 REVIEWED BY THE PALM BEACH COUNTY HEALTH UNIT, DIVISION
 ON ENVIRONMENTAL HEALTH. 901 EVERNIA ST WPB. (561)
 355-3018 PRIOR TO SUBMITTING PLANS FOR BUILD-OUT.
 SECTION 102.2.1.
  
 REVIEW BY KEN STEVENS