| 2006-10-19 18:53:54 | DENIED |
| | REFERENCE: FBC-2004 PLUMBING |
| | FBC-2004 CHAPTER 1 |
| | FBC-2004 CHAPTER 11 |
| | FBC-2004 BUILDING |
| | |
| | 1. SUBMIT CALCULATIONS FOR MINIMUM FACILITIES PER |
| | TABLES 1004.1.2 & 403.1.SHOW COMPLIANCE WITH POTTY |
| | PARITY PER SECTION 403.1.1. SHOW THE SQUARE FOOTAGE OF |
| | ALL OCCUPANCIES. (BUSINESS, ASSEMBLY, STORAGE ETC.). |
| | |
| | 2. INDICATE OCCUPANCIES AND INDICATE CODE REFERENCES. |
| | |
| | 3. FUTURE COFFEE SHOP & SERVICE FOOD PREP AREA. A |
| | GREASE INTERCEPTOR MAY BE REQUIRED. PLEASE CONTACT LYNN |
| | MASSON, ENVIRONMENTAL COMPLIANCE MANAGER FOR A |
| | DETERMINATION. CALL HER AT (561) 822-2271, OR FAX (561) |
| | 822-2279, OR E-MAIL [email protected]. WASTE ORD. 3434. |
| | |
| | 4. SHT A-1 WOMEN'S H/C BATHROOM. DOOR SHALL NOT SWING |
| | INTO THE REQUIRED CLEAR FLOOR SPACE FOR ANY FIXTURE. |
| | SECTION 11-4.22.2. (SEE LAV). |
| | |
| | 5. SHT A-1 WOMEN'S H/C BATHROOM. SUBMIT A DETAIL FOR |
| | THE SHOWER SHOWING COMPLIANCE WITH SECTION 11-4.21 AND |
| | ALL SUBSECTIONS. |
| | |
| | 6. SHT A-1 SHT A-1 SUBMIT DETAILS FOR MEN'S & WOMEN'S |
| | TOILET/BATHROOM SHOWING COMPLIANCE WITH SECTIONS |
| | 11-4.16, & 11-4.19 WITH ALL SUBSECTIONS. (COMMENTS 4, |
| | 5, 6 TOILET ROOMS ACROSS FROM ROOMS 128 & 137). |
| | |
| | 7. SHT A-1 SUBMIT A DETAIL FOR THE LOUNGE ROOM, (132), |
| | SINK. SHOW COMPLIANCE WITH SECTION 11-4.24 AND ALL |
| | SUBSECTIONS. |
| | |
| | 8. SHT A-1 MEN'S AND WOMEN'S TOILET ROOMS 3 & 4. MORE |
| | INFORMATION IS REQUIRED. ARE THESE SEPARATE TOILET |
| | ROOMS, OR TOILET STALLS WITHIN TOILET ROOMS 1 & 2? IF |
| | SEPARATE TOILET ROOMS, AT LEAST ONE STALL IN TOILET |
| | ROOMS 1 & 2 SHALL BE ACCESSIBLE AND COMPLY WITH FIG. |
| | 30E. |
| | |
| | 9. SHT A-10 DETAIL D4 BATHROOM FLOOR PLAN. SHOW THE |
| | TURNING AREA IN THE TOILET ROOMS. SECTION 11-4.22.3. |
| | |
| | 10. SHT A-10 DETAIL E THE FLUSH CONTROL SHALL BE ON THE |
| | WIDE SIDE. SECTION 11-4.16.5. |
| | |
| | 11. SHT A-10 DETAIL A SHOW THE FLUSH CONTROL HEIGHT. |
| | SECTION 11-4.18.4. |
| | |
| | 12. SHT A-10 DETAILS C, D, & E. SHOW CLEARANCES PER |
| | SECTION 11-4.19.2, EXPOSED PIPES & SURFACES SECTION |
| | 11-4.19.4, FAUCETS SECTION 11-4.19.5. |
| | |
| | 13. SHT A-10 DETAIL C SHOWS MIRROR BOTTOM AT 42".PER |
| | SECTION 11-4.19.6 THE MIRRORS SHALL BE MAXIMUM 40" TO |
| | THE BOTTOM.EXPOSED PIPES AND SURFACES PER SECTION |
| | 11-4.19.5, NOT 11-4.23.4 AS SHOWN. CORRECT CODE |
| | REFERENCE. |
| | |
| | 14. SHT A-11 DETAIL I SHOW EXPOSED PIPES & SURFACES PER |
| | 11-4.19.5, NOT 11-4.23.5 AS SHOWN. INDICATE COMPLIANCE |
| | WITH CLEARANCES PER 11-4.19.2, FAUCETS PER 11-4.19.5, |
| | AND MIRROR PER 11-4.19.6 TO BE 40" TO THE BOTTOM, NOT |
| | 42" AS SHOWN. |
| | |
| | 15. SHT A-11 DETAILS R, S, A'& B' SHOW COMPLIANCE |
| | WITH THE FOLLOWING FOR THE W/C'S, 11-4.16.2 CLEAR FLOOR |
| | SPACE, 11-4.16.5 FLUSH CONTROLS, (S & A'), 11-4.16.6 |
| | DISPENSERS. INDICATE THE W/C'S TO BE 18" OFF THE WALL |
| | TO THE CENTER OF THE FIXTURE, (FIG 28). FOR THE LAVS |
| | SHOW CLEARANCES 11-4.19.2, CLEAR FLOOR SPACE 11-4.19.3, |
| | EXPOSED PIPES & SURFACES 11-4.19.4, FAUCETS 11-4.19.5, |
| | AND MIRRORS 11-4.19.6. SHOW THE LAVS AS 15" MINIMUM OFF |
| | THE WALL TO THE CENTER OF THE FIXTURE TO BE CENTERED ON |
| | THE 30" CLEAR FLOOR SPACE. |
| | |
| | 16. SUBMIT A DETAIL FOR THE DRINKING FOUNTAIN SHOWING |
| | COMPLIANCE WITH SECTION 11-4.15 AND ALL SUBSECTIONS. |
| | |
| | 17. SHTS A-1 & P-1. SHT A-1 INDICATES THE WOMEN'S |
| | BATHROOM, THE MEN'S TOILET ROOM, AND THE LOUNGE AS |
| | EXISTING. SHT P-1 INDICATES NEW SANITARY PIPING FOR |
| | THESE FIXTURES. PLEASE CLARIFY. SECTION 106.1.1. |
| | |
| | 18. SHTS P-1 & P-2 KEY NOTES 3 & 4 INDICATE THE P/T |
| | DISCHARGE LINE TO BE RUN UNDER THE SLAB. PER SECTION |
| | 504.6.1 THERE ARE TO BE NO TRAPPED SECTIONS IN THE P/T |
| | DISCHARGE LINE. ALSO AN AIR GAP OR AIR GAP FITTING IS |
| | REQUIRED IN THE ROOM OF THE HEATER. |
| | |
| | 19. SHT P-1 CONDENSATE SHALL DISCHARGE A MINIMUM OF 1' |
| | AWAY FROM THE STRUCTURE SIDEWALL OF THE BUILDING. |
| | SECTION 1503.6 |
| | |
| | 20. SHT P-3 SANITARY RISER DIAGRAM FOR NEW TOILET |
| | CONNECTING TO EXISTING BUILDING DRAIN. THE W/C IN THE |
| | WOMEN'S BATHROOM SHALL BE WET VENTED WITH THE SHOWER |
| | LAV, AND NOT VENTED BY THE W/M. SECTION 909.1 (SEE RED |
| | LINE CORRECTIONS ON ONE SET OF PLANS FOR EXAMPLE). |
| | |
| | 21. SHT P-3 NOTE #2 PER TABLE 704.1, 2-1/2" AND SMALLER |
| | PIPE SHALL BE SLOPED AT 1/4"/FT. UPDATE REFERENCE. |
| | |
| | 22. SHT P-4 DOMESTIC WATER RISER DIAGRAM. WATER HEATERS |
| | SHALL INDICATE THERMAL EXPANSION CONTROL PER SECTION |
| | 607.3.2. NO TRAPPED SECTIONS IN P/T LINE. (SEE COMMENT |
| | #18). FULL OPEN VALVES REQUIRED ON ALL DOWN-FEED WATER |
| | LINES.SECTION 606.1(4). (TWO SETS MISSING VALVES). |
| | |
| | 23. AN RPZV BACKFLOW IS REQUIRED ON THE WATER SERVICE |
| | OF THE BUILDING. IF THERE IS ONE EXISTING, PLEASE |
| | INDICATE ON WATER RISER DIAGRAM. SECTIONS 106.1.1.& |
| | 608.13.2. |
| | |
| | 24. INFORMATIONAL: FUTURE SERVICE FOOD PREP SHALL BE |
| | REVIEWED BY THE PALM BEACH COUNTY HEALTH UNIT, DIVISION |
| | ON ENVIRONMENTAL HEALTH. 901 EVERNIA ST WPB. (561) |
| | 355-3018 PRIOR TO SUBMITTING PLANS FOR BUILD-OUT. |
| | SECTION 102.2.1. |
| | |
| | REVIEW BY KEN STEVENS |