Plan Review Notes
Plan Review Notes For Permit 06090625
Permit Number 06090625
Review Stop M
Sequence Number 1
Notes
Date Text
2006-10-13 19:09:291)IN REGARDS TO NOTE #4 PAGE M-4 PLEASE REFER TO
 SECTION 603.1.7 APPROVED CLOSURE SYSTEMS.THIS SECTION
 INCLUDES FIBERGLASS DUCT .
 2)PAGE M-4 ON THE CONDENSOR MOUNTING DETAIL , PLEASE
 PROVIDE THE GAGE OF 1 IN.STEAP ON THE PLANS.
 3)PLEASE PROVIDE ANCHOR DETAIL ON A/C STAND TO ROOF
 ON PLANS.
 4)PAGE M-1 PLEASE PROVIDE DUCT SIZE ON OUTDOOR AIR
 DUCT ON PLANS.
 5)PLEASE REFER TO SECTION 501.4 FOR EXHAUST DUCT AND
 OUTDOOR AIR DUCT.
 6 )PAGE M-1 ROOM 102 PLEASE REFER TO SECTION 601.4
 BALANCED RETURN AIR2004 FBC (M).
 7)PLEASE REFER TO SECTION 601.4 BALANCED RETURN AIR
 FOR ALL HABITABLE ROOMS.
 8)PLEASE PROVIDE MANUFACTURERS INSTALLATION
 INSTRUCTIONS ON THE PRE COOLED UNITS.
 9)PLEASE PROVIDE ENERGY CALCULATIONS AND MANUAL (J)
 WITH THE PLANS.
 10) PLEASE REFER TO SECTION 13-406.1.ABC.1.4.1 FLORIDA
 ENERGE CODE 2004. BUILDING CAVITIES.
 11)PLEASE REFER TO SECTION 13-410.1.ABC.3.6 CAVITIES
 OF THE BUILDING STRUCTURE. EXCEPTION