| Plan Review Notes For Permit 06090625 |
| Permit Number |
06090625 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2006-10-13 19:09:29 | 1)IN REGARDS TO NOTE #4 PAGE M-4 PLEASE REFER TO | | | SECTION 603.1.7 APPROVED CLOSURE SYSTEMS.THIS SECTION | | | INCLUDES FIBERGLASS DUCT . | | | 2)PAGE M-4 ON THE CONDENSOR MOUNTING DETAIL , PLEASE | | | PROVIDE THE GAGE OF 1 IN.STEAP ON THE PLANS. | | | 3)PLEASE PROVIDE ANCHOR DETAIL ON A/C STAND TO ROOF | | | ON PLANS. | | | 4)PAGE M-1 PLEASE PROVIDE DUCT SIZE ON OUTDOOR AIR | | | DUCT ON PLANS. | | | 5)PLEASE REFER TO SECTION 501.4 FOR EXHAUST DUCT AND | | | OUTDOOR AIR DUCT. | | | 6 )PAGE M-1 ROOM 102 PLEASE REFER TO SECTION 601.4 | | | BALANCED RETURN AIR2004 FBC (M). | | | 7)PLEASE REFER TO SECTION 601.4 BALANCED RETURN AIR | | | FOR ALL HABITABLE ROOMS. | | | 8)PLEASE PROVIDE MANUFACTURERS INSTALLATION | | | INSTRUCTIONS ON THE PRE COOLED UNITS. | | | 9)PLEASE PROVIDE ENERGY CALCULATIONS AND MANUAL (J) | | | WITH THE PLANS. | | | 10) PLEASE REFER TO SECTION 13-406.1.ABC.1.4.1 FLORIDA | | | ENERGE CODE 2004. BUILDING CAVITIES. | | | 11)PLEASE REFER TO SECTION 13-410.1.ABC.3.6 CAVITIES | | | OF THE BUILDING STRUCTURE. EXCEPTION |
|