Plan Review Notes
Plan Review Notes For Permit 06090625
Permit Number 06090625
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2006-10-25 09:29:501. CONSTRUCTION, ALTERATION AND DEMOLITION ACTIVITIES
 TO COMPLY WITH NFPA 241.
 2. DEBRIS SHALL BE REMOVED FROM THE SITE DAILY.
 3. SEPARATE PLANS AND PERMITS REQUIRED FOR THE FIRE
 SPRINKLER SYSTEM MODIFICATIONS THAT ARE PLANNED. 4.
 PLEASE DECLARE INTERIOR FINISH CLASSIFICATIONS FOR
 WALLS AND CEILINGS.
 5. PLEASE PROVIDE PRODUCT LITERATURE AND APPROVALS FOR
 WINDOW E THAT HAS BEEN DECLARED AS TWO HOUR FIRE
 RATED.
 6. ENSURE THAT A KNOX-BOX IS PROVIDED SO THAT FIRE
 RESCUE CAN ACCESS THE BUILDING.
 7. ON PAGE E3 NOTE INDICATES THAT NOT ALL FIRE ALARM
 EQUIPMENT IS NOT SHOWN. MORE DETAILS ARE NEEDED
 REGARDING THE LOCATIONS OF ALL INITIATING AND SIGNALING
 APPLIANCES FOR THE FIRE ALARM SYSTEM.
 8. THE FIRE SPRINKLER SYSTEM AND FIRE ALARM SYSTEM
 SHALL BE MONITORED BY A LICENSED UL LISTED CENTRAL
 STATION APPROVED FOR CENTRAL STATION SERVICE.
 9. PLEASE INDICATE THE TYPE OF FOOD PLANNED FOR THE
 FUTURE SERVICE FOOD PREP PLANNED FOR THE CAFE.
 10. PANIC HARDWARE OR FIRE EXIT PANIC HARDWARE REQUIRED
 ON ALL EXIT DOORS THAT HAVE AN OCCUPANT LOAD OF 100 OR
 MORE PERSONS TRAVELING THROUGH THEM.
 11. ONLY TWO DOORS ARE DECLARED TO BE FIRE RATED ON THE
 DOOR SCHEDULE ON PAGE A-13.
 12. PLEASE PROVIDE FLAMESPREAD DETAILS ON SONIC WALL
 FOLDING PARTITIONS.
 13. ENSURE THAT BUILDING ADDRESS IS PROVIDED ON THE
 BUILDING. ADDRESS SHALL BE A MINIMUM OF AT LEAST 6"
 HIGH AND AT LEAST 1" IN WIDTH.
 14. PLEASE DECLARE OCCUPANCY LOAD FOR AREAS WHERE THE
 ALTERNATING TREAD STAIRS ARE PLANNED.
 15. PLEASE PROVIDE PRESCRIPTIVE STRENGTH REQUIREMENTS
 FOR ALL NEW HANDRAILS AND GUARDRAILS.
 16. THE LIFE SAFETY PLAN ON PAGE LS-1 APPEARS TO BE
 MISSING EXIT SIGNS. EXIT SIGNS SHALL BE PROVIDED AT
 EXIT LOCATIONS AND IN AREAS SO DIRECT PERSONS TO
 EXITS.
 17. TACTILE SIGNS REQUIRED AT EXIT DOOR LOCATIONS. 18.
 IN SOME LOCATIONS "NO EXIT" SIGNS APPEAR TO BE NEEDED
 AS DOORS THAT ARE NOT EXITS ARE LOCATED NEAR DOORS THAT
 ARE EXITS.
 19. THE EXISTING ELECTRICAL ROOM DOOR MUST BE RATED
 SINCE IT WILL BE LOCATED WITHIN A TWO HOUR FIRE RATED
 WALL.
 20. COULD NOT LOCATE ANY PORTABLE FIRE EXTINGUISHERS ON
 LIFE SAFETY PLAN.
 21. PLEASE ENSURE THAT THE REQUIREMENTS FOR REQUIRED
 FIRE WATCH ACTIVITIES ARE UNDERSTOOD PRIOR TO BEGINNING
 WORK.
 22. ALL EXITS ARE TO REMAIN CLEAR AND UNOBSTRUCTED
 DURING CONSTRUCTION ACTIVITIES.
 23. PLEASE PROVIDE A FURNITURE OR SEATING LAYOUT FOR
 ASSEMBLY AREAS OF THE BUILDING.
 24. MAXIMUM OCCUPANTS LOAD WILL BE DETERMINED BY THE
 BUREAU OF FIRE PREVENTION.
 25. MAXIMUM OCCUPANT LOAD SIGNS WILL BE REQUIRED FOR
 THE BUILDING.
  
 MIKE CARSILLO, CHIEF FIRE PREVENTION OFFICER 804-4709