| 2006-10-25 09:29:50 | 1. CONSTRUCTION, ALTERATION AND DEMOLITION ACTIVITIES |
| | TO COMPLY WITH NFPA 241. |
| | 2. DEBRIS SHALL BE REMOVED FROM THE SITE DAILY. |
| | 3. SEPARATE PLANS AND PERMITS REQUIRED FOR THE FIRE |
| | SPRINKLER SYSTEM MODIFICATIONS THAT ARE PLANNED. 4. |
| | PLEASE DECLARE INTERIOR FINISH CLASSIFICATIONS FOR |
| | WALLS AND CEILINGS. |
| | 5. PLEASE PROVIDE PRODUCT LITERATURE AND APPROVALS FOR |
| | WINDOW E THAT HAS BEEN DECLARED AS TWO HOUR FIRE |
| | RATED. |
| | 6. ENSURE THAT A KNOX-BOX IS PROVIDED SO THAT FIRE |
| | RESCUE CAN ACCESS THE BUILDING. |
| | 7. ON PAGE E3 NOTE INDICATES THAT NOT ALL FIRE ALARM |
| | EQUIPMENT IS NOT SHOWN. MORE DETAILS ARE NEEDED |
| | REGARDING THE LOCATIONS OF ALL INITIATING AND SIGNALING |
| | APPLIANCES FOR THE FIRE ALARM SYSTEM. |
| | 8. THE FIRE SPRINKLER SYSTEM AND FIRE ALARM SYSTEM |
| | SHALL BE MONITORED BY A LICENSED UL LISTED CENTRAL |
| | STATION APPROVED FOR CENTRAL STATION SERVICE. |
| | 9. PLEASE INDICATE THE TYPE OF FOOD PLANNED FOR THE |
| | FUTURE SERVICE FOOD PREP PLANNED FOR THE CAFE. |
| | 10. PANIC HARDWARE OR FIRE EXIT PANIC HARDWARE REQUIRED |
| | ON ALL EXIT DOORS THAT HAVE AN OCCUPANT LOAD OF 100 OR |
| | MORE PERSONS TRAVELING THROUGH THEM. |
| | 11. ONLY TWO DOORS ARE DECLARED TO BE FIRE RATED ON THE |
| | DOOR SCHEDULE ON PAGE A-13. |
| | 12. PLEASE PROVIDE FLAMESPREAD DETAILS ON SONIC WALL |
| | FOLDING PARTITIONS. |
| | 13. ENSURE THAT BUILDING ADDRESS IS PROVIDED ON THE |
| | BUILDING. ADDRESS SHALL BE A MINIMUM OF AT LEAST 6" |
| | HIGH AND AT LEAST 1" IN WIDTH. |
| | 14. PLEASE DECLARE OCCUPANCY LOAD FOR AREAS WHERE THE |
| | ALTERNATING TREAD STAIRS ARE PLANNED. |
| | 15. PLEASE PROVIDE PRESCRIPTIVE STRENGTH REQUIREMENTS |
| | FOR ALL NEW HANDRAILS AND GUARDRAILS. |
| | 16. THE LIFE SAFETY PLAN ON PAGE LS-1 APPEARS TO BE |
| | MISSING EXIT SIGNS. EXIT SIGNS SHALL BE PROVIDED AT |
| | EXIT LOCATIONS AND IN AREAS SO DIRECT PERSONS TO |
| | EXITS. |
| | 17. TACTILE SIGNS REQUIRED AT EXIT DOOR LOCATIONS. 18. |
| | IN SOME LOCATIONS "NO EXIT" SIGNS APPEAR TO BE NEEDED |
| | AS DOORS THAT ARE NOT EXITS ARE LOCATED NEAR DOORS THAT |
| | ARE EXITS. |
| | 19. THE EXISTING ELECTRICAL ROOM DOOR MUST BE RATED |
| | SINCE IT WILL BE LOCATED WITHIN A TWO HOUR FIRE RATED |
| | WALL. |
| | 20. COULD NOT LOCATE ANY PORTABLE FIRE EXTINGUISHERS ON |
| | LIFE SAFETY PLAN. |
| | 21. PLEASE ENSURE THAT THE REQUIREMENTS FOR REQUIRED |
| | FIRE WATCH ACTIVITIES ARE UNDERSTOOD PRIOR TO BEGINNING |
| | WORK. |
| | 22. ALL EXITS ARE TO REMAIN CLEAR AND UNOBSTRUCTED |
| | DURING CONSTRUCTION ACTIVITIES. |
| | 23. PLEASE PROVIDE A FURNITURE OR SEATING LAYOUT FOR |
| | ASSEMBLY AREAS OF THE BUILDING. |
| | 24. MAXIMUM OCCUPANTS LOAD WILL BE DETERMINED BY THE |
| | BUREAU OF FIRE PREVENTION. |
| | 25. MAXIMUM OCCUPANT LOAD SIGNS WILL BE REQUIRED FOR |
| | THE BUILDING. |
| | |
| | MIKE CARSILLO, CHIEF FIRE PREVENTION OFFICER 804-4709 |