2006-10-14 16:27:36******** UNSAT ************
  
  
 1) NOTE: PLEASE SEE COVER SHEETS WHICH CONTAINS MEP
 DESIGN ENGINEERING SERVICES. PLEASE KNOW AS NOTED AND
 GIVEN ON PREVIOUS REVIEWS ON OTHER PROJECTS , IF THIS
 TITLE IS BEING USED THIS FIRM MUST BE LICENSED WHEN
 PROVIDING "ENGINEERING SERVICES" AS REQUIRED UNDER FS
 471.023, FAC 61G15-23.002.
 PLEASE KNOW THIS COVER SHEET IS BEING RETAINED BY THIS
 OFFICE.
  
 2) NOTE: PLEASE SEE FIRE REVIEW COMMENTS FOR MIN
 DEVICES REQUIRED TO BE SHOWN AT THIS TIME FOR FIRE
 ALARM SYSTEM. IT IS KNOWN AND REQUIRED FOR THE FA
 SYSTEM TO BE DONE UNDER A SEPARATE PERMIT, HOWEVER MIN
 DEVICES AND LEVELS FOR ADA NEED TO BE SHOWN AT THIS
 TIME.
 PLEASE SEE FBC 2004 11-4.28, .2, AND .3(4).
  
 3) NOTE: PLEASE KNOW, THE FACP LOCATION WILL BE
 DETERMINED BY THEFIRE MARSHAL'S OFFICE AND AS THIS IS
 SHOWN ONE THE ELECTRICAL PLANS, THIS MAY AFFECT THE
 PLANS SUBMITTED AS THE PANEL MAY BE REQUIRED TO BE
 MOVED TO THE NEAREST POINT /ENTRANCE TO ADDRESS OF
 BUILDING?
  
 4) NOTE: PLEASE ALSO SEE NFPA-72 CHAPTER 4, ALSO THE
 FOLLOWING:
 4.4.1.4.2.1THE DEDICATED BRANCH CIRCUIT(S) AND
 CONNECTIONS SHALL BE MECHANICALLY PROTECTED.(
 4.4.1.4.2.2CIRCUIT DISCONNECTING MEANS SHALL HAVE A
 RED MARKING, SHALL BE ACCESSIBLE ONLY TO AUTHORIZED
 PERSONNEL, AND SHALL BE IDENTIFIED AS "FIRE ALARM
 CIRCUIT."
 4.4.1.4.2.3THE LOCATION OF THE CIRCUIT DISCONNECTING
 MEANS SHALL BE PERMANENTLY IDENTIFIED AT THE FIRE ALARM
 CONTROL UNIT.
  
 5) NOTE: PLEASE SEE FBC CHAPTER 13 AS AT THIS TIME NO
 REQUIREMENTS OR PLANS SUBMITTED ARE SHOWING COMPLIANCE
 WITH THIS. PLEASE PROVIDE WORST CASE SCENARIO FOR
 VOLTAGE DROP OF FEEDERS AND BRANCH CIRCUITS.
 13-413.1ABC.1, .1.1, .1.2.
 PLEASE SEE 13-415.1.ABC.1.1, .1.2 AND .1.3 FOR
 AUTOMATED SYSTEM FOR CONTROL FOR ALL LIGTHING. PLEASE
 PROVIDE SCHEDULING, TIMES ONOVER RIDE DEVICES ETC(MAX
 ALLOWED) WHICH DEPENDS ON OR CHOSEN.
 PLEASE PROVIDE CALCULATIONS PER 13-415.2.ABC.1, TABLES
 13-415.2.C.1, 415.2.B.1
  
 6) NOTE: PLEASE SEE 240.4(C) FOR MINIMUM SIZES FOE THE
 SEC'S . PLEASE SEE 310.16, 110.14 ETC.
 CONDUCTORS AS SHOWN ARE NOT LARGE ENOUGH.
  
 7) NOTE: PLEASE SEE 250.66 FOR SIZING THE MIN GEC .
 PLEASE ALSO SEE THE GROUNDING "DELTA" DETAIL SHOWN.
 (3/0MIN).
  
 8) NOTE: PLEASE INDICATE THE MINIMUM SIZES FOR ALL
 EQUIPMENT GROUNDING CONDUCTORS FROM MDP TO ALL SUB
 PANEL.
 250.24, 250.110, 250.122 ETC.
 PLEASE SEE THE SIZE OF THE EQUIPMENT GROUNDING AS SHOWN
 ON THE RISER FROM THE MAIN TO THE DP IS NOT LARGE
 ENOUGH. PLEASE SEE 250.122, 3/0MIN.(IN EACH).
  
 9) NOTE: PLEASE PROVIDE THE AIC RATINGS FOR ALL
 EQUIPMENT, INCLUDING MAINS. 110.9. IT IS NOTED THAT THE
 NOTE ON PLANS MENTIONS 22K, HOWEVER PLEASE SEE 240.12
 AND PROVIDE DETAIL ON SELECTIVE COORDINATION.
  
 10) NOTE: PLEASE PROVIDE MINIMUM PHOTO-METRICS FOR ALL
 EGRESS PATHS. PLEASE SEE NFPA-101 2003, 7.8, 7.9
  
 11) NOTE: PLEASE CORRELATE AND CLARIFY ARCHITECTURAL
 PLANS WITH ELECTRICAL PLANS AND RISER. PLEASE SEE RISER
 APPEARS TO SHOW PANEL "D" LOCATED AT A DETACHED
 BLDG/STRUCTURE WHICH CORRELATES WITH SOME "A" SHEETS,
 HOWEVER THE ELECTRICAL PLANS SHOWS ALL AS ONE BLDG??
 225.31, 250.32 ??
  
 12) NOTE: PLEASE PROVIDE WIND LOAD CALCULATIONS AT THIS
 TIME FOR REVIEW OF LIGHT POLES. ( FBC 140 MPH)THE
 NOTE ON PLANS IS NOTED, HOWEVER THIS INFORMATION IS
 REQUIRED AT THIS TIME.
 PLEASE ALSO SUBMIT PHOTO-METRICS FOR PARKING LOT
 LIGHTING LEVELS.
 FBC 106.1.2, 106.3.5.1.2 ADMIN SECT.
  
 13) NOTE: PLEASE CLARIFY LARGEST MOTOR LOADS AT 125%>
 215.3, 230.42.
  
 14) NOTE: PLEASE PROVIDE A LOAD SUMMARY FOR ALL A/C
 LOADS WHICH ARE BEING FIGURED INTO THE ACTUALLOAD
 CALCULATIONS. PLEASE SEE 220.21 AS ONLY THE LARGER OF
 THE LOADS ON ANY A/C "SYSTEM" IS REQUIRE TO BE SHOWN.
  
 15) NOTE: PLEASE SEE 220.12B FOR TRACK LIGHTING. PLEASE
 SHOW LOADS AND HOW THEY WERE DERIVED FOR THESE AS
 REQUIRED.
 220,
 FBC 106.3.5.1.2 ADMIN SECT.
  
 16) NOTE: PLEASE PLACE ROOM AND AREA DESIGNATIONS ON
 PLANS AND CORRELATE WITH PANEL SCHEDULES.
 PLEASE SEE PANEL SCHEDULES SHALL BE SPECIFIC FOR EACH
 ROOM OR ARE BEING SERVED. IE; OFFICE 106 RECEPTS, BATHS
 LTS, CONFERENCE RM RECEPTS , ETC.
 PLEASE KNOW, IT IS KNOWN THAT DURING CONSTRUCTIONS
 THESE SCHEDULE MOST LIKELY WILL BE REVISED, HOWEVER
 THIS IS REQUIRED AT THIS TIME.
 PANEL SCHEDULE MAY NOT ONLY SAY: GEN LTS, GEN RECEPTS
 ETC,.
 408.4, 240.4, 310.16
 FBC 106.1.2, 106.3.5.1.2.
  
 17) NOTE: PLEASE SEE 700.12E FOR CIRCUITING OF ALL
 EM/EXT LTS. THE BRANCH CIRCUIT FEEDING THE UNIT
 EQUIPMENT SHALL BE THE SAME BRANCH CIRCUIT AS THAT
 SERVING THE NORMAL LIGHTING IN THE AREA AND CONNECTED
 AHEAD OF ANY LOCAL SWITCHES.
  
 18) NOTE: PLEASE SEE 210.8B3 FOR GFI PROTECTION WHICH
 REQUIRES ALL 15- AND 20-AMPERE, 125-VOLT RECEPTACLES IN
 NONDWELLING-TYPE KITCHENS TO BE GFCI PROTECTED. THIS
 REQUIREMENT APPLIES TO EACH AND EVERY 15- AND
 20-AMPERE, 125-VOLT KITCHEN RECEPTACLE, WHETHER OR NOT
 THE RECEPTACLE SERVES COUNTERTOP APPLIANCES.
  
 ** PLEASE SEE COMMENTS FROM OTHER TRADES WHICH MAY VERY
 WELL AFFECT THE ELECTRICAL PLANS.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  
  
  
  
  
  