| 2006-10-14 16:27:36 | ******** UNSAT ************ |
| | |
| | |
| | 1) NOTE: PLEASE SEE COVER SHEETS WHICH CONTAINS MEP |
| | DESIGN ENGINEERING SERVICES. PLEASE KNOW AS NOTED AND |
| | GIVEN ON PREVIOUS REVIEWS ON OTHER PROJECTS , IF THIS |
| | TITLE IS BEING USED THIS FIRM MUST BE LICENSED WHEN |
| | PROVIDING "ENGINEERING SERVICES" AS REQUIRED UNDER FS |
| | 471.023, FAC 61G15-23.002. |
| | PLEASE KNOW THIS COVER SHEET IS BEING RETAINED BY THIS |
| | OFFICE. |
| | |
| | 2) NOTE: PLEASE SEE FIRE REVIEW COMMENTS FOR MIN |
| | DEVICES REQUIRED TO BE SHOWN AT THIS TIME FOR FIRE |
| | ALARM SYSTEM. IT IS KNOWN AND REQUIRED FOR THE FA |
| | SYSTEM TO BE DONE UNDER A SEPARATE PERMIT, HOWEVER MIN |
| | DEVICES AND LEVELS FOR ADA NEED TO BE SHOWN AT THIS |
| | TIME. |
| | PLEASE SEE FBC 2004 11-4.28, .2, AND .3(4). |
| | |
| | 3) NOTE: PLEASE KNOW, THE FACP LOCATION WILL BE |
| | DETERMINED BY THEFIRE MARSHAL'S OFFICE AND AS THIS IS |
| | SHOWN ONE THE ELECTRICAL PLANS, THIS MAY AFFECT THE |
| | PLANS SUBMITTED AS THE PANEL MAY BE REQUIRED TO BE |
| | MOVED TO THE NEAREST POINT /ENTRANCE TO ADDRESS OF |
| | BUILDING? |
| | |
| | 4) NOTE: PLEASE ALSO SEE NFPA-72 CHAPTER 4, ALSO THE |
| | FOLLOWING: |
| | 4.4.1.4.2.1THE DEDICATED BRANCH CIRCUIT(S) AND |
| | CONNECTIONS SHALL BE MECHANICALLY PROTECTED.( |
| | 4.4.1.4.2.2CIRCUIT DISCONNECTING MEANS SHALL HAVE A |
| | RED MARKING, SHALL BE ACCESSIBLE ONLY TO AUTHORIZED |
| | PERSONNEL, AND SHALL BE IDENTIFIED AS "FIRE ALARM |
| | CIRCUIT." |
| | 4.4.1.4.2.3THE LOCATION OF THE CIRCUIT DISCONNECTING |
| | MEANS SHALL BE PERMANENTLY IDENTIFIED AT THE FIRE ALARM |
| | CONTROL UNIT. |
| | |
| | 5) NOTE: PLEASE SEE FBC CHAPTER 13 AS AT THIS TIME NO |
| | REQUIREMENTS OR PLANS SUBMITTED ARE SHOWING COMPLIANCE |
| | WITH THIS. PLEASE PROVIDE WORST CASE SCENARIO FOR |
| | VOLTAGE DROP OF FEEDERS AND BRANCH CIRCUITS. |
| | 13-413.1ABC.1, .1.1, .1.2. |
| | PLEASE SEE 13-415.1.ABC.1.1, .1.2 AND .1.3 FOR |
| | AUTOMATED SYSTEM FOR CONTROL FOR ALL LIGTHING. PLEASE |
| | PROVIDE SCHEDULING, TIMES ONOVER RIDE DEVICES ETC(MAX |
| | ALLOWED) WHICH DEPENDS ON OR CHOSEN. |
| | PLEASE PROVIDE CALCULATIONS PER 13-415.2.ABC.1, TABLES |
| | 13-415.2.C.1, 415.2.B.1 |
| | |
| | 6) NOTE: PLEASE SEE 240.4(C) FOR MINIMUM SIZES FOE THE |
| | SEC'S . PLEASE SEE 310.16, 110.14 ETC. |
| | CONDUCTORS AS SHOWN ARE NOT LARGE ENOUGH. |
| | |
| | 7) NOTE: PLEASE SEE 250.66 FOR SIZING THE MIN GEC . |
| | PLEASE ALSO SEE THE GROUNDING "DELTA" DETAIL SHOWN. |
| | (3/0MIN). |
| | |
| | 8) NOTE: PLEASE INDICATE THE MINIMUM SIZES FOR ALL |
| | EQUIPMENT GROUNDING CONDUCTORS FROM MDP TO ALL SUB |
| | PANEL. |
| | 250.24, 250.110, 250.122 ETC. |
| | PLEASE SEE THE SIZE OF THE EQUIPMENT GROUNDING AS SHOWN |
| | ON THE RISER FROM THE MAIN TO THE DP IS NOT LARGE |
| | ENOUGH. PLEASE SEE 250.122, 3/0MIN.(IN EACH). |
| | |
| | 9) NOTE: PLEASE PROVIDE THE AIC RATINGS FOR ALL |
| | EQUIPMENT, INCLUDING MAINS. 110.9. IT IS NOTED THAT THE |
| | NOTE ON PLANS MENTIONS 22K, HOWEVER PLEASE SEE 240.12 |
| | AND PROVIDE DETAIL ON SELECTIVE COORDINATION. |
| | |
| | 10) NOTE: PLEASE PROVIDE MINIMUM PHOTO-METRICS FOR ALL |
| | EGRESS PATHS. PLEASE SEE NFPA-101 2003, 7.8, 7.9 |
| | |
| | 11) NOTE: PLEASE CORRELATE AND CLARIFY ARCHITECTURAL |
| | PLANS WITH ELECTRICAL PLANS AND RISER. PLEASE SEE RISER |
| | APPEARS TO SHOW PANEL "D" LOCATED AT A DETACHED |
| | BLDG/STRUCTURE WHICH CORRELATES WITH SOME "A" SHEETS, |
| | HOWEVER THE ELECTRICAL PLANS SHOWS ALL AS ONE BLDG?? |
| | 225.31, 250.32 ?? |
| | |
| | 12) NOTE: PLEASE PROVIDE WIND LOAD CALCULATIONS AT THIS |
| | TIME FOR REVIEW OF LIGHT POLES. ( FBC 140 MPH)THE |
| | NOTE ON PLANS IS NOTED, HOWEVER THIS INFORMATION IS |
| | REQUIRED AT THIS TIME. |
| | PLEASE ALSO SUBMIT PHOTO-METRICS FOR PARKING LOT |
| | LIGHTING LEVELS. |
| | FBC 106.1.2, 106.3.5.1.2 ADMIN SECT. |
| | |
| | 13) NOTE: PLEASE CLARIFY LARGEST MOTOR LOADS AT 125%> |
| | 215.3, 230.42. |
| | |
| | 14) NOTE: PLEASE PROVIDE A LOAD SUMMARY FOR ALL A/C |
| | LOADS WHICH ARE BEING FIGURED INTO THE ACTUALLOAD |
| | CALCULATIONS. PLEASE SEE 220.21 AS ONLY THE LARGER OF |
| | THE LOADS ON ANY A/C "SYSTEM" IS REQUIRE TO BE SHOWN. |
| | |
| | 15) NOTE: PLEASE SEE 220.12B FOR TRACK LIGHTING. PLEASE |
| | SHOW LOADS AND HOW THEY WERE DERIVED FOR THESE AS |
| | REQUIRED. |
| | 220, |
| | FBC 106.3.5.1.2 ADMIN SECT. |
| | |
| | 16) NOTE: PLEASE PLACE ROOM AND AREA DESIGNATIONS ON |
| | PLANS AND CORRELATE WITH PANEL SCHEDULES. |
| | PLEASE SEE PANEL SCHEDULES SHALL BE SPECIFIC FOR EACH |
| | ROOM OR ARE BEING SERVED. IE; OFFICE 106 RECEPTS, BATHS |
| | LTS, CONFERENCE RM RECEPTS , ETC. |
| | PLEASE KNOW, IT IS KNOWN THAT DURING CONSTRUCTIONS |
| | THESE SCHEDULE MOST LIKELY WILL BE REVISED, HOWEVER |
| | THIS IS REQUIRED AT THIS TIME. |
| | PANEL SCHEDULE MAY NOT ONLY SAY: GEN LTS, GEN RECEPTS |
| | ETC,. |
| | 408.4, 240.4, 310.16 |
| | FBC 106.1.2, 106.3.5.1.2. |
| | |
| | 17) NOTE: PLEASE SEE 700.12E FOR CIRCUITING OF ALL |
| | EM/EXT LTS. THE BRANCH CIRCUIT FEEDING THE UNIT |
| | EQUIPMENT SHALL BE THE SAME BRANCH CIRCUIT AS THAT |
| | SERVING THE NORMAL LIGHTING IN THE AREA AND CONNECTED |
| | AHEAD OF ANY LOCAL SWITCHES. |
| | |
| | 18) NOTE: PLEASE SEE 210.8B3 FOR GFI PROTECTION WHICH |
| | REQUIRES ALL 15- AND 20-AMPERE, 125-VOLT RECEPTACLES IN |
| | NONDWELLING-TYPE KITCHENS TO BE GFCI PROTECTED. THIS |
| | REQUIREMENT APPLIES TO EACH AND EVERY 15- AND |
| | 20-AMPERE, 125-VOLT KITCHEN RECEPTACLE, WHETHER OR NOT |
| | THE RECEPTACLE SERVES COUNTERTOP APPLIANCES. |
| | |
| | ** PLEASE SEE COMMENTS FROM OTHER TRADES WHICH MAY VERY |
| | WELL AFFECT THE ELECTRICAL PLANS. |
| | |
| | ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |