| 2006-10-10 16:55:41 | BUILDING PLAN REVIEW |
| | PERMIT: 06090625 |
| | ADD: 425 24TH ST |
| | CONT: SOUTHERN CONSTRUCTION SYSTEMS |
| | |
| | TEL: (561)662-2755 |
| | FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | 1STREVIEW |
| | ACTION: DENIED |
| | |
| | 1)--- VERY IMPORTANT STATEMENT --- |
| | PLEASE DO NOT IGNORE! |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUM- |
| | BER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICA |
| | TION PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. THANK |
| | YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | 2)FL S S 713.13 |
| | NOTICE OF COMMENCEMENT, TO BE FILED |
| | WITH THE CLERK OF THE COURT BEFORE A |
| | PERMIT WILL BE ISSUED. NOTE: 713.13(2) |
| | IF THE WORK DESCRIBED IN THE NOTICE |
| | OF COMMENCEMENT IS NOT ACTUALLY COMMENCED |
| | WITHIN 90 DAYS AFTER THE RECORDING |
| | THEREOF, SUCH NOTICE IS NULL & VOID. |
| | |
| | 3 ) SEE ATTACHMENT, CITY OF WPB GIS |
| | INDICATES THERE ARE TWO LOTS , NOT ONE. THE SITE PLAN |
| | INDICATES ALSO INDICATES SEPERATE LOTS AND |
| | ONLY 9'-10" BETWEEN BUILDINGS,BUT NO |
| | DIMENSION FROM THE PROPERTY LINE TO EACHBUILDING. THE |
| | PROPOSED BUILDING STRUCTURE TRANSGRESSES LEGAL BOUNDARY |
| | LINES |
| | BETWEEN THE LOTS WHICH COMBINE TO FORM |
| | 'THE SITE'.A 'UNITY OF TITLE' SHALL BE |
| | RECORDED AT THE COUNTY COURTHOUSE. |
| | SUBMIT A COPY OF THE RECORDED 'UNITY OF |
| | OF TITLE' DOCUMENT SO THAT FBC TABLE 600 |
| | BOUNDARY LINE REQUIREMENTS MAY BE DEEMED |
| | NOT APPLICABLE. |
| | THE LIFE SAFETY PLAN INDICATES AN ADDITION |
| | THAT CROSSES THE LOT LINE, FORMING ONE BUILDING. |
| | |
| | 4) PLEASE INDICATE COMPLIANCE WITH AREA |
| | TABLE 503.PROVIDE AREA INCREASES (506.3) |
| | TO SHOW COMPLIANCE |
| | WITH TABLE 503. |
| | |
| | 5) NOTE:) 109.3.10* IMPACT OF CONSTRUCTION. ALL |
| | CONSTRUCTION ACTIVITY REGULATED BY |
| | THIS CODE SHALL BE PERMORMED IN A MANNER |
| | SO AS NOT TO ADVERSELY IMPACT THE |
| | CONDITION OF ADJACENT PROPERTY, UNLESS |
| | SUCH ACTIVITY IS PERMITTED TO AFFECT |
| | SAID PROPERTY PURSUANT TO A CONSENT BY |
| | THE APPLICABLE PROPERTY OWNER, UNDER |
| | TERMS & CONDITIONS AGREEABLE TO THE |
| | APPLICABLE PROPERTY OWNER.THIS INCLUDES |
| | BUT IS NOT LIMITED TO THE CONTROL OF |
| | DUST, NOISE, WATER OR DRAINAGE RUN-OFF, |
| | DEBRIS, AND THE STORAGE OF CONSTRUCTION |
| | MATERIALS. NEW CONSTRUCTION ACTIVITY |
| | SHALL NOT ADVERSELY IMPACT HISTORIC |
| | SURFACE WATER DRAINAGE FLOWS SERVING |
| | ADJACENT PROPERTIES, & MAY REQUIRE |
| | SPECIAL DRAINAGE DESIGN COMPLYING WITH |
| | ENGINEERING STANDARDS TO PRESERVE THE |
| | POSITIVE PATTERNS OF THE AFFECTED SITES. |
| | ACCORDINGLY, DEVELOPERS, CONTRACTORS, |
| | AND OWNERS OF ALL NEW RESIDENTIAL |
| | DEVELOPMENT, INCLUDING ADDITIONS, POOLS, |
| | PATIOS, DRIVEWAYS, DECKS, OR SIMILAR |
| | ITEMS, ON EXISTING PROPERTIES RESULTING |
| | IN A DECREASE IN EXCESS OF 800SQ FT OF |
| | PERMEABLE LAND AREA ON ANY PARCELL SHALL |
| | AS A PERMIT CONDITION, PROVIDE A |
| | PROFESSIONALLY PREPARED DRAINAGE PLAN |
| | CLEARLY INDICATING COMPLIANCE WITH THIS |
| | PARAGRAPH. UPON COMPLETION OF THE |
| | IMPROVEMENT, A CERTIFICATE FROM A |
| | LICENSED ENGINEER SHALL BE SUBMITTED TO |
| | THE INSPECTOR IN ORDER TO RECEIVE |
| | APPROVAL OF THE FINAL INSPECTION. |
| | |
| | 6 ) 109.3.10.1 HURICANE PROTECTION. |
| | IT SHALL BE UNLAWFUL FOR ANY PERSON TO |
| | ALLOW CONSTRUCTION RELATED MATERIALS |
| | EQUIPMENT AND DEBRIS TO REMAIN LOOSE OR |
| | OTHERWISE UNSECURED AT A CONSTRUCTION |
| | SITE FROM 24 HRS. AFTER A HURRICANE |
| | WATCH HAS BEEN ISSUED UNTIL THE |
| | HURRICANE WATCH OR WARNING HAS BEEN |
| | LIFTED. ALL SUCH CONSTRUCTION MATERIALS, |
| | EQUIPMENT AND DEBRIS SHALL BE EITHER |
| | REMOVED FROM THE CONSTRUCTION SITE OR |
| | SECURED IN SUCH A MANNER AS TO MINIMIZE |
| | THE DANGER OF SUCH CONSTRUCTION |
| | MATERIALS, EQUIPMENT AND DEBRIS CAUSING |
| | DAMAGE TO PERSONS OR PROPERTY FROM HIGH |
| | WINDS. ANY PERSONS WHO FAILS TO COMPLY |
| | TO REMOVE OR SECURE THE CONSTRUCTION |
| | MATERIALS EQUIPMENT AND DEBRIS WITHIN |
| | 24 HRS AFTER A HURRICANE WATCH HAS BEEN |
| | ISSUED SHALL BE SUBJECT TO A FINE NOT TO |
| | EXCEED $500.00. |
| | IN ADDITION TO THE ABOVE, A LICENSED |
| | CONTRACTOR WHO VIOLATES THIS SECTION |
| | SHALL BE SUBJECT TO DISCIPLINE PURSUANT |
| | TO SECTION 113 OF THIS CHAPTER. |
| | |
| | 7) SHEET D-1 NORTH WALL OF THE EXISTING BUILDING |
| | INDICATES NEW OPENINGS IN WALL. THE SURVEY INDICATES |
| | THE BUILDING TO BE ANYWHERE FROM |
| | 2.5' TO 2.8' AWAY FROM THE |
| | PROPERTY LINE. PLEASE SEE TABLE 704.8 FOR PROTECTED AND |
| | NONPROTECTED OPENINGS, 0'-3' THE TABLE STATES NO |
| | OPENINGS ARE ALLOWED. |
| | |
| | 8) LS-1 DOOR# 108 SWINGS OVER THE PROPERTY LINE. 3202.2 |
| | ENCROACHMENTS ABOVE GRADE AND BELOW 8 FEET IN HEIGHT. |
| | ENCROACHMENTS INTO THE PUBLIC RIGHT-OF-WAY ABOVE GRADE |
| | AND BELOW 8 FEET (2438 MM) IN HEIGHT SHALL BE |
| | PROHIBITED EXCEPT AS PROVIDED FOR IN SECTIONS 3202.2.1 |
| | THROUGH 3202.2.3 . DOORS AND WINDOWS SHALL NOT OPEN OR |
| | PROJECT INTO THE PUBLIC RIGHT-OF-WAY. |
| | |
| | 9) LS-1 DOOR# 118 ALSO IS MISSING A LANDING ON THE |
| | EXTERIOR |
| | SIDE. 1008.1.5 LANDINGS AT DOORS. LANDINGS SHALL HAVE |
| | A |
| | WIDTH NOT LESS THAN THE WIDTH OF THE STAIRWAY OR THE |
| | DOOR, |
| | WHICHEVER IS THE GREATER. DOORS IN THE FULLY OPEN |
| | POSITION |
| | SHALL NOT REDUCE A REQUIRED DIMENSION BY MORE THAN 7 |
| | INCHES |
| | (178 MM). WHEN A LANDING SERVES AN OCCUPANT LOAD OF 50 |
| | OR MORE, DOORS IN ANY POSITION SHALL NOT REDUCE THE |
| | LANDING |
| | TO LESS THAN ONE-HALF ITS REQUIRED WIDTH. LANDINGS |
| | SHALL HAVE |
| | A LENGTH MEASURED IN THE DIRECTION OF TRAVEL OF NOT |
| | LESS THAN |
| | 44 INCHES (1118 MM). |
| | |
| | 10)LS-1 THE SOUTHWEST CORNER OF THE BUILDING |
| | INDICATES A |
| | NEW ADDITION, A TICKET BOOTH, JUST WEST OF THIS AREA IS |
| | WHAT APPEARS |
| | TO BE A FENCED IN AREA WITH EITHER GATES OR DOORS. THEY |
| | OPPOSE |
| | EACH OTHER. THERE IS TWO ISSUES: |
| | |
| | 10A)1008.1.2 EGRESS DOORS SHALL BE SIDE-SWINGING. |
| | DOORS |
| | SHALL SWING IN THE DIRECTION OF EGRESS TRAVEL WHERE |
| | SERVING AN |
| | OCCUPANT LOAD OF 50 OR MORE PERSONS . |
| | |
| | 10B) 11-4.13.7 TWO DOORS IN SERIES. |
| | THE MINIMUM SPACE BETWEEN TWO HINGED OR PIVOTED DOORS |
| | IN SERIES SHALL BE 48 INCHES (1219 MM) PLUS THE WIDTH |
| | OF ANY |
| | DOOR SWINGING INTO THE SPACE. DOORS IN SERIES SHALL |
| | SWING |
| | EITHER IN THE SAME DIRECTION OR AWAY FROM THE SPACE |
| | BETWEEN THE DOORS [SEE FIGURE 11-26 (A)]. |
| | |
| | 11A) LS-1 THE OTHER ISSUE IS WILL THERE BE MULTIPLE |
| | EVENTS |
| | OCCURING AT THIS SITE AT THE SAME TIME? |
| | |
| | 11B)THE MAIN COMMUNITY HALL DOES HAVE A FOYER, PLEASE |
| | PROVIDE |
| | A QUEUING PLAN THAT WILL NOT EMPEDE EXITING. 1024.4 |
| | FOYERS AND LOBBIES. IN GROUP A-1 OCCUPANCIES, WHERE |
| | PERSONS ARE ADMITTED TO THE BUILDING AT TIMES WHEN |
| | SEATS ARE NOT AVAILABLE AND ARE ALLOWED TO WAIT IN A |
| | LOBBY OR |
| | SIMILAR SPACE, SUCH USE OF LOBBY OR SIMILAR SPACE SHALL |
| | NOT |
| | ENCROACH UPON THE REQUIRED CLEAR WIDTH OF THE MEANS |
| | OF |
| | EGRESS. SUCH WAITING AREAS SHALL BE SEPARATED FROM |
| | THE |
| | |
| | REQUIRED MEANS OF EGRESS BY SUBSTANTIAL PERMANENT |
| | PARTITIONS |
| | OR BY FIXED RIGID RAILINGS NOT LESS THAN 42 INCHES |
| | (1067 MM) |
| | HIGH. SUCH FOYER, IF NOT DIRECTLY CONNECTED TO A PUBLIC |
| | STREET |
| | BY ALL THE MAIN ENTRANCES OR EXITS, SHALL HAVE A |
| | STRAIGHT |
| | AND UNOBSTRUCTED CORRIDOR OR PATH OF TRAVEL TO EVERY |
| | SUCH |
| | MAIN ENTRANCE OR EXIT. |
| | |
| | 12)IN REVIEWING THE LS-1 SHEET AND SHEET SP-1 THE |
| | OCCUPANT LOAD |
| | TABLE IT APPEARS THAT THE LOADS WERE NOT DERIVED FROM |
| | TABLE 1004.1.2. |
| | THE BUSINESS OCCUPANCIES ARE LOW. CONFERENCE ROOM# |
| | 133 HAS |
| | ZERO, THE LOUNGE HAS ZERO OCCUPANT LOAD AS WELL AS |
| | STORAGE AREAS. |
| | THE COMMUNITY BOARD ROOM COULD ALSO BE FIGURED WITH A |
| | LOAD |
| | OF 7 SQ FT / PERSON.PLEASE PROVIDE A NEW ANYLSIS OF |
| | THE OCCUPANT |
| | LOADING. |
| | |
| | 13) THE LIFESAFETY PLAN INDICATES A FOYER AND OTHER |
| | CORRIDORS THAT |
| | SERVE THE A-1 ASSEMBLY OCCUPANCY BUT WIWTHOUT RATED |
| | CORRIDORS WITH |
| | CEILINGS. TABLE 1016.1 FOR SPRINKLERED BUILDINGS |
| | REQUIRES |
| | RATED CORRIDORSFOR ASSEMBLY OCCUPANCIES WITH AN |
| | OCCUPANT |
| | LOAD GREATER THAN 30. |
| | |
| | 14) LS-1 THE CORRIDOR DOOR NOT IDENTIFIED BY DOORS 157 |
| | & 158SWINGS |
| | AGAINST EGRESS. 1008.1.2 DOORS SHALL SWING IN THE |
| | DIRECTION |
| | OF EGRESS TRAVELWHERE SERVING AN OCCUPANT LOAD OF 50 |
| | OR MORE PERSONS. |
| | |
| | 15)LS-1 STUDIO 1 & 2, THE EGRESS FOR EACH UNIT WORKS |
| | WHEN THE UNITS |
| | ARE FIGURED SEPERATELY BUT WHEN THE OCCUPANT LOAD IS |
| | COMBINEDTO |
| | FORM A SINGLE LARGE ROOM, THE OCCUPANT LOAD IS GREATER |
| | THAN 50 REQUIRING TWO EXITS |
| | TO BE 1/3 THE DIAGONAL OF THE ROOM SERVED . 1014.2.1. |
| | |
| | 16) LS-1 ROOM# 129IS LABELED FILE STORAGE, 1013.2 |
| | EGRESS THROUGH INTERVENING SPACES. |
| | EGRESS FROM A ROOM OR SPACE SHALL NOT PASS THROUGH |
| | ADJOINING OR INTERVENING ROOMS OR |
| | AREAS, EXCEPT WHERE SUCH ADJOINING ROOMS OR AREAS ARE |
| | ACCESSORY TO THE AREA SERVED; |
| | ARE NOT A HIGH-HAZARD OCCUPANCY AND PROVIDE A |
| | DISCERNIBLE PATH OF EGRESS TRAVEL TO AN |
| | EXIT. EGRESS SHALL NOT PASS THROUGH KITCHENS, STORAGE |
| | ROOMS, CLOSETS OR SPACES USED FOR |
| | SIMILAR PURPOSES. AN EXIT ACCESS SHALL NOT PASS |
| | THROUGH A ROOM THAT CAN BE LOCKED TO |
| | PREVENT EGRESS. MEANS OF EGRESS FROM DWELLING UNITS OR |
| | SLEEPING AREAS SHALL NOT LEAD |
| | THROUGH OTHER SLEEPING AREAS, TOILET ROOMS OR |
| | BATHROOMS. |
| | |
| | 17) LS-1THE EXISTINGELECTRIC ROOM SHOWS AN EXIT |
| | THROUGH THE ROOM |
| | WHICH SHOULD BE LOCKED.1013.2. |
| | |
| | 18)LS-1 THE DOUBLE ENTRY DOORS AT THE SOUTHEAST |
| | PORTION OF THE BUILDING |
| | SWING OVER THE PROPERTY LINE. 3202.2 ENCROACHMENTS |
| | ABOVE GRADE AND BELOW |
| | 8 FEET IN HEIGHT. ENCROACHMENTS INTO THE PUBLIC |
| | RIGHT-OF-WAY ABOVE GRADE AND |
| | BELOW 8 FEET (2438 MM) IN HEIGHT SHALL BE PROHIBITED |
| | EXCEPT AS PROVIDED FOR IN |
| | SECTIONS 3202.2.1 THROUGH 3202.2.3 . DOORS AND WINDOWS |
| | SHALL NOT OPEN OR |
| | PROJECT INTO THE PUBLIC RIGHT-OF-WAY. |
| | |
| | 19)LS-1 THIS SAME AREA INDICATES THE USE OF A |
| | VERTICAL LIFT. PLEASE SUBMIT |
| | THE MANUFACTURERS SPECSIN ACCORDANCE WITH ASME |
| | A17.1. |
| | (WHEELCHAIR LIFTS) ARE USED, THEY SHALL COMPLY WITH |
| | SECTIONS 11-4.2.4 , |
| | 11-4.5 , 11-4.27 , AND ASME A17.1, SAFETY CODE FOR |
| | ELEVATORS AND |
| | ESCALATORS , SECTION XX, 1990. |
| | |
| | 20) LS-1 PLANS INDICATE USE OF AN OVERHEAD DOOR# 163, |
| | THIS IS A PORTION OF A |
| | 1 HR RATED EXIT ACCESS CORRIDOR, ONLY SWING DOORS . |
| | 1008.1.2 DOOR SWING . |
| | EGRESS DOORS SHALL BE SIDE-HINGED SWINGING.SECURITY |
| | GRILLES CAN NOT |
| | BE USED FOR ASSEMBLY OCCUPANCY. |
| | NOTE, SECURUTY GRILLES :IN GROUPS B, F, M, R AND S, |
| | HORIZONTAL SLIDING OR |
| | VERTICAL SECURITY GRILLES ARE PERMITTED AT THE MAIN |
| | EXIT AND SHALL BE OPENABLE |
| | FROM THE INSIDE WITHOUT THE USE OF A KEY OR SPECIAL |
| | KNOWLEDGE OR EFFORT |
| | DURING PERIODS THAT THE SPACE IS OCCUPIED. THE GRILLES |
| | SHALL REMAIN SECURED |
| | IN THE FULL-OPEN POSITION DURING THE PERIOD OF |
| | OCCUPANCY BY THE GENERAL PUBLIC. |
| | WHERE TWO OR MORE MEANS OF EGRESS ARE REQUIRED, NOT |
| | MORE THAN ONE-HALF OF |
| | THE EXITS OR EXIT ACCESS DOORWAYS SHALL BE EQUIPPED |
| | WITH HORIZONTAL SLIDING OR |
| | VERTICAL SECURITY GRILLES. |
| | |
| | 21)LS-1 EAST END OF BUILDING THE RAMP INDICATES ONLY |
| | A 6" INCLINE, WHEREAS THE ELEVATIONS |
| | INDICATE A GREATER CHANGE IN GRADE. NEITHER THIS SHEET |
| | OR A-6 INDICATE THE CHANGE IN GRADE? |
| | NOTE IF THERE IS A CHANGE IN GRADE GREATER THAN 30" AN |
| | INTERMEDIATE LANDING WILL BE REQUIRED. |
| | |
| | 22) SHEET A-6RAMP AND STAIR FLOOR PLAN INDICATEA |
| | LANDING , BUT THE LANDING IS NOT CENTERED |
| | TO COMPLY WITH MANUVERING SPACES IN 11-4.13.6 AND 60" |
| | CLEAR IN 1010.6.3. |
| | |
| | 23) SHEET A-6 RAMP AND STAIR GAURDRAIL INEEDS TO COMPLY |
| | WITH: |
| | 1012.3 OPENING LIMITATIONS. OPEN GUARDS SHALL HAVE |
| | BALUSTERS OR |
| | ORNAMENTAL PATTERNS SUCH THAT A 4-INCH-DIAMETER (102 |
| | MM) SPHERE |
| | CANNOT PASS THROUGH ANY OPENING UP TO A HEIGHT OF 34 |
| | INCHES |
| | (864 MM). FROM A HEIGHT OF 34 INCHES (864 MM) TO 42 |
| | INCHES |
| | (1067 MM) ABOVE THE ADJACENT WALKING SURFACES, A |
| | SPHERE |
| | 8 INCHES (203 MM) IN DIAMETER SHALL NOT PASS. |
| | |
| | 24)SHEET A-6THE FLOOR PLAN OF THE STAIR AND RAMP, |
| | DOORWAY& LANDING, |
| | BLOCKS THE EXIT STAIRS. 1008.1.5. |
| | |
| | 25)LS-1 MEZZANINE ALTERNATING STAIR.1009.10 |
| | ALTERNATING TREAD DEVICES. |
| | ALTERNATING TREAD DEVICES ARE LIMITED TO AN ELEMENT OF |
| | A MEANS OF EGRESS |
| | IN BUILDINGS OF GROUPS F, H AND S FROM A MEZZANINE NOT |
| | MORE THAN 250 |
| | SQUARE FEET (23 M 2 ) IN AREA AND WHICH SERVES NOT MORE |
| | THAN THREE |
| | OCCUPANTS; IN BUILDINGS OF GROUP I-3 FROM A GUARD |
| | TOWER, OBSERVATION |
| | STATION OR CONTROL ROOM NOT MORE THAN 250 SQUARE FEET |
| | (23 M 2 ) IN AREA |
| | AND FOR ACCESS TO UNOCCUPIED ROOFS. |
| | |
| | 26)LS-1 HALLWAY# 122 IS TO BE A 1 HR RATED CORRIDOR |
| | TABLE 1016.1. PLEASE |
| | PROVIDE THE ASSEMBLY FOR THE WOOD FLOOR, WALLS & |
| | CEILING. |
| | |
| | 27)LS-1 NORTHEAST CORNER OF THE BUILDING A WOMENS |
| | RESTROOM, NOT IDENTIFIED |
| | HAS A INSWING DOOR. THIS DOOR SWINGS INTO THE REQUIRED |
| | CLEAR FLOOR SPACE |
| | REQUIRED FOR FIXTURES.11-4.22.2 DOORS. ALL DOORS |
| | TO ACCESSIBLE |
| | TOLIET ROOMS SHALL COMPLYWITH 11-4.13. DOORS SHALL |
| | NOT SWING INTO |
| | CLEAR FLOOR SPACE REQUIRED FOR ANY FIXTURE. |
| | |
| | 28)LS-1 DOOR # 117 MISSING THE 18" CLEARENCE LATCH |
| | SIDE OF DOOR. |
| | 11-4.13.6 MANEUVERING CLEARENCES |
| | AT DOORS. MINIMUM MANEUVERING CLEARANCES |
| | AT DOORS THAT ARE NOT AUTOMATIC OR |
| | POWER-ASSISTED SHALL BE AS SHOWN IN |
| | FIG. 25. THE FLOOR OR GROUND AREA WITH |
| | IN THE REQUIRED CLEARANCES SHALL BE |
| | CLEAR & LEVEL. |
| | |
| | 29) LS-1 PROPOSED COFFEE SHOP, WILL THE PATRONS BE ABLE |
| | TO GO INSIDE OR JUST UP TO THE WINDOW? |
| | PLANS DO NOT PROVIDE THE SILL HEIGHT?11-5.2 COUNTERS |
| | AND BARS. |
| | WHERE FOOD OR DRINK IS SERVED AT COUNTERS EXCEEDING 34 |
| | INCHES (865 MM) IN HEIGHT FOR CONSUMPTION BY CUSTOMERS |
| | SEATED ON STOOLS OR STANDING AT THE COUNTER, A PORTION |
| | OF THE MAIN COUNTER WHICH IS 60 INCHES (1525 MM) IN |
| | LENGTH MINIMUM SHALL BE PROVIDED IN COMPLIANCE WITH |
| | SECTION 11-4.32 OR SERVICE SHALL BE AVAILABLE AT |
| | ACCESSIBLE TABLES WITHIN THE SAME AREA. |
| | |
| | 30) ON THE INTERIOR SIDE OF THE COFFEE SHOP THERE IS A |
| | 6" DIFFERENCE IN GRADE, HOW WILL VERTICAL ACCESSIBILITY |
| | BE ACCOMPLISHED? |
| | 11-4.1.6(K)(III) |
| | |
| | 31) A-1, PROPOSED 2ND FLOOR SHOWS NO MEANS OF |
| | EGRESS,TO |
| | THE LOFT OR MEZZANINE LEVEL . PLANAS DO NOT INDICATE IF |
| | THIS IS EXISTING OR NEW WORK. |
| | PLANS DO NOT PROVIDE IF THIS STORAGE AREA IS DESIGNED |
| | AS LIGHT 125 PSF OR HEAVY 250PSF? |
| | |
| | 32) SHEET A-7 TICKET BOOTH INDICATES A SECTION 4/ A13 |
| | NO SUCH SECTION? PLEASE |
| | PROVIDE A SECTION THROUGH THE TICKET COUNTER INDICATE |
| | THE HEIGHT PLEASE? |
| | |
| | 33)SHEET A-8 OVERHEAD DOOR DETAIL, PLANS INDICATE |
| | THIS IS TO BE A 2HR RATED WALL , |
| | HOW WILL THIS UNIT MAKE THE RATING? AGAIN THIS IS OVER |
| | A EXIT ACCESS CORRIDOR. |
| | |
| | 34) 1609.1.4 PROTECTION OF OPENINGS. |
| | IN WIND-BORNE DEBRIS REGIONS, EXTERIOR |
| | GLAZING THAT RECEIVES POSITIVE PRESSURE |
| | IN THE LOWER 60 FEET (18.3 M) IN |
| | BUILDINGS SHALL BE ASSUMED TO BE |
| | OPENINGS AND THE BALANCE OF GLAZED |
| | OPENINGS IN THE REST OF THE BUILDING |
| | SHALL BE ASSUMED TO BE ZERO UNLESS SUCH |
| | GLAZING THAT RECEIVES POSITIVE PRESSURE |
| | IS IMPACT RESISTANT OR PROTECTED WITH AN |
| | IMPACT RESISTANT COVERING MEETING THE |
| | REQUIREMENTS OF SSTD 12, ASTM E 1886 AND |
| | ASTM E 1996, OR MIAMI-DADE TAS 201, 202 |
| | AND 203 REFERENCED THEREIN AS FOLLOWS: |
| | 1.GLAZED OPENINGS LOCATED WITHIN 30 |
| | FEET (9.1 M) OF GRADE SHALL MEET THE |
| | REQUIREMENTS OF THE LARGE MISSILE TEST. |
| | 2.GLAZED OPENINGS LOCATED MORE THAN |
| | 30 FEET (9.1 M) ABOVE GRADE SHALL MEET |
| | THE PROVISIONS OF THE SMALL MISSILE |
| | TEST. |
| | |
| | 35A)PRODUCT APPROVALS SUBMITTED WITH |
| | PERMIT APPLICATION AFTER OCTOBER 1, 2003 |
| | ARE REQUIRED TO COMPLY WITH THE FLORIDA |
| | PRODUCT APPROVAL SYSTEM. FOR INFORMATION |
| | PLEASE SEE THE STATE WEBSITE AT |
| | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH |
| | STATEWIDE APPROVAL ARE REQUIRED TO BE |
| | SUBMITTED WITH A COVER SHEET THAT LISTS |
| | THE PRODUCT IDENTITY NUMBER FROM THE |
| | STATE. IF THE PRODUCT DOES NOT HAVE |
| | STATEWIDE APPROVAL, SUBMIT AN APPLICA- |
| | TION FOR LOCAL PRODUCT APPROVAL OR SITE |
| | SPECIFIC FORM PER RULE 9B-72. SEE |
| | ATTACHMENT. WWW.FLORIDABUILDING.ORG |
| | |
| | 35B) FL BLD CODE 1609.1.4: COMPONENTS & CLADDING, |
| | PROVIDE 2 COPIES(3 IF THRESH- |
| | OLD OR RESIDENT INSPECTOR) OF PRODUCT |
| | TESTING REPORTS,MISSING REPORTS ARE AS |
| | FOLLOWS: |
| | A) WINDOWS : YKK AP"YHS"MISSING FLORIDA COVER |
| | SHEET AND ONLY THE FRONT PAGE OF NOA SUBMITTED.B) |
| | DOORS: YKK AP"35H" MISSING THE FLORIDA COVER SHEET |
| | PLUS THE TECHNICAL DRAWINGS. |
| | C)DOORS : NANA WALL SYSTEM - CREATE LOCAL APPROVAL |
| | ONCE THE |
| | TECHNICAL DRAWINGS ARE SUBMITTED IF PRESSURES ARE |
| | OK. |
| | D) DOORS FLEMING MISSING FLORIDA COVERSHEET AND |
| | REPORTS. |
| | E) ROLL UP DOOR: WAYNE DALTON HIGHLIGHT WHICH DOOR OR |
| | SYSTEM |
| | THAT WILL BE USED. |
| | F) ROOFING ASSEMBLIES: JPS ELASTOMERICS) THIS ROOF |
| | IS MISSING OR NOT IN |
| | COMPLIANCE WITH THE FOLLOW ITEMS: |
| | _X__ CONTRACTOR DID NOT PROVIDE THE MEAN |
| | ROOF HEIGHT. |
| | |
| | X___ CONTRACTOR DID NOT INDICATE THE ROOF |
| | PITCH. |
| | |
| | _X__ CONTRACTOR FAILED TO INDICATE WHICH |
| | SYSTEM TO BE USED. |
| | CONTRACTOR FAILED TO SUBMIT THE NOAPLUS |
| | FAILED TO INDICATE WHICH SUBSYSTEM IS TO BE USED._X__ |
| | THE SYSTEM PROVIDED HAS A LOW |
| | PRESSURE FOR ZONE ___ . |
| | |
| | _X__THE SYSTEM PROVIDED STATES |
| | LIMITATION# 7, SHOULD THE FASTENER |
| | RESISTANCE BE LESS THAN THAT |
| | REQUIRED, AS DETERMINED BY THE |
| | BUILDING OFFICIAL, A REVISED |
| | FASTENER SPACING, PREPARED , SIGNED |
| | AND SEALED BY A FLORIDA REGISTERED |
| | PROFESSIONAL ENGINEER, REGISTERED |
| | ARCHITECT OR REGISTERED ROOF |
| | CONSULTANT MAY BE SUBMITTED. |
| | |
| | ___THE SYSTEM PROVIDED INDICATES |
| | LIMITATION# 9, NO ENHANCED |
| | FASTENING ALLOWED. |
| | |
| | 36)BEFORE A PERMIT TO CONSTRUCT, MAY |
| | BE ISSUED, IMPACT FEES MUST BE PAID TO |
| | PALM BEACH COUNTY. THE ACTUAL PERMIT |
| | SET OF PLANS MUST BE STAMPED BY THAT |
| | OFFICE, AND A COPY OF THE PAID RECEIPT |
| | ATTACHED TO THE PERMIT APPLICATION. |
| | PLEASE CALL (561)233-5025 FOR MORE |
| | INFORMATION. |
| | |
| | BUILDING PLAN REVIEW |