| Notes |
| Date |
Text |
| 2006-09-18 00:00:00 | *** DENIED *** | | | 1) MANUAL J CAL'S ARE CALLING FOR 23,867 | | | SENSIBLE BTU'S, THE PLANS ARE CALLING | | | FOR 35,000 SENSIBLE BTU'S, THE PLANS CAN | | | ONLY CALL FOR 20% MORE THAN THE MANUAL J | | | CAL'S, PER 2005 FBC CH. 13 | | | 607.1.ABC.1.1, PLEASE CORRECT. | | | | | | 2) PLEASE SUBMIT A SIGNED PROPOSAL OR | | | AJUST THE VALUE ON THE PERMIT | | | APPLICATION, AS THE VALUE ON THE PERMIT | | | APPLICATION APPEARS LOW FOR THE WORK TO | | | BE DONE, OR THE CITY WPB WILL AJUST THE | | | VALUE USING MARSHALL & SWIFT ESTIMATOR, | | | PER 2004 CITY WPB AMEND. 108.3 . | | | | | | 3) ALL INFORMATION, DRAWINGS, | | | SPECIFICATIONS AND ACCOMPANYING DATA | | | SHALL BEAR THE NAME AND SIGNATURE OF THE | | | PERSON RESPONSIBLE FOR THE DESIGN. PER | | | FBC 104.2.1 . | | | | | | 4) PLEASE ARRANGE FOR PERMIT # 06071027 | | | TO BE VOIDED. | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729. |
|