Plan Review Notes
Plan Review Notes For Permit 06090569
Permit Number 06090569
Review Stop P
Sequence Number 1
Notes
Date Text
2006-09-27 00:00:00DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FLORIDA ADMINISTRATIVE CODE
  
 1. SHT A101 PER FAC 61G1-16.004(2) THE
 FIRM LICENSE NUMBER IS REQUIRED IN THE
 TITLE BLOCK. ARCHITECTS LICENSE NUMBER
 IS SHOWN. NO LICENSE NUMBER FOR EDRC
 ARCHITECTS. FS 481.219.
  
 2. THE SANITARY SYSTEM IS AN ENGINEERED
 SYSTEM, (SOVENT). CHANGE TO AN
 ENGINEERED SYSTEM SHALL BE SUBMITTED BY
 AN ENGINEER AND EXISTING RISERS SHALL BE
 SHOWN, WITH CHANGES INDICATED. SHOW ALL
 PIPE SIZES AND VENTING IF REQUIRED.
 SECTION 106.3.5.1.3.
  
 3. SUBMIT A WATER RISER DIAGRAM
 ISOMETRIC SHOWING ALL PIPE SIZES,
 VALVES, AND WATER HAMMER ARRESTORS
 REQUIRED BY SECTION 604.9. WATER HAMMER
 ARRESTORS SHALL BE LOCATED NEAR THE
 FIXTURE IN AN, "EFFECTIVE RANGE", NOT IN
 THE CEILING. WH-PDI 201 AND MANUF.
 INSTALLATION INSTRUCTIONS.
  
 4. SHT A101 STAFF TOILET PLUMBING PLAN
 SHOWS 1-1/2" SANT. PIPING TO THE WASH
 MACHINE. PER TABLE 709.1, MINIMUM 2"
 TRAP IS REQUIRED.
  
 5. SUBMIT MANUF. SPECIFICATIONS FOR THE
 LAV AND THE W/C. PER FIGURE 405.3.1 THE
 MINIMUM CLEARNACE BETWEEN THE W/C AND
 THE LAV IS 21". PLANS INDICATE 57-1/4"
 OPENING IN ROOM AND SCALES OUT LESS THAN
 REQUIRED CLEARANCE. SECTION 106.1.1.
  
 REVIEW BY KEN STEVENS