| Date |
Text |
| 2006-09-27 00:00:00 | ******DENIED****** | | | REFERENCE: FBC-2004 SEC. 424.2 OR | | | FBRC-2003 SEC. 4101 SWIMMING POOLS | | | | | | THE FOLLOWING INFORMATION IS REQUIRED | | | FOR PLUMBING PLAN REVIEW: | | | | | | 1) FBC-2004 SEC. 424.2.14.1, OR | | | FBCR-2004 SEC. R4101.14.1 SWIMMING POOL | | | WATER HEATERS SHALL BEAR THE LABEL OF A | | | RECOGNIZED TESTING AGENCY. (MANUFACTURE | | | SHEETS REQUIRED, PLEASE SUBMIT) | | | | | | 2) FBC-2004 SEC. 424.2.14.2, OR | | | FBCR-2004 SEC. R4101.14.2 WATER | | | RETENTION, PROVIDE A POSITIVE MEANS OF | | | RETAINING WATER IN THE HEATER WHEN PUMP | | | IS SHUT OFF.(MANUFACTURE SHEETS | | | REQUIRED, PLEASE SUBMIT) | | | | | | 3) FBC-2004 SEC. 424.2.6.6.5, OR | | | FBCR-2004 SEC. R4101.6.6.5 WHERE | | | PROVIDED, THE VACUUM OR PRESSURE CLEANER | | | FITTING SHALL BE LOCATED AT LEAST 6" AND | | | NOT GREATER THAN 12" BELOW THE MINIMUM | | | OPERATING WATER LEVEL OR AS AN | | | ATTACHMENT TO THE SKIMMER.(MANUFACTURE | | | SHEETS REQUIRED OR ADD MAKE AND MODEL | | | NUMBER TO NOTES) | | | | | | END OF COMMENTS: | | | | | | REVIEW BY MIKE PERSON | | | (561) 805-6730 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] | | | UNDER SUPERVISION OF K.STEVENS | | | (561) 805-6721 | | | | | | | | | | | | |
|