2006-10-13 16:26:00BUILDING PLAN REVIEW
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW 1ST
 ACTION: DENIED
  
 1) 2107.2.3 ACI 530/ASCE 5/TMS 402, SECTION
 2.1.10.6.1.1, LAP SPLICES .
 THE MINIMUM LENGTH OF LAP SPLICES FOR REINFORCING BARS
 IN TENSION OR COMPRESSION, L L D , SHALL BE CALCULATED
 BY EQUATION 21-2, BUT SHALL NOT BE LESS THAN 15 INCHES
 (380 MM).INDICATE THE EMBEDMENT DIMENTION OF THE
 JDOWELS AND THE LAP SPLICES.SHOW THE AREA OF THE NEW
 SITE WALL ON THE PLANS.
  
 2) THE CLAIMED VALUATION ON THE PERMIT APPLICATION IS
 LOW. FOR PERMITTING PURPOSES, VALUATION OF BUILDINGS
 AND SYSTEMS SHALL BE THE TOTAL REPLACEMENT COST
 EXCLUDING LAND VALUE. OUR VALUATION REFERENCE IS ICC
 (BVD), MARSHALL-SWIFT AND MEANS COST ANALYSIS SERVICES
 PER 108.3 FBC*.
  
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 TEL:(561)805-6726
  