| 2006-09-25 00:00:00 | *****UNSAT***** |
| | |
| | |
| | |
| | |
| | |
| | 1.) THE PERMIT AND PLANS SHOULD REFLECT |
| | THE LOCALE WHERE THE ACTUAL WORK IS |
| | BEING DONE; WHICH IS 307 EVERNIA STREET |
| | NOT 310 EVERNIA STREET. |
| | |
| | 2.) SINCE THE CONTRACT IS GREATER THAN |
| | $2500.00, THE APPLICANT SHALL FILE WITH |
| | THE AHJ EITHER A RECORDED NOTICE OF |
| | COMMENCEMENT OR A NOTORIZED STATEMENT |
| | THAT THE NOTICE HAS BEEN FILED FOR |
| | RECORDING, ALONG WITH A COPY THEREOF. |
| | |
| | 3.) SINCE THE SCOPE OF THE WORK IS |
| | GREATER THAN $5,000.00, AS PER FLORIDA ADMINISTRATIVE |
| | CODES, A PROFESSIONAL |
| | ENGINEER SHALL SIGN HIS SEAL TO ALL |
| | PLANS, SPECIFICATIONS, ETC TO BE FILED |
| | FOR PUBLIC RECORD. THE STAMPED |
| | ENGINEERED SEAL SHALL HAVE THE WORDING |
| | "LICENSE" IN LIEU OF "CERTICATE". |
| | |
| | 4.) FIRE ALARM SYSTEM TO BE FULLY |
| | ADDRESSABLE. |
| | |
| | 5.) DUCT SMOKE DETECTORS SHALL INITIATE |
| | A GENERAL ALARM. |
| | |
| | 6.) FIRE ALARM SYSTEM IN CONJUNCTION |
| | WITH FIRE SPRINKLER SYSTEM TO BE |
| | MONITORED. |
| | |
| | 7.) WATERFLOW TO ACTIVATE GENERAL FIRE |
| | ALARM WITHIN 45 TO 60 SECONDS. |
| | |
| | 8.) FIRE ALARM SYSTEM SHALL BE UL |
| | CERTIFIED FOR CENTRAL STATION. INSTALL |
| | UL CERTIFICATE AT THE FIRE ALARM CONTROL |
| | PANEL AND PROVIDE A COPY TO WPBFR BY |
| | FINAL FIRE ALARM INSPECTION. |
| | |
| | |
| | |
| | |
| | |
| | |
| | |