| Plan Review Notes For Permit 06090457 |
| Permit Number |
06090457 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2006-09-18 00:00:00 | *** DENIED *** | | | 1) AS NOTED FOR THE PAST THREE PERMITS | | | YOUR COMPANY APPLIED FOR, THE ENGINEER'S | | | LICENSE NUMBER MUST APPEAR IN THE TITLE | | | BLOCK, PER FAC 61G15-23.002 . | | | | | | 2) SEE PAGE 5-5 ROOF CURB DETAILS (WIND | | | LOADS OF 120 MPH, NEEDS TO BE 140 MPH, | | | PER 2004 FBC 1609. | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729. |
|