| 2007-03-09 08:01:37 | DENIED |
| | REFERENCE: FBC-2004 PLUMBING |
| | FBC-2004 BUILDING |
| | FBC-2004 CHAPTER 1 |
| | FBC-2004 CHAPTER 11 |
| | FLORIDA ADMINISTRATIVE CODE FLORIDA |
| | STATUTES |
| | NFPA 99C 2002 |
| | |
| | FROM PREVIOUS REVIEW: |
| | |
| | 1. OK |
| | 2. OK |
| | 3. OK |
| | 4. OK |
| | 5. OK |
| | 6. OK |
| | 7. OK |
| | 8. OK |
| | |
| | 9. SHT P.2 PLUMBING LEGEND #2 AND DETAIL #3 WATER |
| | FILTER SYSTEM. FILTER SHALL COMPLY WITH NSF 42. SUBMIT |
| | MANUF. SPECIFICATION. SECTION 611.1. |
| | ****NO RESPONSE - NOT ADDRESSED. |
| | ******RESPONSE NOTED, AND INDICATES THE FILTERED WATER |
| | SYSTEM HAS BEEN DELETED, BUT THE PLANS STILL SHOW |
| | "FILTERED C.W. TYP. BRANCH"ON THE VAC. AIR & FILTERED |
| | WATER DIAGRAM. PLEASE CLARIFY. SECTION 106.1.1. |
| | |
| | 10. SUBMIT RISER ISOMETRICS FOR THE FOLLOWING. THE |
| | WATER SYSTEM, SHOWING ALL PIPE SIZES, VALVES, AND WATER |
| | HAMMER ARRESTORS REQUIRE BY SECTION 604.9. THE VACUUM |
| | SYSTEM SHOWING ALL PIPE SIZES, VALVES, ETC. THE |
| | COMPRESSED AIR SYSTEM, SHOWING ALL PIPE SIZES, VALVES |
| | ETC. SECTION 106.3.5.1.3, AND FIGURES 4.5.2.1.3(A) OR |
| | 4.5.2.1.3(B) FOR THE VACUUM SYSTEM. |
| | ****RESPONSE NOTED, BUT ALL PIPE SIZES ARE NOT SHOWN, |
| | AND THE FULL OPEN VALVES ON ALL WATER DOWN-FEED LINES |
| | REQUIRED BY SECTION 606.1(4) ARE NOT SHOWN ON THE WATER |
| | RISER ISOMETRIC. |
| | ******RESPONSE NOTED, BUT THE WATER HAMMER ARRESTORS |
| | SHALL BE LOCATED IN AN "EFFECTIVE RANGE" NEAR THE |
| | FIXTURES, NOT IN THE CEILING. PDI-WH 201 & MANUF. |
| | INSTALLATION INSTRUCTIONS. |
| | |
| | 11. OK |
| | 12. OK |
| | 13. OK |
| | 14. OK |
| | 15. OK |
| | |
| | *************NEW COMMENT************* |
| | |
| | 1B. OK |
| | |
| | |
| | REVIEW BY KEN STEVENS |