| Date |
Text |
| 2007-01-10 07:23:35 | DENIED |
| | REFERENCE: FBC-2004 PLUMBING |
| | FBC-2004 BUILDING |
| | FBC-2004 CHAPTER 1 |
| | FBC-2004 CHAPTER 11 |
| | FLORIDA ADMINISTRATIVE CODE FLORIDA |
| | STATUTES |
| | NFPA 99C 2002 |
| | |
| | FROM PREVIOUS REVIEW: |
| | |
| | 1. OK |
| | 2. OK |
| | 3. OK |
| | |
| | 4. SHT A.1 TOILET ROOM 115 ADAPTABLE RESTROOM. SHOW THE |
| | W/C TO BE 1'6" OFF THE WALL TO THE CENTERLINE OF THE |
| | FIXTURE. FIGURE 28.SHOW A 5' TURNING AREA PER SECTION |
| | 11-4.22.3. |
| | ****RESPONSE NOTED, BUT THE DOOR SWING SHALL SWING OUT |
| | OF THE TOILET ROOM FOR THE ROOM TO BE ADAPTABLE. |
| | |
| | 5. SHT A.1 FINISH SCHEDULE. INDICATE HOW PAINTED GWB |
| | MEETS THE REQUIREMENTS OF A "SMOOTH, HARD, NONABSORBENT |
| | SURFACE" AS REQUIRED IN SECTION 1210.2. TOILET ROOMS |
| | 104 & 111. |
| | ****RESPONSE NOTED, BUT EPOXY PAINT DOES NOT COMPLY |
| | WITH THE REQUIREMENT FOR A HARD SURFACE. |
| | |
| | 6. SHT A.4 DETAIL 9/A.4 SECTION REQUIRES A KNEE |
| | CLEARANCE THAT IS 27" HIGH, 30" WIDE, AND 19" DEEP |
| | SHALL BE PROVIDED UNDERNEATH THE SINKS. UNDERLAVATORY |
| | ENCLOSURE IS NOT APPROVED. DELETE FROM THE DETAIL. SHOW |
| | COMPLIANCE WITH THE FOLLOWING: |
| | A. OK |
| | B. OK |
| | C. 11-4.24.6 EXPOSED PIPES & SURFACES - NOT |
| | ADDRESSED. |
| | D. OK |
| | |
| | 7. OK |
| | 8. OK |
| | |
| | 9. SHT P.2 PLUMBING LEGEND #2 AND DETAIL #3 WATER |
| | FILTER SYSTEM. FILTER SHALL COMPLY WITH NSF 42. SUBMIT |
| | MANUF. SPECIFICATION. SECTION 611.1. |
| | ****NO RESPONSE - NOT ADDRESSED. |
| | |
| | 10. SUBMIT RISER ISOMETRICS FOR THE FOLLOWING. THE |
| | WATER SYSTEM, SHOWING ALL PIPE SIZES, VALVES, AND WATER |
| | HAMMER ARRESTORS REQUIRE BY SECTION 604.9. THE VACUUM |
| | SYSTEM SHOWING ALL PIPE SIZES, VALVES, ETC. THE |
| | COMPRESSED AIR SYSTEM, SHOWING ALL PIPE SIZES, VALVES |
| | ETC. SECTION 106.3.5.1.3, AND FIGURES 4.5.2.1.3(A) OR |
| | 4.5.2.1.3(B) FOR THE VACUUM SYSTEM. |
| | ****RESPONSE NOTED, BUT ALL PIPE SIZES ARE NOT SHOWN, |
| | AND THE FULL OPEN VALVES ON ALL WATER DOWN-FEED LINES |
| | REQUIRED BY SECTION 606.1(4) ARE NOT SHOWN ON THE WATER |
| | RISER ISOMETRIC. |
| | |
| | 11. OK |
| | 12. OK |
| | 13. OK |
| | 14. OK |
| | 15. A SEPARATE MED-GAS PERMIT IS REQUIRED FOR THE |
| | VACUUM AND COMPRESSED AIR SYSTEMS. CERTIFICATION FOR |
| | THE CONTRACTOR, INSTALLER AND/OR BRAZER WITH PICTURE |
| | IDENTIFICATION IS REQUIRED AT THE TIME OF APPLICATION. |
| | (INFORMATIONAL ONLY). |
| | |
| | *************NEW COMMENT************* |
| | |
| | 1B. THE PERSONAL SIGNATURE OF THE ARCHITECT SHALL |
| | APPEAR ON ALL ARCHITECTURAL DOCUMENTS. 61G1-16.003 & FS |
| | 481.2055. THE SEAL IS STAMPED WITH A SIGNATURE STAMP. |
| | THIS IS NOT APPROVED. PLEASE SIGN EACH SHEET. |
| | |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 805-6721 |
| | FAX (561) 805-6731 |
| | E-MAIL [email protected] |