| 2006-09-30 00:00:00 | *** UNSAT *** |
| | |
| | 1) NOTE: PLEASE SEE FAC 61G1-16.004, |
| | WHICH REQUIRES THE PRINTED NAME OF THE |
| | ARCHITECT ON TITLE BLOCKS. |
| | PLEASE ALSO SEE THAT THE RAISED SEALS |
| | MUST BE CLEAR AND VISABLE WITH ALL |
| | INFORMATION AS REQUIRED ON SAID SEAL. |
| | PLEASE SEE SEALS ARE NOT EASILY |
| | READABLE. |
| | FS 481.221, FAC 61G1-16.003 |
| | ** THIS IS REQUIRED FOR ALL SHEETS AND |
| | FOR ALL TRADES WHETHER OR NOT COMMENT IS |
| | MADE BY OTHER REVIEWER(S). |
| | |
| | 2) NOTE: PLEASE SEE THE FOLLOWING MIN |
| | CODES SHALL BE STATED ON PLANS. IMPLY |
| | STATING THE "LATEST EDITION" CAN NOT BE |
| | USED AS THE LATEST EDITIONS OF SOME |
| | CODES ARE OUT AND AVAILABLE YET NOT YET |
| | ADOPTED BY THE STATE. |
| | PLEASE STATE THE FOLLOWING. |
| | 2002 NFPA-70 (NEC), 2002 NFPA-72, 2003 |
| | NFPA-101, 2004 FBC. |
| | PLEASE KNOW, OTHER CODES RELEVANT MAY BE |
| | REQUESTED BY OTHER REVIEWER(S). |
| | |
| | 3) NOTE: PLEASE SEE THAT NEC 517, 517.13 |
| | DETAIL IS SHOWN ON PLANS. |
| | PLEASE SEE NOTE BELOW RISER DENOTING |
| | GROUND BOND PER NEC MAY NOT USED IN LEIU |
| | OF DETAIL REQUIRED. |
| | FBC 106.1.2 ADMIN SECT AS ADOPTED BY THE |
| | CITY OF WEST PALM BEACH. |
| | |
| | 4) NOTE: PLEASE SEE FBC CHAPTER 13, 13-415.1.ABC.1.1, |
| | .1.2 AND .1.3. |
| | PLEASE PROVIDE LIGHTING CONTROL(S), |
| | STATED DEVICES, LOCATIONS OF OVER RIDES |
| | AND EVICES. PLEASE INDICATE THE MAX |
| | TIMES ON OVER RIDES. (FYI, TIMER TYPE |
| | 4HRS MAX, OCCUPANT TYPE 30MINS MAX). |
| | PLEASE INDICATE THE MAX LPD(LIGHTING |
| | POWER DENSITIES). PER 13-415.2.ABC.1, |
| | TABLES 415. |
| | |
| | 5) NOTE: PLEASE INDICATE ALL ROOM/AREAS DESIGNATIONS ON |
| | PLANS AND CORRELATE |
| | PANEL SCHEDULE WHICH IS TO BE SPECIFIC |
| | TO AREAS BEING FED. |
| | 408.4, |
| | |
| | 6) NOTE: PLEASE PROVIDE EITHER NEW OR |
| | EXISTING SIGN CIRCUIT LOCATION PER |
| | 600.5. IT IS UNCLEAR AT THIS TIME. |
| | |
| | 7) NOTE: PLEASE SEE RISER SHOW THE MAIN |
| | PANEL IN SPACE AS 400 MCB. PLEASE SEE |
| | THIS APPEARS TO BE A MISPRINT AS THE |
| | SCHEDULE AND SERVICE PROVIDED MENTIONS |
| | 300A. |
| | POSSIBLE, 400MLO/300MCB. |
| | FBC 106.1.2 ADMIN SECT. |
| | |
| | 8) NOTE: PLEASE INDICATE IF PANEL "A" |
| | CONTAINS "FEED-THRU" LUGS OR IS THERE |
| | OCP WHICH FEEDS PANEL"A-1'.?? |
| | |
| | 9) NOTE: PLEASE INDICATE WHERE THE |
| | CONNECTED LOADS ARE BEIGN DERIVED. |
| | PLEASE INDICATE A LOAD SUMMARY FOR |
| | SPACE. PLEASE ALSO INDICATE ALL |
| | CONTINUOUS LOADS AT 125% (3OR MORE HRS). |
| | 220.3,220.10,220.11,220.13,215.3, 230.42 |
| | ETC. |
| | |
| | 10) NOTE: PLEASE INDICATE "EQUIPMENT |
| | GROUNDING" METHOD FROM MAIN MDP TO ALL |
| | EQUIPMENT. |
| | 250.110, 250.122. |
| | ** PLEASE KNOW, IF USINGCONDUIT, THERE |
| | MUST BE THE NEW CONNECTORS WHICH MUST BE |
| | LSTED FOR THIS PURPOSE, OTHERWISE PLEASE |
| | INDICATE THE "EQUIPMENT GROUNDING |
| | CONDUCTOR" PER 250.122. |
| | |
| | 11) NOTE; PLEASE SEE PANEL "A-1" |
| | INDICATES 30POLES, YET SHOWS 42 |
| | CIRCUITS/POLES ARE SHOWN ON PANEL.. |
| | PLEASE CORRELATE AND ADJUST. |
| | 106.1.2 FBC. |
| | |
| | 12) NOTE; PLEASE PROVIDE THE AIC RATING |
| | FOR THE NEW MB FROM MDP TO NEW TENANT |
| | SPACE. |
| | PLEASE ALSO SEE THE AIC RATING FOR EACH |
| | OF THE TENANT PANELS IS BEING SHOWN AT |
| | 22K, WHICH SEEMS HIGH FOR BRANCH BRKRS?? |
| | ** THIS IS OK, HOWEVER PLEASE KNOW, IF |
| | SHOWN, THEN 22K RATED BRNACH BRKRS WILL |
| | BE REQUIRED. |
| | 110.9, |
| | FBC 106.1.2 ADMIN SECT. |
| | 106.3.5.1.2 |
| | |
| | ** PLEASE SEE ANY COMMENTS FROM OTHER |
| | TRADES WHICH MAY AFFECT THE ELECTRICAL PLANS/DEISGN. |
| | |
| | ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |