| Plan Review Notes For Permit 06090447 |
| Permit Number |
06090447 |
|
| Review Stop |
B |
| Sequence Number |
7 |
|
| Notes |
| Date |
Text |
| 2007-07-19 10:30:48 | REVISIONS TO SHEETS A1, A2, A3, A5, A6 ARE DENIED. | | | | | | 1) ON SHEET A1 THE WINDOW NOTES SPECIFY PGT WINDGUARD | | | WINDOWS. THE CONTRACTOR HAS REVISED THE WINDOW PRODUCT | | | APPROVALS TO IMPACT RATED KDWINDOWS. PLEASE REVISE. | | | | | | 2) THE WINDOWS SIZES SHOWN ON THE ELEVATIONS AND FLOOR | | | PLAN DO NOT CORRESPOND WITH THE DIMENSIONS IN THE | | | WINDOW SCHEDULE ON A1 FOR THE KITCHEN AND BATHROOM | | | WINDOWS. | | | | | | 3) PROVIDE A DETAIL OF THE IN FILL FRAMING AT THE | | | BATHROOMWINDOWS. | | | | | | 4) THE REAR ELEVATION ON A3 HAS THE WRONG DETAIL TAG | | | FOR THE IN FILL FRAMING. IT SHOULD BE 1 ON A6. | | | | | | 5) THE OPENING WIDTH DIMENSION IN DETAIL 1 ON A5 IS TOO | | | SMALL FOR THE WINDOWS SPECIFIED IN THE SCHEDULE ON A1. | | | PLEASE REVISE. | | | | | | 6) THE OPENING WIDTH DIMENSION IN DETAIL 1 ON A6 IS TOO | | | SMALL FOR THE WINDOWS SPECIFIED IN THE SCHEDULE ON A1. | | | PLEASE REVISE. | | | | | | - ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 |
|