Plan Review Notes
Plan Review Notes For Permit 06090447
Permit Number 06090447
Review Stop B
Sequence Number 7
Notes
Date Text
2007-07-19 10:30:48REVISIONS TO SHEETS A1, A2, A3, A5, A6 ARE DENIED.
  
 1) ON SHEET A1 THE WINDOW NOTES SPECIFY PGT WINDGUARD
 WINDOWS. THE CONTRACTOR HAS REVISED THE WINDOW PRODUCT
 APPROVALS TO IMPACT RATED KDWINDOWS. PLEASE REVISE.
  
 2) THE WINDOWS SIZES SHOWN ON THE ELEVATIONS AND FLOOR
 PLAN DO NOT CORRESPOND WITH THE DIMENSIONS IN THE
 WINDOW SCHEDULE ON A1 FOR THE KITCHEN AND BATHROOM
 WINDOWS.
  
 3) PROVIDE A DETAIL OF THE IN FILL FRAMING AT THE
 BATHROOMWINDOWS.
  
 4) THE REAR ELEVATION ON A3 HAS THE WRONG DETAIL TAG
 FOR THE IN FILL FRAMING. IT SHOULD BE 1 ON A6.
  
 5) THE OPENING WIDTH DIMENSION IN DETAIL 1 ON A5 IS TOO
 SMALL FOR THE WINDOWS SPECIFIED IN THE SCHEDULE ON A1.
 PLEASE REVISE.
  
 6) THE OPENING WIDTH DIMENSION IN DETAIL 1 ON A6 IS TOO
 SMALL FOR THE WINDOWS SPECIFIED IN THE SCHEDULE ON A1.
 PLEASE REVISE.
  
 - ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714