Plan Review Notes
Plan Review Notes For Permit 06090447
Permit Number 06090447
Review Stop E
Sequence Number 5
Notes
Date Text
2007-06-27 13:30:58 
  
 REVISION DENIED
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE
 COMPLIANCE AND RESUBMIT FOR REVIEW.
  
 1} THE CONDUIT FOR THE SERVICE RISER DOES NOT COMPLY
 WITH TABLE C-8 FOR FILL REQUIREMENT, THIS WAS REDLINED
 ON THE PREVIOUS REVIEW, PLEASE CORRECT ON THE PLAN.
 SHEET E-2.
  
 2} VERIVY CIRCUIT #3 ON THE PANEL SCHEDULE, 20 AMP WITH
 #8 CONDUCTORS, LISTED A SPARE.
  
 3} CLOUD THE REVISIONS ON SHEETS E-3 AND E-4.
  
 4} RELOCATE THE RANGE AND WATER HEATER RECEPTACLES TO
 THEIR RELEVANT LOCATION, OR REMOVE IF NOT BEING
 INSTALLED.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]