| Plan Review Notes For Permit 06090447 |
| Permit Number |
06090447 |
|
| Review Stop |
E |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2007-01-03 18:08:26 | | | | NONCOMPLIANT. | | | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE | | | COMPLIANCE AND RESUBMIT FOR REVIEW. | | | | | | 1} THE PANELS ARE SHOWING THREE PHASE BUSSES (A,,B,C), | | | REMOVE "C". | | | | | | 2} THE #8 EQUIPMENT GROUND FROM THE METER TO THE HOUSE | | | PANEL IS IN VIOLATION OF 250.6 AND SHALL BE REMOVED. | | | THIS WILL BE INSTALLED AFTER THE DISCONNECT WHERE THE | | | NEUTRAL WILL BE ISOLATED FROM THE GROUND.. | | | | | | 3} THE DISHWASHER STILL APPEARS ON THE PLAN. ADD TO THE | | | CALCS OR REMOVE SAME, 220 | | | | | | 4} THE BATHROOM CIRCUIT IS LISTED AS 240 VOLTS IN THE | | | NOTES SHEET E-1 AND E-2. | | | | | | 5} THE WASHER/DRYER STACK UNITS ARE SHOWN ON THE PLAN | | | BUT NOT IN THE CALCS. SOME ARE 240 AND SOME ARE 120 | | | VOLT, PLEASE CORRELATE. | | | | | | 6} THE BATTERY PACK EMERGENCU LIGHTS MUST BE ON A LOCAL | | | CIRCUIT TO FUNCTION WHEN THAT CIRCUIT FAILS. SEE | | | 700.12(E) FOR VERBAGE. | | | | | | WILLIAM R. TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | 561/805-6718 |
|