| Plan Review Notes For Permit 06090447 |
| Permit Number |
06090447 |
|
| Review Stop |
P |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2006-11-17 08:28:01 | DENIED; | | | 1. AUTOMATIC CLOTHES WASHERS ARE NOT SHOWN ON FLOOR | | | PLAN. PAGES A-1 AND A-2 PLEASE ADD. | | | 2. AUTOMATIC CLOTHES WASHER BRANCH DRAIN IS REQUIRED TO | | | BE 3". SEE FBC-2004 PLUMBING SECTION 406.3. | | | 3. PLEASE SIZE ALL PIPES ON RISER DIAGRAM. | | | 4.ENGINEER TO SIGN NOT INITIAL PLANS. | | | 5. WATER RISER DIAGRAM PAGE P-2 WATER HAMMER ARRESTORS | | | ARE REQUIRED AT THE AUTOMATIC CLOTHES WASHERS. PLEASE | | | SHOW ON DRAWINGS. | | | PLUMBING PLAN REVIEW BY; | | | JOHN LEECH | | | 805-6695 |
|