2006-11-16 08:04:52DENIED BY BUILDING
  
 1)A RECORDED COPY OF THE NOTICE OF COMMENCEMENT
 MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) SPECIFY THE STUD SPACING IN THE WALL SECTION ON
 SHEET A-5.
  
 3) ASTM C926REQUIRES STUCCO APPLIED VERTICALLY OVER
 METAL LATH WITH A SOLID BASE TO HAVE A MINIMUM
 THICKNESS OF 7/8". SEE FBC 2510.3. PLEASE CORRECT WALL
 SECTION ON A-5.
  
 4)FBC 2510.6 REQUIRES A WEATHER RESISTANT BARRIER
 OVER THE PLYWOOD BACKING BEHIND THE LATH AND STUCCO.
 PLEASE SPECIFY ON WALL SECTION ON A-5.
  
 5) THE WINDOW SCHEDULE ON A-1 STILL HAS ERRORS. THERE
 ARE MASONRY OPENINGS SPECIFIED THAT ARE THE SAME SIZE
 OR SMALLER THAN THE WINDOW SIZES. THE SIZE CODE FOR
 CASEMENT WINDOWS D, O, V & GG ARE NOT CORRECT. PLEASE
 CORRECT.
  
 6) PLEASE SUBMIT PRODUCT APPROVALS ( APPROVED BY THE
 D.O.R.) FOR THE STRUCTURAL WINDOW MULLIONS.
  