| Plan Review Notes For Permit 06090447 |
| Permit Number |
06090447 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2006-09-22 00:00:00 | DENIED; | | | 1.NO FLOOR DRAINS SHOULD BE IN UNITS. | | | WATER HEATER ON 2ND FLOOR ARE REQUIRED | | | TO HAVE WATER HEATER PANS. FLOOR DRAINS | | | ARE NOT NEEDED. REMOVE FLOOR DRAINS. | | | 2.WATER HEATER DETAIL; | | | A) PAN DRAIN LINE TO BE A MIN. OF | | | 3/4" FBC-2004 EXISTING BUILDING | | | SEC.610.3 REFS. TO FBC PLUMBING | | | SEC.504.7.1 . | | | B)PRESSURE RELIEF VALVE CAN | | | TERMINATE IN THE WATER HEATER | | | PAN. PLEASE SHOW RELIEF DISCHARGE | | | AT 3/4" | | | PLUMBING PLAN REVIEW BY; | | | JOHN LEECH | | | 805-6695 |
|