Plan Review Notes
Plan Review Notes For Permit 06090447
Permit Number 06090447
Review Stop P
Sequence Number 1
Notes
Date Text
2006-09-22 00:00:00DENIED;
 1.NO FLOOR DRAINS SHOULD BE IN UNITS.
 WATER HEATER ON 2ND FLOOR ARE REQUIRED
 TO HAVE WATER HEATER PANS. FLOOR DRAINS
 ARE NOT NEEDED. REMOVE FLOOR DRAINS.
 2.WATER HEATER DETAIL;
 A) PAN DRAIN LINE TO BE A MIN. OF
 3/4" FBC-2004 EXISTING BUILDING
 SEC.610.3 REFS. TO FBC PLUMBING
 SEC.504.7.1 .
 B)PRESSURE RELIEF VALVE CAN
 TERMINATE IN THE WATER HEATER
 PAN. PLEASE SHOW RELIEF DISCHARGE
 AT 3/4"
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695