| Notes |
| Date |
Text |
| 2007-07-20 07:51:30 | REVISIONS TO SHEETS D1, A1, A2, A3 AND A5 ARE DENIED. | | | | | | 1) ON SHEET A1 THE WINDOW NOTES SPECIFY PGT WINDGUARD | | | WINDOWS. THE CONTRACTOR IS IN THE PROCESS OF CHANGING | | | THE WINDOW PRODUCT APPROVALS TO IMPACT RATED KD | | | WINDOWS. PLEASE REVISE. | | | | | | 2) THE WINDOWS SIZES SHOWN ON THE ELEVATIONS AND FLOOR | | | PLAN DO NOT CORRESPOND WITH THE DIMENSIONS IN THE | | | WINDOW SCHEDULE ON A1 FOR THE KITCHEN AND BATHROOM | | | WINDOWS. | | | | | | 3) PROVIDE A DETAIL OF THE IN FILL FRAMING AT THE | | | BATHROOMWINDOWS. | | | | | | 4) THE OPENING WIDTH DIMENSION IN DETAIL 1 ON A5 IS TOO | | | SMALL FOR THE WINDOWS SPECIFIED IN THE SCHEDULE ON A1. | | | PLEASE REVISE. | | | | | | - ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 |
|