| 2007-06-26 15:11:49 | REVISED PRODUCT APPROVALS FOR WINDOWS ARE DENIED | | | | | | 1) PLAN SHEET A-1 WILL BE REQUIRED TO BE REVISED TO | | | REFLECT THE CHANGES TO THE WINDOW TYPES THAT ARE NOT | | | INDICATED IN THE WINDOW SCHEDULE. | | | | | | 2)WPB ADMIN CODE 106.3* PRODUCT | | | APPROVALS. THOSE PRODUCT WHICH ARE | | | REGULATED BY DCA RULE 9B-72 SHALL BE | | | REVIEWED AND APPROVED IN WRITING BY THE | | | DESIGNER OF RECORD PRIOR TO SUBMITTAL | | | FOR JURISDICTIONAL APPROVAL. | | | | | | 3) THE PRODUCT APPROVAL FOR THE SERIES 455 IS MISSING | | | PAGES E-1 AND E-2. | | | | | | 4) THE PRODUCT APPROVALS SUBMITTED FOR THE MULLIONS AND | | | CASEMENT WINDOWS DO NOT COMPLY WITH THE 2004 FBC FOR | | | NOT ALLOWING A 1/3 STRESS INCREASE OF STEEL FASTENERS, | | | BUT HAVE REVISED NOAS THAT DO COMPLY. SUBMIT THE LATEST | | | NOAS. | | | | | | 5) THE PRODUCT APPROVALS FOR THE FIXED WINDOW AND THE | | | SINGLE HUNG WINDOW DO NOT COMPLY WITH THE 2004 FBC FOR | | | THE REASON STATED ABOVE. | | | | | | 6) ADDITIONAL FEES ARE DUE. 5 PRODUCT APPROVALS WERE | | | SUBMITTED AND THE FEE WAS ASSESSED FOR ONE. AN | | | ADDITIONAL $40.00 IS DUE. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | |
|