2007-06-29 13:41:27 
  
  
 REVISION DENIED
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE
 COMPLIANCE AND RESUBMIT FOR REVIEW.
  
 1} THE CONDUIT FOR THE SERVICE RISER DOES NOT COMPLY
 WITH TABLE C-8 FOR FILL REQUIREMENT, THIS WAS REDLINED
 ON THE PREVIOUS REVIEW, PLEASE CORRECT ON THE PLAN.
 SHEET E-2.
  
 2} VERIVY CIRCUIT #3 & #4ON THE PANEL SCHEDULE, 20 AMP
 WITH #12 CONDUCTORS, LISTED A SPARE.
  
 3} CLOUD THE REVISIONS ON ALL SHEETS.
  
 4} RELOCATE THE RANGE AND WATER HEATER RECEPTACLES TO
 THEIR RELEVANT LOCATION, OR REMOVE IF NOT BEING
 INSTALLED.
  
 5} CIRCUITS #13, 15 AND 17 ARE #14 CONDUCTOR IN
 CONFLICT WITH THE ELECTRICAL SPECIFICATIONS ON SHEET
 E-4 CALLING FOR #12 CONDUCTORS MINIMUM. PLEASE
 CLARIFY.
  
 6} THE ENGINEER NEEDS TO SEAL THE PLANS SO THE
 IMPRESSION IS LEGIBLE PER 471.025 FS.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  