Plan Review Notes
Plan Review Notes For Permit 06090444
Permit Number 06090444
Review Stop E
Sequence Number 3
Notes
Date Text
2007-01-08 17:46:07 
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE
 COMPLIANCE AND RESUBMIT FOR REVIEW.
  
 1} THE NOTES ARE INDICATING 240 VOLT CIRCUITS FOR THE
 BATHROOM CIRCUIT, PLEASE CORRECT.
  
 2} THE SYMBOL ON THE PLAN AT THE WASHER INDICATES A 240
 VOLT RECEPTACLE, ALL UNITS, CORRELATE WITH SCHEDULE.
  
 3} THE SMALL APPLIANCE CIRCUIT IN EACH OF THE UNITS
 EXTENDS INTO THE LIVING ROOM IN VIOLATION OF
 210.52(B)(1).
  
 4} THE EMERGENCY LIGHTS MUST BE ON THE SAME CIRCUIT AS
 THE STAIR LIGHTING PER 700.12(E).
  
 5} THE PANELS INDICATE THEY ARE 24 POLE, BUT ONLY 18
 CIRCUITS ARE SHOWN ON EACH. PLEASE COMPLETE THE PANEL
 SCHEDULES PER 408.4.
  
 6} THE DESIGNATION FOR SMOKE DETECTORS ON THE PLAN
 INDICATES A LOW VOLTAGE ALARM TYPE SYSTEMWITH
 AUDIO/VISUAL DEVICES. PLEASE LOCATE ALL DEVICES ON THE
 PLAN.IF THESE ARE 120 VOLT ALARMS WITH BATTERY BACK UP
 PLEASE CORRECTLY DESIGNATE AS "SA" TO ELIMINATE
 CONFUSIONFOR THE INSTALLER.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW.
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]
  
 ONE SET OF PLANS IS BEING RETAINED BY THIS OFFICE.
  