Plan Review Notes For Permit 06090444
Permit Number 06090444
Review Stop P
Sequence Number 2
Notes
Date Text
2006-11-17 08:51:03DENIED;
 1.AUTOMATIC CLOTHES WASHERS ARE NOT SHOWN ON FLOOR
 PLAN, PAGE A-1 AND A-2. PLEASE ADD.
 2. AUTOMATIC CLOTHES WASHER BRANCH DRAIN IS REQUIRED TO
 BE 3". FBC-2004 PLUMBING SECTION 406.3.
 3. PLEASE SIZE ALL PIPES ON RISER DIAGRAM.
 4. ENGINEERS REQUIRED TO SIGN NOT INITIAL PLANS.
 5. WATER RISER DIAGRAM PAGE P-2. WATER HAMMER
 ARRESTORES ARE REQUIRED AT AUTOMATIC CLOTHES WASHERS.
 PLEASE SHOW ON PLANS.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695