Plan Review Notes
Plan Review Notes For Permit 06090444
Permit Number 06090444
Review Stop E
Sequence Number 2
Notes
Date Text
2006-11-14 17:20:33 
  
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE
 COMPLIANCE AND RESUBMIT FOR REVIEW.
  
 1} THE LOAD CALCULATIONS ARE SHOWN AS
 USING THE DEMAND FACTOR IN 230.31 (40%),
 AND THEN TAKING AN ADDITIONAL DEMAND
 FACTOR FROM TABLE 230.32(45%). WHILE
 EITHER ONE IS PERMISSIBLE, NOT TOGETHER.
 ALSO SEE 230.32(B) REGARDING HOUSE
 LOADS. THIS COMMENT WAS ON THE PRIOR REVIEW.
  
 2} ALL LIGHTING BRANCH CIRCUIT PANEL DESIGNATIONS ON
 SHEETS E-1 AND E-2 ARE INCORRECT.(FA #S)
  
 3} THE DISHWASHER CIRCUIT REFERENCED ON E-2 IS NOT ON
 THE PANEL SCHEDULE OR IN THE LOAD CALCULATION.
  
 4} THE WASHER/DRYER APPEARS TO BE STACKED ON THE PLAN,
 PLEASE CORRECT THE SCHEDULE.
  
 5} THE SMALL APPLIANCE CIRCUITS FOR THE KITCHEN MUST
 COMPLY WITH 210.52(B)(3), TWO IN THE KITCHEN, THERE IS
 ONLY ONE. CIRCUIT #12 MAY BE IN THE DINING ROOM, BUT
 MUST ALSO BE IN THE KITCHEN.
  
 6} THE GFI ON THE OUTSIDE IN FRONT IS IN VIOLATION OF
 210.52(B)(2), CANNO TBE ON THTE SMALL APPLIANCE
 CIRCUIT.
  
 7} THE GFI IN THE BACK OUTSIDE IS IN VIOLATION OF
 210.11(C)(3), BATH CIRCUITS.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW.
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]