Plan Review Notes
Plan Review Notes For Permit 06090444
Permit Number 06090444
Review Stop B
Sequence Number 2
Notes
Date Text
2006-11-16 07:09:23DENIED BY BUILDING
  
 1)A RECORDED COPY OF THE NOTICE OF COMMENCEMENT
 MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) SPECIFY THE STUD SPACING IN THE WALL SECTION ON
 SHEET A-5.
  
 3) ASTM C926REQUIRES STUCCO APPLIED VERTICALLY OVER
 METAL LATH WITH A SOLID BASE TO HAVE A MINIMUM
 THICKNESS OF 7/8". SEE FBC 2510.3. PLEASE CORRECT WALL
 SECTION ON A-5.
  
 4)FBC 2510.6 REQUIRES A WEATHER RESISTANT BARRIER
 OVER THE PLYWOOD BACKING BEHIND THE LATH AND STUCCO.
 PLEASE SPECIFY ON WALL SECTION ON A-5.
  
 5) THE SECOND FLOOR DEMO PLANS ON SHEET D-2 DO NOT SHOW
 THE BATHROOM WINDOWS. PLEASE CORRECT.
  
 6) PLEASE SUBMIT PRODUCT APPROVALS ( APPROVED BY THE
 D.O.R.) FOR THE STRUCTURAL WINDOW MULLIONS.
  
 7) THE WINDOW SCHEDULE ON A-1 STILL HAS ERRORS. THERE
 ARE MASONRY OPENINGS SPECIFIED THAT ARE SMALLER THAN
 THE WINDOW SIZES.PLEASE CORRECT.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved