| Plan Review Notes For Permit 06090444 |
| Permit Number |
06090444 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2006-11-16 07:09:23 | DENIED BY BUILDING | | | | | | 1)A RECORDED COPY OF THE NOTICE OF COMMENCEMENT | | | MUST BE SUBMITTED BEFORE A | | | PERMIT CAN BE ISSUED. | | | | | | 2) SPECIFY THE STUD SPACING IN THE WALL SECTION ON | | | SHEET A-5. | | | | | | 3) ASTM C926REQUIRES STUCCO APPLIED VERTICALLY OVER | | | METAL LATH WITH A SOLID BASE TO HAVE A MINIMUM | | | THICKNESS OF 7/8". SEE FBC 2510.3. PLEASE CORRECT WALL | | | SECTION ON A-5. | | | | | | 4)FBC 2510.6 REQUIRES A WEATHER RESISTANT BARRIER | | | OVER THE PLYWOOD BACKING BEHIND THE LATH AND STUCCO. | | | PLEASE SPECIFY ON WALL SECTION ON A-5. | | | | | | 5) THE SECOND FLOOR DEMO PLANS ON SHEET D-2 DO NOT SHOW | | | THE BATHROOM WINDOWS. PLEASE CORRECT. | | | | | | 6) PLEASE SUBMIT PRODUCT APPROVALS ( APPROVED BY THE | | | D.O.R.) FOR THE STRUCTURAL WINDOW MULLIONS. | | | | | | 7) THE WINDOW SCHEDULE ON A-1 STILL HAS ERRORS. THERE | | | ARE MASONRY OPENINGS SPECIFIED THAT ARE SMALLER THAN | | | THE WINDOW SIZES.PLEASE CORRECT. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 |
|