| 2006-09-20 00:00:00 | DENIED |
| | REFERENCE: FBC-2004 PLUMBING |
| | FBC-2004 FUEL GAS |
| | FBC-2004 CHAPTER 1 |
| | FLORIDA ADMINISTRATIVE CODE |
| | FLORIDA STATUTES |
| | |
| | 1. ALL ARCHITECTURAL SHEETS. THE ADDRESS |
| | FOR THE ARCHITECT SHOWN ON THE TITLE |
| | BLOCK DOES NOT REFLECT THE INFORMATION |
| | ON FILE ON DBPR WEBSITE. PLEASE |
| | CORRELATE INFORMATION AS REQUIRED IN FAC |
| | 61G1-16.004(1) BUSINESS ADDRESS. FS |
| | 481.219. (SEE ATTACHED SHEET) |
| | |
| | 2. ALL SHEETS BE AGILE ENGINEERING, INC. |
| | THE CERTIFICATE OF AUTHORIZATION IS |
| | REQUIRED IN THE TITLE BLOCK. FAC |
| | 61G15-23.002(2). FS 471.025. (SEE |
| | ATTACHED SHEET) |
| | |
| | 3. ITS NOT INDICATED IF PIPING WILL BE |
| | CHANGED OUT, BUT THE SANITARY RISER |
| | DIAGRAM DOES NOT MEET CODE REQUIREMENTS. |
| | A. THE FLOOR DRAINS ARE NOT VENTED. |
| | SECTION 1002.1 |
| | B. THE VENTS FROM THE FIRST FLOOR SHALL |
| | CONNECT, (REVENT), ABOVE THE FLOOD RIM |
| | LEVEL OF THE FIXTURES OF THE SECOND |
| | FLOOR. SECTION 905.4. |
| | C. DISH WASHERS ARE NOT TRAPPED. D/W'S |
| | SHALL CONNECT ABOVE THE TRAP OF THE |
| | KITCHEN SINK ON THE TAILPIECE. SECTION |
| | 1002.1. |
| | D. THE FIXTURES FROM THE SECOND FLOOR |
| | SHALL NOT DRAIN THRU THE FIXTURES ON THE |
| | FIRST FLOOR. SECTION 908.3. |
| | E. SECOND FLOOR FIXTURE BRANCH DRAIN |
| | CONNECTS BOTH TO THE MAIN STACK AND THE |
| | VENT STACK OF THE FIRST FLOOR FIXTURES |
| | ON ONE RISER. SECTION 106.1.1. |
| | |
| | 4. THE WATER RISER DIAGRAMS DO NOT MEET |
| | CODE REQUIREMENTS. |
| | A. WATER HAMMER ARRESTORS ARE REQUIRED |
| | ON ALL QUICK CLOSING VALVES. (AT THE |
| | DISH WASHER AND AT THE ICE MAKER IN REF) |
| | SECTION 604.9 |
| | B. WATER HEATER PIPING SHALL BE FULL |
| | SIZE TO THE SUPPLY INLET AND FROM THE |
| | OUTLET OF THE WATER HEATER. CHECK MANUF. |
| | SPECIFICATIONS. (SEE WATER HEATER |
| | DETAIL). |
| | |
| | 5. WATER HEATER DETAIL: |
| | A. PAN DRAIN TO BE 3/4" PER SECTION |
| | 504.7.1. |
| | B. P/T DISCHARGE PIPE SHALL BE FULL |
| | SIZE PER SECTION 504.6.1. |
| | C. CODE SECTION REFERENCE SHALL BE |
| | FBC-2004 PLUMBING, NOT 1997 SPC. |
| | |
| | 6. MINIMUM FACILITIES INDICATE A WASH |
| | MACHINE CONNECTION PER DWELLING UNIT, OR |
| | ONE CLOTHES WASHER CONNECTION PER 20 |
| | DWELLING UNITS IN A WASHER ROOM. PLEASE |
| | INDICATE COMPLIANCE WITH REQUIREMENT. |
| | TABLE 403.1. |
| | |
| | REVIEW BY KEN STEVENS |