Plan Review Notes
Plan Review Notes For Permit 06090444
Permit Number 06090444
Review Stop P
Sequence Number 1
Notes
Date Text
2006-09-20 00:00:00DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 FUEL GAS
 FBC-2004 CHAPTER 1
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1. ALL ARCHITECTURAL SHEETS. THE ADDRESS
 FOR THE ARCHITECT SHOWN ON THE TITLE
 BLOCK DOES NOT REFLECT THE INFORMATION
 ON FILE ON DBPR WEBSITE. PLEASE
 CORRELATE INFORMATION AS REQUIRED IN FAC
 61G1-16.004(1) BUSINESS ADDRESS. FS
 481.219. (SEE ATTACHED SHEET)
  
 2. ALL SHEETS BE AGILE ENGINEERING, INC.
 THE CERTIFICATE OF AUTHORIZATION IS
 REQUIRED IN THE TITLE BLOCK. FAC
 61G15-23.002(2). FS 471.025. (SEE
 ATTACHED SHEET)
  
 3. ITS NOT INDICATED IF PIPING WILL BE
 CHANGED OUT, BUT THE SANITARY RISER
 DIAGRAM DOES NOT MEET CODE REQUIREMENTS.
 A. THE FLOOR DRAINS ARE NOT VENTED.
 SECTION 1002.1
 B. THE VENTS FROM THE FIRST FLOOR SHALL
 CONNECT, (REVENT), ABOVE THE FLOOD RIM
 LEVEL OF THE FIXTURES OF THE SECOND
 FLOOR. SECTION 905.4.
 C. DISH WASHERS ARE NOT TRAPPED. D/W'S
 SHALL CONNECT ABOVE THE TRAP OF THE
 KITCHEN SINK ON THE TAILPIECE. SECTION
 1002.1.
 D. THE FIXTURES FROM THE SECOND FLOOR
 SHALL NOT DRAIN THRU THE FIXTURES ON THE
 FIRST FLOOR. SECTION 908.3.
 E. SECOND FLOOR FIXTURE BRANCH DRAIN
 CONNECTS BOTH TO THE MAIN STACK AND THE
 VENT STACK OF THE FIRST FLOOR FIXTURES
 ON ONE RISER. SECTION 106.1.1.
  
 4. THE WATER RISER DIAGRAMS DO NOT MEET
 CODE REQUIREMENTS.
 A. WATER HAMMER ARRESTORS ARE REQUIRED
 ON ALL QUICK CLOSING VALVES. (AT THE
 DISH WASHER AND AT THE ICE MAKER IN REF)
 SECTION 604.9
 B. WATER HEATER PIPING SHALL BE FULL
 SIZE TO THE SUPPLY INLET AND FROM THE
 OUTLET OF THE WATER HEATER. CHECK MANUF.
 SPECIFICATIONS. (SEE WATER HEATER
 DETAIL).
  
 5. WATER HEATER DETAIL:
 A. PAN DRAIN TO BE 3/4" PER SECTION
 504.7.1.
 B. P/T DISCHARGE PIPE SHALL BE FULL
 SIZE PER SECTION 504.6.1.
 C. CODE SECTION REFERENCE SHALL BE
 FBC-2004 PLUMBING, NOT 1997 SPC.
  
 6. MINIMUM FACILITIES INDICATE A WASH
 MACHINE CONNECTION PER DWELLING UNIT, OR
 ONE CLOTHES WASHER CONNECTION PER 20
 DWELLING UNITS IN A WASHER ROOM. PLEASE
 INDICATE COMPLIANCE WITH REQUIREMENT.
 TABLE 403.1.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]