| 2006-09-25 00:00:00 | |
| | |
| | NONCOMPLIANT |
| | |
| | PLEASE MAKE THE FOLLOWING CORRECTIONS |
| | FOR CODE COMPLIANCE AND RESUBMIT FOR |
| | REVIEW. |
| | |
| | 1} THE LOAD CALCULATIIONS ARE SHOWN AS |
| | USING THE DEMAND FACTOR IN 230.31 (40%), |
| | AND THEN TAKING AN ADDITIONAL DEMAND |
| | FACTOR FROM TABLE 230.32(45%). WHILE |
| | EITHER ONE IS PERMISIBLE, NOT TOGETHER. |
| | ALSO SEE 230.32(B) REGARDING HOUSE |
| | LOADS. |
| | |
| | 2} THE GROUNDING ELECTRODE CONDUCTOR IS |
| | TOO SMALL FOR THE SERVICE SHOWN AND WILL |
| | CERTAINLY BE TOO SMALL FOR THE SERVICE |
| | WHEN THE CALCULATIONS ARE ADJUSTED. SEE |
| | 250.66. |
| | |
| | 3} PLEASE LIST THE CONDUCTOR SIZES WITH |
| | THE BREAKER SIZES ON THE PANEL SCHEDULE |
| | SO THAT COMPLIANCE WITH 310.16 AND |
| | 240.CAN BE REVIEWED. |
| | |
| | 4} THERE ARE AIR HANDLERS SHOWN ON THE |
| | PLAN BUT NOT LISTED ON THE SCHEDULE OR |
| | NOT INCLUDED IN THE CALCULATIONS. PLEASE |
| | INCLUDE. |
| | |
| | 5} THE BATH CIRCUIT REQUIRED BY |
| | 210.11(C)(3)IS NOT IN THE SCHEDULE. |
| | |
| | 6} THERE APPEARS TO BE ONLY ONE SMALL |
| | APPLIANCE CIRCUIT IN THE KITCHEN, TWO |
| | ARE REQUIRED PER 210.52(B)(1). LIST SAME |
| | ON SCHEDULE. |
| | |
| | 7} BEDROOM 1 AND BEDROOM 2 CIRCUIT |
| | NUMBERS DO NOT CORRESPOND TO THE |
| | SCHEDULE . |
| | |
| | 8} SEE THAT ALL ITEMS ON PLAN SHOWN ON |
| | THE GROUNDING ELECTRODE SYSTEM MUST BE |
| | INSTALLED IF SHOWN ON PLANS , PLEASE |
| | VERIFY IF ALL ARE AVAILABLE PER |
| | 250.50-250.52. |
| | |
| | IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| | |