Plan Review Notes
Plan Review Notes For Permit 06090444
Permit Number 06090444
Review Stop E
Sequence Number 1
Notes
Date Text
2006-09-25 00:00:00 
  
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} THE LOAD CALCULATIIONS ARE SHOWN AS
 USING THE DEMAND FACTOR IN 230.31 (40%),
 AND THEN TAKING AN ADDITIONAL DEMAND
 FACTOR FROM TABLE 230.32(45%). WHILE
 EITHER ONE IS PERMISIBLE, NOT TOGETHER.
 ALSO SEE 230.32(B) REGARDING HOUSE
 LOADS.
  
 2} THE GROUNDING ELECTRODE CONDUCTOR IS
 TOO SMALL FOR THE SERVICE SHOWN AND WILL
 CERTAINLY BE TOO SMALL FOR THE SERVICE
 WHEN THE CALCULATIONS ARE ADJUSTED. SEE
 250.66.
  
 3} PLEASE LIST THE CONDUCTOR SIZES WITH
 THE BREAKER SIZES ON THE PANEL SCHEDULE
 SO THAT COMPLIANCE WITH 310.16 AND
 240.CAN BE REVIEWED.
  
 4} THERE ARE AIR HANDLERS SHOWN ON THE
 PLAN BUT NOT LISTED ON THE SCHEDULE OR
 NOT INCLUDED IN THE CALCULATIONS. PLEASE
 INCLUDE.
  
 5} THE BATH CIRCUIT REQUIRED BY
 210.11(C)(3)IS NOT IN THE SCHEDULE.
  
 6} THERE APPEARS TO BE ONLY ONE SMALL
 APPLIANCE CIRCUIT IN THE KITCHEN, TWO
 ARE REQUIRED PER 210.52(B)(1). LIST SAME
 ON SCHEDULE.
  
 7} BEDROOM 1 AND BEDROOM 2 CIRCUIT
 NUMBERS DO NOT CORRESPOND TO THE
 SCHEDULE .
  
 8} SEE THAT ALL ITEMS ON PLAN SHOWN ON
 THE GROUNDING ELECTRODE SYSTEM MUST BE
 INSTALLED IF SHOWN ON PLANS , PLEASE
 VERIFY IF ALL ARE AVAILABLE PER
 250.50-250.52.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]