| Date |
Text |
| 2006-09-18 00:00:00 | DENIED BY BUILDING |
| | |
| | 1)A RECORDED COPY OF THE NOTICE OF |
| | COMMENCEMENT MUST BE SUBMITTED BEFORE A |
| | PERMIT CAN BE ISSUED. |
| | |
| | 2) SPECIFY THE LEVEL OF ALTERATION FOR |
| | THE PROJECT. SEE 2004 FBC EXISTING |
| | BUILDING CODE CHAPTER 3. |
| | |
| | 3) BEDROOM WINDOWS MUST COMPLY WITH |
| | EMERGENCY EGRESS REQUIREMENTS OF FBC |
| | 1025. |
| | |
| | 4) THE NOTE ON SHEET A5 STATES TO FASTEN |
| | P.T. TO CONC. W/ 1/4" DIA.X 3/4"CONC. |
| | SCEWS @ 16" O.C. THAT LENGTH FASTENER |
| | WILL NOT BE SUFFICENT. PLEASE CORRECT. |
| | |
| | 5) A TAG FOR DETAIL 2/SK IS SPECIFIED ON |
| | SHEET A3. I WAS UNABLE TO LOCATE THIS |
| | DETAIL. PLEASE SPECIFY THE SHEET ON |
| | WHICH THE DETAIL IS LOCATED AS THE |
| | BOTTOM CHARACTERS OF THE ID TAG. |
| | |
| | 6) PLEASE SPECIFY THE REPAIRS THAT WILL |
| | BE DONE TO THE BALCONIES. "REPAIR AS |
| | NEEDED" IS TOO GENERAL. SEE CITY |
| | AMENDMENTS TO FBC 106.1.1. |
| | |
| | 7) ON SHEET A3 THE KITCHEN DOORS ARE |
| | SHOWN ON THE SOUTH ELEVATION WITH |
| | WINDOWS. SUBMIT PRODUCT APPROVALS FOR |
| | DOORS WITH WINDOWS AS INDICATED BY |
| | PLANS. |
| | |
| | 8) SUBMIT PRODUCT APPROVALS FOR THE |
| | VENTED STORAGE ROOM DOORS AS SHOWN ON A3 |
| | OF PLANS. |
| | |
| | 9) THE WINDOW SCHEDULE ON A2 CONTAINS |
| | SEVERAL ERRORS. |
| | - WINDOW JJ IS LOCATED IN A BEDROOM, NOT |
| | A BATHROOM. |
| | - THE MASONRY OPENING HEIGHTS ARE |
| | SMALLER THAN THE WINDOW HEIGHTS FOR |
| | SEVERAL OF THE WINDOWS LISTED. |
| | - THE WINDOW CODE SIZE FOR SEVERAL OF |
| | THE ONES LISTED SHOULD BE SH25 NOT H25. |
| | PLEASE REVIEW SCHEDULE AND CORRECT. |
| | |
| | 10) CLARIFY THE SCOPE OF WORK THAT IS |
| | INDICATED BY DETAIL 1/SK. IS THIS THE |
| | EXTERIOR WALL BEING DEMOLISHED AND |
| | REPLACED WITH A NEW WALL? IF IT IS, |
| | PROVIDE A CROSS-SECTION OF THE NEW WALL |
| | SPECIFYING EXTERIOR AND INTERIOR WALL |
| | COVERINGS, EXTERIOR SUBSTRATE, VAPOR |
| | BARRIER, INSULATION (R-VALUE), ETC. |
| | |
| | ROBERT MCDOUGAL |
| | BLDG. PLAN REVIEW |
| | (561)805-6714 |
| | |