Plan Review Notes
Plan Review Notes For Permit 06090421
Permit Number 06090421
Review Stop P
Sequence Number 2
Notes
Date Text
2006-11-15 15:22:37UNSAT 2ND TIME
 REFERENCE: FBC-2004 PLUMBING AND FBC-2004 CHAPTER 1
  
 THE FOLLOWING CORRECTIONS ARE REQUIRED FOR PLUMBING
 PLAN REVIEW TO MEET CODE COMPLIANCE:
  
 1. THE WASHING MACHINE ON THE SANITARY RISER DIAGRAM IS
 SIZED INCORRECT PER FBC-2004 PLUMBING SECTION 406.3 AND
 PLEASE INDICATE THE STANDPIPE (FBC-2004 PLUMBING
 SECTION 802.4) ON THE RESUBMITTAL.
 (A) 406.3 WASTE CONNECTIONS.THE TRAP AND
 FIXTURE DRAIN FOR AN AUTOMATIC CLOTHES
 WASHER SHALL BE A MINIMUM OF 2 INCHES
 (51MM) IN DIAMETER. THE AUTOMATIC
 CLOTHES WASHER FIXTURE DRAIN SHALL
 CONNECT TO A BRANCH DRAIN OR DRAINAGE
 STACK A MINIMUM OF 3 INCHES (76MM) IN
 DIAMETER.
 (B) 802.4 STANDPIPES.STANDPIPES SHALL BE INDIVIDUALLY
 TRAPPED. STANDPIPES SHALL
 EXTEND A MINIMUM OF 18 INCHES (457MM)
 AND A MAXIMUM OF 42 INCHES (1066MM)
 ABOVE THE TRAP WEIR. ACCESS SHALL BE
 PROVIDED TO ALL STANDPIPES AND DRAINS
 FOR RODDING. PLEASE INDICATE THE STANDPIPE ON THE
 RESUBMITTAL.
  
 2. PLEASE INDICATE A CLEANOUT FOR THE WASHING MACHINE
 AT 4' AFF PER FBC-2004 PLUMBING SECTION 708.9 ON THE
 SANITARY RISER DIAGRAM ON THE RESUBMITTAL.
  
 3. THE SPACING BETWEEN THE LAVATORY AND THE SHOWER IS
 WRONG ON THE FLOOR PLAN LAYOUT DRAWING PER FBC-2004
 PLUMBING SECTION 405.3.1. A MINIMUM OF 15" IS REQUIRED
 FROM THE LAVATORY CENTER TO THE SIDE OF THE SHOWER.
 PLEASE CORRECT THE FIXTURE SPACING ON THE RESUBMITTAL.
  
 4. FBC-2004 CHAPTER 1,SECTION 106.3.4.2:
 THE PERSON RESPONSIBLE FOR THE DESIGN OF
 THE DRAWING SHALL CLEARLY PRINT AND SIGN
 NAME, AND ALSO DATE DRAWING. PLEASE DO
 THIS PRIOR TO RESUBMITTING.
  
 **IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING,
 PLEASE REPLACE ONLY SHEETS
 WHICH HAVE CHANGED AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY. NOTE: ONLY ONE CORRECTED DRAWING
 IN RED INK FOR REFERENCE FOR
 RESUBMITTAL.
  
 END OF COMMENTS:
  